SiUS04-904
Control Specification (09/12 Class)
Function and Control
45
3.11.1 Fully Closed with Power ON
Initialize the electronic expansion valve when turning on the power, set the opening position and
develop pressure equalizing.
3.11.2 Pressure Equalization Control
When the compressor is stopped, open and close the electronic expansion valve and develop
pressure equalization.
3.11.3 Opening Limit
Outline
Limit a maximum and minimum opening of the electronic expansion valve.
Detail
A maximum electronic expansion valve opening : 450 pulses
A minimum electronic expansion valve opening : 52 pulses
The electronic expansion valve is fully closed in the room where cooling is stopped and is opened
with fixed opening during defrosting.
3.11.4 Starting Operation Control
Control the electronic expansion valve opening when the system is starting, and prevent the
system from being super heated or producing condensation.
3.11.5 High Discharge Pipe
Temperature
When the compressor is operating, if the discharge pipe temperature exceeds a certain value, open
the electronic expansion valve and run the refrigerant from the low pressure side and lower
discharge pipe temperature.
3.11.6 Disconnection of the Discharge Pipe Thermistor
Outline
Detect a disconnected discharge pipe thermistor by comparing the discharge pipe temperature with
the condensation temperature. If any are disconnected, open the electronic expansion valve
according to the outdoor air temperature and the operating frequency, operate for a specified time,
and then stop.
After 3 minutes of waiting, restart the unit and check if any are is disconnected. If any are
disconnected, stop the system after operating for a specified time. If the disconnection is detected 9
times in succession, then the system is shut down.
Detail
Detect Disconnection
If the timer for open control (cooling : 12min., heating : 15min.) goes over, and the 9-minute timer
for the compressor operation continuation is not counting time, the following adjustment must be
made.
1. When the operation mode is cooling
When the discharge pipe temperature is lower than the outdoor heat exchanger temperature,
the discharge pipe thermistor disconnection must be ascertained.
2. When the operation mode is heating
When the discharge pipe temperature is lower than the max temperature of indoor unit heat
exchanger, the discharge pipe thermistor disconnection must be ascertained.
Adjustment when the thermistor is disconnected
When the compressor stop repeats after a specified time, the system should be shut down.
Содержание FTXS09HVJU
Страница 1: ...SiUS04 904 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series...
Страница 9: ...Safety Considerations SiUS04 904 viii Safety Considerations...
Страница 10: ...SiUS04 904 List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 13: ...SiUS04 904 4 Specifications Part 2 Specifications 1 Specifications 5 1 1 SEER 16 Models 5 1 2 SEER 13 Models 8...
Страница 30: ...Printed Circuit Board Connector Wiring Diagram SiUS04 904 Printed Circuit Board Connector Wiring Diagram 21...
Страница 72: ...Control Specification 15 18 24 Class SiUS04 904 62 Function and Control...
Страница 77: ...FTXS09 12HVJU SiUS04 904 66 Operation Manual...
Страница 78: ...SiUS04 904 FTXS09 12HVJU Operation Manual 67...
Страница 83: ...FTXS09 12HVJU SiUS04 904 72 Operation Manual is no longer displayed on the LCD...
Страница 84: ...SiUS04 904 FTXS09 12HVJU Operation Manual 73 is no longer displayed on the LCD...
Страница 85: ...FTXS09 12HVJU SiUS04 904 74 Operation Manual...
Страница 86: ...SiUS04 904 FTXS09 12HVJU Operation Manual 75...
Страница 87: ...FTXS09 12HVJU SiUS04 904 76 Operation Manual 3P232717 1C...
Страница 90: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 79 is no longer displayed on the LCD...
Страница 91: ...FTXS15 18 24HVJU SiUS04 904 80 Operation Manual...
Страница 94: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 83 is no longer displayed on the LCD...
Страница 95: ...FTXS15 18 24HVJU SiUS04 904 84 Operation Manual Do not hit or forcefully push the operation...
Страница 96: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 85 is no longer displayed on the LCD...
Страница 97: ...FTXS15 18 24HVJU SiUS04 904 86 Operation Manual is no longer displayed on the LCD...
Страница 98: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 87 is no longer displayed on the LCD...
Страница 99: ...FTXS15 18 24HVJU SiUS04 904 88 Operation Manual...
Страница 100: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 89...
Страница 101: ...FTXS15 18 24HVJU SiUS04 904 90 Operation Manual 3P232717 2C...