SiUS04-904
Troubleshooting
100
Service Diagnosis
4.3
Freeze-up Protection Control or High Pressure Control
Remote
Controller
Display
A5
Method of
Malfunction
Detection
High pressure control
During heating operations, the temperature detected by the indoor heat exchanger thermistor is
used for the high pressure control (stop, outdoor fan stop, etc.)
Freeze-up protection control (operation halt) is activated during cooling operation according to
the temperature detected by the indoor unit heat exchanger thermistor.
Malfunction
Decision
Conditions
High pressure control
During heating operations, the temperature detected by the indoor heat exchanger thermistor is
above 149°F
(65°C)
Freeze-up protection
When the indoor unit heat exchanger temperature is below 32°F
(0°C)
during cooling operation.
Supposed
Causes
Operation halt due to clogged air filter of the indoor unit.
Operation halt due to dust accumulation on the indoor unit heat exchanger.
Operation halt due to short-circuit.
Detection error due to faulty indoor unit heat exchanger thermistor.
Detection error due to faulty indoor unit PCB.
Содержание FTXS09HVJU
Страница 1: ...SiUS04 904 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series...
Страница 9: ...Safety Considerations SiUS04 904 viii Safety Considerations...
Страница 10: ...SiUS04 904 List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 13: ...SiUS04 904 4 Specifications Part 2 Specifications 1 Specifications 5 1 1 SEER 16 Models 5 1 2 SEER 13 Models 8...
Страница 30: ...Printed Circuit Board Connector Wiring Diagram SiUS04 904 Printed Circuit Board Connector Wiring Diagram 21...
Страница 72: ...Control Specification 15 18 24 Class SiUS04 904 62 Function and Control...
Страница 77: ...FTXS09 12HVJU SiUS04 904 66 Operation Manual...
Страница 78: ...SiUS04 904 FTXS09 12HVJU Operation Manual 67...
Страница 83: ...FTXS09 12HVJU SiUS04 904 72 Operation Manual is no longer displayed on the LCD...
Страница 84: ...SiUS04 904 FTXS09 12HVJU Operation Manual 73 is no longer displayed on the LCD...
Страница 85: ...FTXS09 12HVJU SiUS04 904 74 Operation Manual...
Страница 86: ...SiUS04 904 FTXS09 12HVJU Operation Manual 75...
Страница 87: ...FTXS09 12HVJU SiUS04 904 76 Operation Manual 3P232717 1C...
Страница 90: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 79 is no longer displayed on the LCD...
Страница 91: ...FTXS15 18 24HVJU SiUS04 904 80 Operation Manual...
Страница 94: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 83 is no longer displayed on the LCD...
Страница 95: ...FTXS15 18 24HVJU SiUS04 904 84 Operation Manual Do not hit or forcefully push the operation...
Страница 96: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 85 is no longer displayed on the LCD...
Страница 97: ...FTXS15 18 24HVJU SiUS04 904 86 Operation Manual is no longer displayed on the LCD...
Страница 98: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 87 is no longer displayed on the LCD...
Страница 99: ...FTXS15 18 24HVJU SiUS04 904 88 Operation Manual...
Страница 100: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 89...
Страница 101: ...FTXS15 18 24HVJU SiUS04 904 90 Operation Manual 3P232717 2C...