5.11.1 Initialization as Power Supply On
The electronic expansion valve is initialized (fully closed) when the power is turned on. Then, the
valve opening position is set and the pressure is equalized.
5.11.2 Pressure Equalizing Control
When the compressor is stopped, the pressure equalizing control is activated. The electronic
expansion valve opens, and develops the pressure equalization.
5.11.3 Opening Limit Control
The maximum and minimum opening of the electronic expansion valve are limited.
The electronic expansion valve is fully closed when cooling operation stops, and is opened at a
fixed degree during defrosting.
5.11.4 Starting Operation Control
The electronic expansion valve opening is controlled when the operation starts, thus preventing
superheating or liquid compression.
5.11.5 Control when the Frequency Changes
When the target discharge pipe temperature control is active, if the target frequency changes to a
specified value in a certain time period, the target discharge pipe temperature control is canceled
and the target opening of the electronic expansion valve is changed according to the frequency
shift.
5.11.6 High Discharge Pipe Temperature Control
When the compressor is operating, if the discharge pipe temperature exceeds a certain value, the
electronic expansion valve opens and the refrigerant runs to the low pressure side.
This procedure lowers the discharge pipe temperature.
09/12 class
15 class
18/24 class
Maximum opening (pulse)
470
480
490
Minimum opening (pulse)
32
52
52
Содержание FTX-N Series
Страница 14: ...SiUS091601EA 9 Part 1 General Information 1 Applicable Models 10 2 Functions 11 Part 1 General Information...
Страница 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications...
Страница 132: ...Troubleshooting for FTX FVXS Series SiUS091601EA 127 Part 6 Service Diagnosis Reference Check No 01 Refer to P 181...
Страница 161: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 156 Reference Check No 14 Refer to P 185...
Страница 165: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 160 Reference Check No 18 Refer to P 190...
Страница 180: ...Troubleshooting for Outdoor Unit SiUS091601EA 175 Part 6 Service Diagnosis Reference Check No 19 Refer to P 191...
Страница 197: ...SiUS091601EA Check Part 6 Service Diagnosis 192 12 class 15 class Multimeter R23024 R25105 1 2 3 4 Multimeter...
Страница 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter...
Страница 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U...
Страница 228: ...Piping Diagrams SiUS091601EA 223 Part 8 Appendix 1 2 Outdoor Unit RXL09QMVJU RXL12QMVJU 9 3D100008 3D100009A...
Страница 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368...
Страница 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A...