SiUS091601EA
Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis
158
Reference
7.4 DC Fan Lock
Error Code
E7
Method of Error
Detection
An error is determined with the high-voltage fan motor rotation speed detected by the Hall IC.
Error Decision
Conditions
The fan does not start in 15 ~ 30 seconds even when the fan motor is running.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Disconnection of the fan motor
Foreign matter stuck in the fan
Defective fan motor
Defective outdoor unit PCB
Troubleshooting
Check No.16
(R21669)
Caution
YES
YES
NO
YES
NO
NO
YES
NO
NO
Turn on the power.
Rotate the fan.
YES
Check No. 16
Check the rotation pulse input on
the outdoor unit PCB (main PCB).
Turn off the power and
reconnect the connector.
Remove the foreign
matters.
Replace the outdoor fan
motor.
Replace the fuse.
Replace the outdoor unit
PCB (main PCB).
Fan motor
connector disconnected?
Foreign matters
in or around the fan?
Replace the outdoor fan
motor.
Fan rotates
smoothly?
Pulse signal
generated?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the fuse (
#
) for the
fan motor blown?
#
FU2
Содержание FTX-N Series
Страница 14: ...SiUS091601EA 9 Part 1 General Information 1 Applicable Models 10 2 Functions 11 Part 1 General Information...
Страница 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications...
Страница 132: ...Troubleshooting for FTX FVXS Series SiUS091601EA 127 Part 6 Service Diagnosis Reference Check No 01 Refer to P 181...
Страница 161: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 156 Reference Check No 14 Refer to P 185...
Страница 165: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 160 Reference Check No 18 Refer to P 190...
Страница 180: ...Troubleshooting for Outdoor Unit SiUS091601EA 175 Part 6 Service Diagnosis Reference Check No 19 Refer to P 191...
Страница 197: ...SiUS091601EA Check Part 6 Service Diagnosis 192 12 class 15 class Multimeter R23024 R25105 1 2 3 4 Multimeter...
Страница 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter...
Страница 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U...
Страница 228: ...Piping Diagrams SiUS091601EA 223 Part 8 Appendix 1 2 Outdoor Unit RXL09QMVJU RXL12QMVJU 9 3D100008 3D100009A...
Страница 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368...
Страница 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A...