SiUS04-904
Control Specification (09/12 Class)
Function and Control
47
3.12 Malfunctions
3.12.1 Sensor Malfunction Detection
Sensor malfunction may occur in the thermistor.
Relating to Thermistor Malfunction
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Fin thermistor
4. Outdoor air thermistor
3.12.2 Detection of Overload and Overcurrent
Outline
In order to protect the inverter, detect an excessive output current, and for protecting compressor,
monitor the OL operation.
Detail
If the OL (compressor head) temperature exceeds 248°F / 120°C (depending on the
model), the compressor is interrupted.
If the inverter current exceeds 22 A, the system shuts down the compressor.
3.12.3 Refrigerant Shortage Control
Outline
There are three ways of control to detect refrigerant shortage.
I Detecting by power consumption
If the power consumption is below the specified value and the frequency is higher than the
specified frequency, it is regarded as refrigerant shortage.
The power consumption is low compared to the normal operation when refrigerant is insufficient,
and refrigerant shortage is detected by checking a power consumption.
II Detecting by discharge pipe temperature
If the discharge pipe temperature is higher than the target discharge pipe temperature, and the
electronic expansion valve is fully open (450 pulses) more than the specified time, it is regarded as
refrigerant shortage.
III Detecting by the difference of temperature
If the difference between inhale and exhale temperature is smaller than the specified value, it is
regarded as refrigerant shortage.
Refer to “Refrigerant Shortage” on page 138 for detail.
Frequency
Power consumption
Refrigerant shortage zone
55 Hz
(R2834)
Refrigerant shortage
zone
(R1391)
Содержание FTXS09HVJU
Страница 1: ...SiUS04 904 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series...
Страница 9: ...Safety Considerations SiUS04 904 viii Safety Considerations...
Страница 10: ...SiUS04 904 List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 13: ...SiUS04 904 4 Specifications Part 2 Specifications 1 Specifications 5 1 1 SEER 16 Models 5 1 2 SEER 13 Models 8...
Страница 30: ...Printed Circuit Board Connector Wiring Diagram SiUS04 904 Printed Circuit Board Connector Wiring Diagram 21...
Страница 72: ...Control Specification 15 18 24 Class SiUS04 904 62 Function and Control...
Страница 77: ...FTXS09 12HVJU SiUS04 904 66 Operation Manual...
Страница 78: ...SiUS04 904 FTXS09 12HVJU Operation Manual 67...
Страница 83: ...FTXS09 12HVJU SiUS04 904 72 Operation Manual is no longer displayed on the LCD...
Страница 84: ...SiUS04 904 FTXS09 12HVJU Operation Manual 73 is no longer displayed on the LCD...
Страница 85: ...FTXS09 12HVJU SiUS04 904 74 Operation Manual...
Страница 86: ...SiUS04 904 FTXS09 12HVJU Operation Manual 75...
Страница 87: ...FTXS09 12HVJU SiUS04 904 76 Operation Manual 3P232717 1C...
Страница 90: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 79 is no longer displayed on the LCD...
Страница 91: ...FTXS15 18 24HVJU SiUS04 904 80 Operation Manual...
Страница 94: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 83 is no longer displayed on the LCD...
Страница 95: ...FTXS15 18 24HVJU SiUS04 904 84 Operation Manual Do not hit or forcefully push the operation...
Страница 96: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 85 is no longer displayed on the LCD...
Страница 97: ...FTXS15 18 24HVJU SiUS04 904 86 Operation Manual is no longer displayed on the LCD...
Страница 98: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 87 is no longer displayed on the LCD...
Страница 99: ...FTXS15 18 24HVJU SiUS04 904 88 Operation Manual...
Страница 100: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 89...
Страница 101: ...FTXS15 18 24HVJU SiUS04 904 90 Operation Manual 3P232717 2C...