Troubleshooting for Outdoor Unit
SiUS091601EA
163
Part 6 Service Diagnosis
Reference
7.7 Discharge Pipe Temperature Control
Error Code
F3
Method of Error
Detection
An error is determined with the temperature detected by the discharge pipe thermistor.
Error Decision
Conditions
If the temperature detected by the discharge pipe thermistor rises above
A
, the compressor
stops.
The error is cleared when the discharge pipe temperature has dropped below
B
.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
If the frequency drops, the temperature is lowered in compensation.
Supposed
Causes
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Troubleshooting
Check No.01
A
B
(°C)
(°F)
(°C)
(°F)
09 class
110
230
88
190.4
A
B
(°C)
(°F)
(°C)
(°F)
12/18/24 class
120
248
107
224.6
15 class
110
230
95
203
(R20417)
Caution
NG
OK
OK
OK
NG
NG
∗
Discharge pipe thermistor
∗
Outdoor heat exchanger thermistor
∗
Outdoor temperature thermistor
∗
Refrigerant shortage
∗
Four way valve
∗
Water mixed
∗
Stop valve
Check No. 12
Check the electronic
expansion valve.
Replace the defective
thermistor(s).
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.
Содержание FTX-N Series
Страница 14: ...SiUS091601EA 9 Part 1 General Information 1 Applicable Models 10 2 Functions 11 Part 1 General Information...
Страница 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications...
Страница 132: ...Troubleshooting for FTX FVXS Series SiUS091601EA 127 Part 6 Service Diagnosis Reference Check No 01 Refer to P 181...
Страница 161: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 156 Reference Check No 14 Refer to P 185...
Страница 165: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 160 Reference Check No 18 Refer to P 190...
Страница 180: ...Troubleshooting for Outdoor Unit SiUS091601EA 175 Part 6 Service Diagnosis Reference Check No 19 Refer to P 191...
Страница 197: ...SiUS091601EA Check Part 6 Service Diagnosis 192 12 class 15 class Multimeter R23024 R25105 1 2 3 4 Multimeter...
Страница 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter...
Страница 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U...
Страница 228: ...Piping Diagrams SiUS091601EA 223 Part 8 Appendix 1 2 Outdoor Unit RXL09QMVJU RXL12QMVJU 9 3D100008 3D100009A...
Страница 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368...
Страница 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A...