Main Functions
SiUS04-924
Function and Control 17
1.5
Automatic Operation
Automatic Cooling / Heating Function
When the AUTO mode is selected with the remote controller, the microcomputer automatically
determines the operation mode from cooling and heating according to the room temperature and
setting temperature at the time of operation startup, and automatically operates in that mode.
The unit automatically switches the operation mode to cooling or heating to maintain the room
temperature at the main unit setting temperature.
Detailed
Explanation of
the Function
1. Remote controller setting temperature is set as automatic cooling / heating setting temperature
(64~86°F / 18~30°C).
2. Main unit setting temperature equals remote controller setting temperature.
3. Mode switching points are as follows.
Heating
Cooling switching point:
Room temperature
Main unit setting tempe5.4°F(+3.0°C).
Cooling
Heating switching point:
Room temperature < Main unit setting temperature –4.5°F(–2.5°C).
Thermostat ON / OFF point is the same as the ON / OFF point of cooling or heating
operation.
4. During initial operation
Room temperature
Remote controller setting temperature: Cooling operation
Room temperature < Remote controller setting temperature: Heating operation
Ex: When the set point is 77°F(25°C)
Cooling Operation
73.4°F(23°C): Thermostat OFF
72.5°F(22.5°C):
Switch to Heating Operation
Heating Operation
80.6°F(27°C): Thermostat OFF
82.4°F(28°C):
Switch to Cooling Operation
(R9856)
Set point +5.4ºF(+3.0ºC)
Set point –3.6ºF(–2.0ºC)
=Thermostat OFF
Set point +3.6ºF(+2.0ºC)
Heating Operation
Set point –4.5ºF(–2.5ºC)
Cooling Operation
Содержание FTXS30HVJU
Страница 1: ...SiUS04 924 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series ...
Страница 8: ...SiUS04 924 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Страница 10: ...SiUS04 924 Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Страница 50: ...Control Specification SiUS04 924 Function and Control 43 ...
Страница 53: ...Instruction SiUS04 924 46 Operation Manual 2 Instruction 2 1 Remote Controller ...
Страница 54: ...SiUS04 924 Instruction Operation Manual 47 operation ...
Страница 55: ...Instruction SiUS04 924 48 Operation Manual 2 2 AUTO DRY COOL HEAT FAN Operation ...
Страница 56: ...SiUS04 924 Instruction Operation Manual 49 ...
Страница 58: ...SiUS04 924 Instruction Operation Manual 51 fins fins fins fins angles Inside ...
Страница 60: ...SiUS04 924 Instruction Operation Manual 53 2 5 INTELLIGENT EYE Operation fins above ...
Страница 61: ...Instruction SiUS04 924 54 Operation Manual ...
Страница 62: ...SiUS04 924 Instruction Operation Manual 55 2 6 POWERFUL Operation ...
Страница 63: ...Instruction SiUS04 924 56 Operation Manual 2 7 OUTDOOR UNIT QUIET Operation ...
Страница 64: ...SiUS04 924 Instruction Operation Manual 57 2 8 ECONO Operation ...
Страница 65: ...Instruction SiUS04 924 58 Operation Manual 2 9 TIMER Operation ...
Страница 66: ...SiUS04 924 Instruction Operation Manual 59 ...
Страница 69: ...Instruction SiUS04 924 62 Operation Manual ...
Страница 70: ...SiUS04 924 Instruction Operation Manual 63 ...
Страница 71: ...Instruction SiUS04 924 64 Operation Manual ...
Страница 72: ...SiUS04 924 Instruction Operation Manual 65 3P228444 2B ...
Страница 132: ...Indoor Unit SiUS04 924 Removal Procedure 125 10 Remove the shelter 11 Internal layout Step Procedure Points R9509 R9510 ...
Страница 193: ...SiUS04 924 187 Appendix Part 9 Appendix 1 Piping Diagrams 188 2 Wiring Diagrams 189 ...