Field Settings
SiBE05-722_B
217
Trial Operation and Field Settings
4.3
Facility Setting Jumper (cooling at low outdoor
temperature)
Outline
For Cooling Only Model
This function is limited only for facilities (the target of air conditioning is equipment (such as
computer)). Never use it in a residence or office (the space where there is a human).
Detail
You can expand the operation range to –15°C by cutting jumper on the outdoor unit PCB. If the
outdoor temperature falls to –20°C or lower, the operation stops. If the outdoor temperature
rises, the operation starts again.
RKS25/35E2V1B
RKS25/35G2V1B
RKS25/35G2V1B9
Caution
1. If the outdoor unit is installed where the outdoor heat exchanger of the unit is exposed to
direct wind, provide a windbreak wall.
2. Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and
off when using facility settings.
3. Do not place humidifiers or other items which might raise the humidity in rooms where facility
settings are being used.
1
2
3
PCB
J1
J3
J4
J5
J6
J7
J8
S80
S80
S80
S90
S70
.
(R12420)
Cut J8 with nippers
or a similar tools
1
2
3
S90
PCB
S50
S20
S10
S1
J4
J8
J9
Cut the jumper J8.
(R12206)
1
2
3
S70
S40
S2
S90
J5
J4
J3
(R12187)
Cut the jumper J4.