Check
SiUS091601EA
181
Part 6 Service Diagnosis
Note(s)
8. Check
8.1 Thermistor Resistance Check
Check No.01
Measure the resistance of each thermistor using multimeter.
The resistance values are defined by below table.
If the measured resistance value does not match the listed value, the thermistor must be replaced.
Disconnect the connector of thermistor ASSY from the PCB to measure the resistance between
the pins using multimeter.
To check the thermistor soldered on a PCB, disconnect the PCB from other PCB/parts, and
measure the resistance between the both ends of soldered thermistor.
R6000680
When replacing the defective thermistor(s), replace the thermistor as ASSY.
Thermistor
FTX09/12/15
NMVJU
FTX18/24UVJU
FVXS series
FDMQ series
Indoor
Unit
R1T
Room temperature thermistor
B
A
—
R2T
Indoor heat exchanger thermistor
A
A
—
R1T
Suction air thermistor
—
—
A
R2T
Middle thermistor
—
—
A
R3T
Liquid pipe thermistor
A
A
A
Outdoor
Unit
R1T
Outdoor air temperature thermistor
A
A
A
R2T
Outdoor heat exchanger thermistor
A
A
A
R3T
Discharge pipe thermistor
A
A
A
Multimeter
Resistance range
Thermistor ASSY
Soldered thermistor
Multimeter
R(25°C / 77°F) = 10 k
:
, B = 3435 K
R(25°C / 77°F) = 20 k
:
, B = 3950 K
Thermistor
temperature
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
R(25°C / 77°F) = 10 k
:
B = 3435 K
Type B
73.4
57.0
44.7
35.3
28.2
22.6
18.3
14.8
12.1
10.0
8.2
6.9
5.8
4.9
4.1
R(25°C / 77°F) = 20 k
:
B = 3950 K
Type A
197.8
148.2
112.1
85.60
65.93
51.14
39.99
31.52
25.02
20.00
16.10
13.04
10.62
8.707
7.176
50
–4
5
14
23
32
41
50
59
68
77
86
95
104
113
122
°C
°F
(˚C)
(k
Ω
)
–15
0
15
30
45
150
100
50
(˚F)
5
32
59
86
113
(˚C)
(˚F)
50
25
0
–15
5
32
59
86
113
0
15
30
45
(k
Ω
)
Содержание FTX-N Series
Страница 14: ...SiUS091601EA 9 Part 1 General Information 1 Applicable Models 10 2 Functions 11 Part 1 General Information...
Страница 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications...
Страница 132: ...Troubleshooting for FTX FVXS Series SiUS091601EA 127 Part 6 Service Diagnosis Reference Check No 01 Refer to P 181...
Страница 161: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 156 Reference Check No 14 Refer to P 185...
Страница 165: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 160 Reference Check No 18 Refer to P 190...
Страница 180: ...Troubleshooting for Outdoor Unit SiUS091601EA 175 Part 6 Service Diagnosis Reference Check No 19 Refer to P 191...
Страница 197: ...SiUS091601EA Check Part 6 Service Diagnosis 192 12 class 15 class Multimeter R23024 R25105 1 2 3 4 Multimeter...
Страница 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter...
Страница 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U...
Страница 228: ...Piping Diagrams SiUS091601EA 223 Part 8 Appendix 1 2 Outdoor Unit RXL09QMVJU RXL12QMVJU 9 3D100008 3D100009A...
Страница 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368...
Страница 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A...