General Functionality
ESIE02–01
2–16
Part 2 – Functional Description
3
1
2
4
5
1.11
Discharge Pipe Temperature Control
Applicable units
R(Y)P71-250B
Purpose
The purpose of the discharge pipe temperature control is to prevent a discharge pipe temperature that
is too high or too low.
Low temp.
starting conditions
The table below contains the low temperature conditions to start the discharge pipe temperature
control.
High temp.
starting conditions
The table below contains the high temperature conditions to start the discharge pipe temperature
control.
Used input
The discharge pipe temperature control uses the following inputs:
Function
Description
Starting conditions
F3-error occurs if
the conditions...
Wet operation
Prevents liquid suction to
the compressor.
■
Change in E.V. opening
< 50 pulses
■
Td < Tc + 10˚C
Are met for 15 min
continuously.
Thermistor
out
Detects if the discharge
thermistor is not in the cor-
rect position.
■
Td < 55˚C
■
After start-up + 5 min:
-
∆
Td
≤
5 K
- Td < Ta + 10˚C
Are repeated 6
times.
Function / description
Starting conditions
F3-error occurs if
the conditions...
Detects too high discharge gas
temperatures.
Td
≥
125˚C for 20 s continuously
Are repeated 6
times.
Input
Connection on
indoor PCB
Connection on
outdoor PCB
Outdoor discharge thermistor
—
R3T-X6A
Outdoor heat exchanger thermistor
—
R2T-X5A
Indoor heat exchanger thermistor
R2T-X18A
—
Содержание FHC45BZ7V1
Страница 1: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Страница 2: ......
Страница 3: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Страница 4: ......
Страница 16: ...Introduction ESIE02 01 xii 3 1 4 5...
Страница 18: ...ESIE02 01 1 2 Part 1 System Outline 3 1 1 5...
Страница 42: ...General Outline Outdoor Units ESIE02 01 1 26 Part 1 System Outline 3 1 1 4 5...
Страница 49: ...ESIE02 01 General Outline Indoor Units Part 1 System Outline 1 33 3 1 4 5...
Страница 72: ...General Outline Indoor Units ESIE02 01 1 56 Part 1 System Outline 3 1 1 4 5...
Страница 86: ...Specifications ESIE02 01 1 70 Part 1 System Outline 3 1 1 4 5...
Страница 110: ...ESIE02 01 1 94 Part 1 System Outline...
Страница 130: ...Switch Box Layout ESIE02 01 1 114 Part 1 System Outline 3 1 1 4 5...
Страница 180: ...PCB Layout ESIE02 01 1 164 Part 1 System Outline 3 1 1 4 5...
Страница 182: ...ESIE02 01 2 2 Part 2 Functional Description 3 1 2 5...
Страница 204: ...General Functionality ESIE02 01 2 24 Part 2 Functional Description 3 1 2 4 5...
Страница 216: ...Overview of the cooling mode functions ESIE02 01 2 36 Part 2 Functional Description 3 1 2 4 5...
Страница 232: ...ESIE02 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 294: ...Error Codes System Malfunctions ESIE02 01 3 64 Part 3 Troubleshooting 3 1 3 4 5...