Functions of Heat Pump Models
Si01-406
36
Functions and Control
2.7
Powerful Operation
Outline
In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed.
Details of the
Control
When Powerful button is pushed in each operation mode, the fan speed / setting temperature
will be converted to the following states in a period of twenty minutes.
Ex.) : Powerful operation in cooling mode.
Operation mode
Fan speed
Target set temperature
Cooling
H tap + 90 rpm
18°C
Dry
Dry rotating speed +
50 rpm
Normally targeted
temperature in dry
operation; Approx. –2°C
Heating
H tap + 90 rpm
30°C
Fan
H tap + 90 rpm
—
Automatic
Same as cooling /
heating in Powerful
operation
The target is kept
unchanged
(R2823)
Target temp.
Fan
80rpm
Set temp.
18˚C
Powerful ON
Powerful OFF
H tap
Set tap
It should be the lower limit of cooling temperature.
It counts 20 min. also in the remote controller.
Ending condition: "or" in 1 to 3
1. TPF ends.
2. Stop
3. Powerful operation is OFF.
TPF=(20min.)
Содержание FT25CV1A
Страница 7: ...Si01 406 vi Table of Contents...
Страница 15: ...Functions Si01 406 4 List of Function...
Страница 21: ...Specifications Si01 406 10 Specifications...
Страница 31: ...Printed Circuit Board Connector Wiring Diagram Si01 406 20 Printed Circuit Board Connector Wiring Diagram...
Страница 189: ...R50 60CV1A Si01 406 178 Removal Procedure 6 Remove the screw 7 Take off the electrical parts box Step Procedure Points...
Страница 205: ...Wiring Diagrams Si01 406 194 Appendix...
Страница 209: ...Si01 406 iv Index...