ESIE02–01
General Functionality
Part 2 – Functional Description
2–9
3
2
4
5
1
Time chart
The time chart below illustrates emergency operation.
■
In cooling, the unit runs for 20 min and then stops for 10 min in order to avoid freeze-up of the
indoor coil.
■
During emergency operation, do not attempt to operate the equipment from the remote control.
The remote control shows
88
while the emergency operation is active on the indoor unit.
Active components
The table below shows when the most important components are active in the different forced
operating modes.
Additional info
To avoid misunderstandings, take the following into account:
■
If the PCB or the motorized valve is malfunctioning, emergency operation cannot be carried out.
■
No signal is transmitted between the indoor and outdoor units and remocon.
■
If a safety device should be activated during emergency operation, all actuators are turned OFF.
■
“Heat” cannot be set for c/o air conditioners.
■
Emergency operation uses (and switches ON) both indoor and outdoor control PCBs. The outdoor
control PCB determines the changeover.
■
In heating, defrosting is activated once every hour.
Power supply
Motorized valve
4-way valve
Compressor
Solenoid valve
Fully closed
10 s
60 s
Outdoor unit fan
Component
Forced cooling
Forced heating
Forced defrosting
Compressor
ON
ON
ON
4-way valve
■
RY35-45E(A)Z7V1: ON
■
RYP71-250B: OFF
■
RY35-45E(A)Z7V1: OFF
■
RYP71-250B: ON
■
RY35-45E(A)Z7V1: ON
■
RYP71-250B: OFF
Outdoor unit fan
H fan speed
H fan speed
OFF
Indoor unit fan
H fan speed
H fan speed
H fan speed
Drain pump
ON
OFF
ON
Содержание FHC45BZ7V1
Страница 1: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Страница 2: ......
Страница 3: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Страница 4: ......
Страница 16: ...Introduction ESIE02 01 xii 3 1 4 5...
Страница 18: ...ESIE02 01 1 2 Part 1 System Outline 3 1 1 5...
Страница 42: ...General Outline Outdoor Units ESIE02 01 1 26 Part 1 System Outline 3 1 1 4 5...
Страница 49: ...ESIE02 01 General Outline Indoor Units Part 1 System Outline 1 33 3 1 4 5...
Страница 72: ...General Outline Indoor Units ESIE02 01 1 56 Part 1 System Outline 3 1 1 4 5...
Страница 86: ...Specifications ESIE02 01 1 70 Part 1 System Outline 3 1 1 4 5...
Страница 110: ...ESIE02 01 1 94 Part 1 System Outline...
Страница 130: ...Switch Box Layout ESIE02 01 1 114 Part 1 System Outline 3 1 1 4 5...
Страница 180: ...PCB Layout ESIE02 01 1 164 Part 1 System Outline 3 1 1 4 5...
Страница 182: ...ESIE02 01 2 2 Part 2 Functional Description 3 1 2 5...
Страница 204: ...General Functionality ESIE02 01 2 24 Part 2 Functional Description 3 1 2 4 5...
Страница 216: ...Overview of the cooling mode functions ESIE02 01 2 36 Part 2 Functional Description 3 1 2 4 5...
Страница 232: ...ESIE02 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 294: ...Error Codes System Malfunctions ESIE02 01 3 64 Part 3 Troubleshooting 3 1 3 4 5...