Function and Control
3.12 Malfunctions
3.12.1 Sensor Malfunction Detection
Sensor malfunction may occur either in the thermistor or current transformer (CT) system.
Relating to Thermistor Malfunction
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Fin thermistor
4. Outside air thermistor
3.12.2 Detection of Overload and Overcurrent
Outline
In order to protect the inverter, detect an excessive output current, and for protecting compressor,
monitor the OL operation.
Detail
If the OL (compressor head) temperature exceeds 266°F(130°C, depending on the
model), the compressor is interrupted.
If the inverter current exceeds 30A, the compressor is interrupted.
3.12.3 Insufficient Gas Control
Outline
There are 2 ways of control to detect insufficient gas.
I Detecting by DC current
If the DC current is below the specified value and the frequency is higher than 40 Hz, it is regarded
as insufficient gas.
The DC current is weak compared to the normal operation when gas is insufficient, and gas
insufficiency is detected by checking the DC current.
II Detecting by discharge pipe temperature
If the discharge temperature is higher than the target discharge pipe temperature, and the
electronic expansion valve is fully open more than the specified time, it is regarded as insufficient
gas.
Refer to Insufficient Gas on page 102 for details.
Frequency
DC current
Insufficient gas zone
40 Hz
(R9315)
Gas insufficient
zone
(R1391)
Содержание FTXS30HVJU
Страница 1: ...SiUS04 924 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series ...
Страница 8: ...SiUS04 924 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Страница 10: ...SiUS04 924 Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Страница 50: ...Control Specification SiUS04 924 Function and Control 43 ...
Страница 53: ...Instruction SiUS04 924 46 Operation Manual 2 Instruction 2 1 Remote Controller ...
Страница 54: ...SiUS04 924 Instruction Operation Manual 47 operation ...
Страница 55: ...Instruction SiUS04 924 48 Operation Manual 2 2 AUTO DRY COOL HEAT FAN Operation ...
Страница 56: ...SiUS04 924 Instruction Operation Manual 49 ...
Страница 58: ...SiUS04 924 Instruction Operation Manual 51 fins fins fins fins angles Inside ...
Страница 60: ...SiUS04 924 Instruction Operation Manual 53 2 5 INTELLIGENT EYE Operation fins above ...
Страница 61: ...Instruction SiUS04 924 54 Operation Manual ...
Страница 62: ...SiUS04 924 Instruction Operation Manual 55 2 6 POWERFUL Operation ...
Страница 63: ...Instruction SiUS04 924 56 Operation Manual 2 7 OUTDOOR UNIT QUIET Operation ...
Страница 64: ...SiUS04 924 Instruction Operation Manual 57 2 8 ECONO Operation ...
Страница 65: ...Instruction SiUS04 924 58 Operation Manual 2 9 TIMER Operation ...
Страница 66: ...SiUS04 924 Instruction Operation Manual 59 ...
Страница 69: ...Instruction SiUS04 924 62 Operation Manual ...
Страница 70: ...SiUS04 924 Instruction Operation Manual 63 ...
Страница 71: ...Instruction SiUS04 924 64 Operation Manual ...
Страница 72: ...SiUS04 924 Instruction Operation Manual 65 3P228444 2B ...
Страница 132: ...Indoor Unit SiUS04 924 Removal Procedure 125 10 Remove the shelter 11 Internal layout Step Procedure Points R9509 R9510 ...
Страница 193: ...SiUS04 924 187 Appendix Part 9 Appendix 1 Piping Diagrams 188 2 Wiring Diagrams 189 ...