background image

 

D-EIMHP01505-22_00EN 29/59 

 

5.  ELECTRICAL INSTALLATION 

5.1.  General specifications 

Refer to the specific wiring diagram for the unit you have bought. Should the wiring diagram not be on the unit, or should 
it have been lost, please contact your manufacturer representative, who will send you a copy. 
In  case  of  discrepancy  between  wiring  diagram  and  electrical  panel/cables,  please  contact  the  manufacturer 
representative. 
 

 

▪ Be sure to keep the power line and transmission line apart from each other. Transmission wiring 
and power supply wiring may cross but may not run parallel. 
▪ Transmission wiring and power supply wiring may not touch internal piping in order to avoid wire 
damage due to high temperature piping. 
▪ Firmly close the lid and arrange the electrical wires to prevent the lid or other parts from coming 
loose.
 

 
▪  Be  sure  to  follow  the  limits  below.  If  the  unit-to-unit  cables  are  beyond  these  limits,  it  may  result  in  malfunction  of 
transmission: 
▪ Maximum wiring length: 30 m. 
▪ Total wiring length: 30 m. 
For the wiring above, always use vinyl cords with 0.75 to 1.25 mm

2

 sheath or cables (2-core wires). (3-core wire cables 

are allowable for the cooler/heater changeover user interface only.) 
 
Electrical  equipment  is  capable  of  operating  correctly  in  the  intended  ambient  air  temperature.  For  very  hot/cold 
environments  (refer  to  4.13, 

“Operation  limits”),  additional  measures  are  recommended  (contact  the  manufacturer 

representative). 
The electrical equipment is capable of operating correctly when the relative humidity does not exceed 50% at a maximum 
temperature of +40 °C. Higher relative humidity are permitted at lower temperatures (for example 90% at 20 °C). 

5.2.  Electric connections 

Provide an electrical circuit to connect the unit. It must be connected to the copper cables with an adequate section relative 
to the absorption values and according to the current electrical standards. 
Daikin Applied Europe S.p.A. declines all responsibility for an inadequate electrical connection. 
 

 

The  connections  to  the  terminals  must  be  made  with  copper  terminals  and  cables,  otherwise 
overheating or corrosion may occur at the connection points with the risk of damaging the unit. The 
electrical connection must be carried out by qualified personnel, in compliance with the laws in force. 
There is a risk of electric shock. 

The power supply to the unit must be set up in such a way that it can be switched on or off independently from that of other 
system components and other equipment in general, by means of a general switch. 
The electrical connection of the panel must be carried out maintaining the correct sequence of the phases. Refer to the 
specific  wiring  diagram  for  the  unit  you  have  bought.  In  case  of  discrepancy  between  the  wiring  diagram  and  electrical 
panel/cables, please contact the manufacturer representative. 
 

 

Do  not  apply  torque,  tension  or  weight  to  the  main  switch  terminals.  Power  line  cables  must  be 
supported by appropriate systems

.

 

To  avoid  interference,  all  control  wires  must  be  connected  separately  from  the  power  cables.  To  do  this,  use  several 
electrical passage ducts. 
The protections for the power supply system must be designed according to the values mentioned above. A fuse must be 
present on each phase and, where provided for by the national laws of the country of installation, a leak detector to earth.  
 

 

Before any electrical connection work to the compressor motor and / or the fans, make sure that the 
system is switched off and the main switch of the unit is open. 
Failure to observe this rule could result in serious personal injury. 

5.3.  Cable requirements 

The cables connected to the circuit breaker must respect the insulation distance in the air and the surface isolation distance 
between the active conductors and the earth, according to IEC 614391 table 1 and 2, and to the local national laws. The 
cables connected to the main switch must be tightened using a pair of keys and respecting the unified clamping values, 
relative to the quality of the screws of the washers and nuts used. 
Connect the earth conductor (yellow / green) to the PE ground terminal. 
The equipotential protection conductor (earth conductor) must have a section according to table 1 of EN 602041 Point 5.2, 
shown below. 

Содержание EWYT021CZI-A1

Страница 1: ...505 22_00EN 1 59 REV 00 Date 31 05 2022 Supersedes Air to water heat pump units with scroll compressors split version EWYT CZ I O Original Instructions Installation and Maintenance Manual D EIMHP01505...

Страница 2: ...s 19 4 6 Combining Units and Options 20 4 7 Preparing Refrigerant Piping 20 4 8 Noise and sound protection 22 4 9 Water circuit for connection with the unit 22 4 9 1 Water piping 23 4 9 2 Flow switch...

Страница 3: ...ing 16 Figure 6 Mounting holes location bottom view 16 Figure 7 DUAL unit 17 Figure 8 Units installed side by side along their shorter sides B or D 18 Figure 9 Units installed side by side along their...

Страница 4: ...23 Table 10 Acceptable water quality limits 24 Table 11 Pump curves associated with each unit size 25 Table 12 Minimum water content in the system 26 Table 13 Operating limits 27 Table 14 Table 1 of E...

Страница 5: ...measures to prevent them from starting up 9 The surfaces of the machine and pipes can get very hot or cold and cause the risk of scalding 10 Never exceed the maximum pressure limit PS of the water ci...

Страница 6: ...indoor units shall be electrically connected refer to the wiring diagram supplied with the units Cooling or Conditioning Mode One or more scroll compressors which increase the pressure of the refrige...

Страница 7: ...e the detector will automatically trigger the shut down of the unit to prevent accidents Furthermore the emergency fan will also be triggered and turned on in order to disperse the refrigerant This un...

Страница 8: ...r leakage Appliance NOT accessible to the public install it in a secured area protected from easy access This unit is suitable for installation in a commercial and light industrial environment 1 5 1 I...

Страница 9: ...ot Lowest Underground Floor If the indoor unit is installed in the lowest underground floor the maximum refrigerant quantity with respect to the flammability value shall be evaluated through the follo...

Страница 10: ...st underground floor installation CF Concentratiom factor for Not Lowest Undergroud Floor CF 0 5 LFL Lower Flammability Limit for R32 LFL 0 307 kg m3 H Room Height but not more than 2 2 m A Room Area...

Страница 11: ...is installed at not more than 100 mm from the floor Openings are permanent and cannot be closed The height of the opening between the wall and floor which the rooms are not less than 20 mm A second h...

Страница 12: ...s location as well as the occupied space Rooms parts of buildings building where sleeping facilities are provided Rooms parts of buildings building where people are restricted in their movement Rooms...

Страница 13: ...ling the unit to prevent damage to components Before installing the unit check that the model and power supply voltage shown on the nameplate are correct Responsibility for any damage after acceptance...

Страница 14: ...unit to fall during transportation or loading unloading Equipment ropes lifting accessories and handling procedures must comply with local regulations and current legislation The ropes and hooks used...

Страница 15: ...ifting the Outdoor DUAL unit Figure 2 Lifting the outdoor DUAL unit 4 2 3 Lifting the INDOOR unit A forklift can only be used for transport as long as the unit remains on its pallet as shown above Fig...

Страница 16: ...ecessary to use weight distribution beams For installation on the ground a strong concrete base at least 150 mm thickness and wider than the unit must be provided This base must be able to support the...

Страница 17: ...units to ensure optimum ventilation to the condenser coils When deciding where to position the unit and to ensure a proper air flow the following factors must be taken into consideration avoid any war...

Страница 18: ...to adapt itself to new operating conditions and deliver the maximum available capacity under any given circumstances even if the lateral distance is lower than the recommended unless the operating con...

Страница 19: ...pace requirements Figure 10 Indoor Unit minimum space requirements The indoor unit and the equipment pipes shall be installed in such a way that it shall be protected against accidental damage in the...

Страница 20: ...to wind and snow install a baffle plate on the air side of the outdoor unit in heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit If later...

Страница 21: ...16 00 mm 1 00 mm 22 20 mm 1 10 mm 28 6 mm 1 15 mm Table 5 Pipe thickness for R32 To select the piping size Determine the proper size using the following tables and reference figure only for indicatio...

Страница 22: ...pressors and fans The noise level for each model size is listed in sales documentation If the unit is correctly installed operated and maintained the noise emission level do not require any special pr...

Страница 23: ...witch The purpose of the flow switch is to stop the unit in the event of interrupted water flow thus protecting the BPHE from freezing This is a palette flow switch appropriate for uninterrupted use o...

Страница 24: ...le for damage to or malfunctioning of equipment caused by failure to treat water or by improperly treated water In the following table are listed the acceptable water quality limits DAE Water quality...

Страница 25: ...T032CZI A1 B EWYT040CZI A1 B EWYT064CZI A2 C Table 11 Pump curves associated with each unit size 4 13 Operation limits Operation out of the mentioned limits may damage the unit In case of any doubt co...

Страница 26: ...of the compressor stator generated by the inrush current of the starting In order to prevent damage to the compressor the control system will therefore permit no more than 10 startups per hour The pla...

Страница 27: ...is 2 5 1 5 1 67 and so to calculate the minimum water content in the system for a 21 kW unit all we need to do is multiple the default minimum volume by this correction factor to obtain the new minim...

Страница 28: ...n the expansion vessel An inappropriate initial pressure setting in the expansion vessel will result in malfunctioning of the system Changes to the initial pressure of the expansion vessel must be mad...

Страница 29: ...nals must be made with copper terminals and cables otherwise overheating or corrosion may occur at the connection points with the risk of damaging the unit The electrical connection must be carried ou...

Страница 30: ...ety device requirements The power supply must be protected with a Residual current device as indicated in the table below Main switch and Fuses can be added in accordance with the applicable legislati...

Страница 31: ...and 392 V respectively The average is 383 386 392 3 387 The unbalance percentage is 392 387 100 387 less than the maximum allowed 3 5 5 Master Wiring Diagram The following electric diagram shows the b...

Страница 32: ...63 A D125 Table 15 Reference No 1 UNIT NOMINAL CURRENT SIZE CIRCUIT BREAKER Q I Unit In A Idn mA EWYT021CZI A1 C13 300 Type A EWYT032CZI A1 C13 300 Type A EWYT040CZI A1 C13 300 Type A EWYT064CZI A2 C1...

Страница 33: ...solute Then once the vacuum is completed let the system in vacuum for at least 2 hours After that pressurise the system with nitrogen gas to a maximum gauge pressure of 4 0 MPa 40 bar Never set the ga...

Страница 34: ...the piping system it is necessary to remove the seal plugs Figure 23 Ball Valve Before removing the plugs on the piping connections ensure that the ball valves are in CLOSED position Before removing t...

Страница 35: ...may cause damage to them Once successfully performed the leak test and verified that no refrigerant is present within the piping that needs to be brazed it is possible to connect the piping system to...

Страница 36: ...y Toxic gas may be produced if refrigerant gas comes into contact with fire NEVER directly touch any accidental leaking refrigerant This could result in severe wounds caused by frostbite 6 4 To connec...

Страница 37: ...with a non return valve that can evacuate to a gauge pressure of 100 7 kPa 1 007 bar 5 Torr absolute Make sure the pump oil does not flow oppositely into the system while the pump is not working Use t...

Страница 38: ...at the expansion valve within the indoor unit i e the one used in chiller mode is set to 100 OPEN Otherwise it would not be possible to perform a vacuum on the whole refrigerant circuit To set the ope...

Страница 39: ...gerant without turning on the water pump Be sure to turn on the power 6 hours before operation in order to have power running to the crankcase heater and to protect the compressor Make sure that the b...

Страница 40: ...charge pre charge which differs for each unit Once installed the technician shall add the extra quantity based on the formula above mentioned 3 Once the additional refrigerant quantity has been added...

Страница 41: ...erant charge added C1 D total refrigerant charge Pre Add C1 E total refrigerant charge added C2 only for dual version F total refrigerant charge Pre Add C2 only for dual version G total tCO2 eq added...

Страница 42: ...care to keep this equipment in good working order However during operation and maintenance it is essential to observe the following instructions Do not allow unauthorized and or unqualified personnel...

Страница 43: ...of high voltage due to firing of the capacitors refrigerating system The following precautions should be taken before working on the refrigerant circuit obtain permit for hot work if required ensure t...

Страница 44: ...sk of sandstorms Combinations of the above Unit exposed to a highly aggressive environment can face corrosion in a shorter time than the ones installed on a standard environment Corrosion causes a rap...

Страница 45: ...the water flow rate X Check the safety valve X Coil section Outdoor Unit Check the cleaning of coils and water heat exchangers Note 5 X Verify that fans are well tightened X Verify the coil fins X BP...

Страница 46: ...he unit allows maintaining high observational standards 10 Check for any dissolved metals 11 Clean condenser banks with clean water and water heat exchangers with appropriate chemicals Particles and f...

Страница 47: ...cked to make sure that they interrupt the control circuit if they intervene 8 2 3 Service and limited warranty All units are factory tested and guaranteed for 12 months as of the first start up or 18...

Страница 48: ...D EIMHP01505 22_00EN 48 59 9 REFRIGERANT CIRCUIT SCHEME Figure 24 Refrigerant circuit P ID diagram for MONO circuit EWYT CZ unit...

Страница 49: ...EXV LIQUID RECEIVER L5 LIQUID RECEIVER OUT L6 BPHE EXCHANGER 4 WAY VALVE L7 SUCTION L8 LIQUID SUBCOOLER L9 SUBCOOLER COMPRESSOR L10 CHECK VALVE LINE L11 BPHE COMPRESSOR INDOOR UNIT L12 SUBCOOLER BOHE...

Страница 50: ...25 Water Circuit P ID for EWYT CZ Units WATER CIRCUIT EQUIPMENT a PUMP d DRAIN e PLUGGED FITTING f SAFETY VALVE 3 BAR g SHUT OFF VALVE h AIR VENT m EXPANSION VESSEL y AIR FILTER TT TEMPERATURE SENSOR...

Страница 51: ...D EIMHP01505 22_00EN 51 59 Figure 26 Refrigerant circuit P ID diagram for DUAL circuit EWYT CZ outdoor unit...

Страница 52: ...00EN 52 59 Figure 27 Refrigerant circuit P ID diagram for DUAL circuit EWYT CZ indoor unit REFRIGERANT PED GROUP LINE PS bar Ts C R32 1 HIGH PRESSURE GAS 42 9 10 120 HIGH PRESSURE LIQ 42 9 10 65 LOW P...

Страница 53: ...ting holes Unit ID plate information On the unit frame outside UN 3358 labels On the packaging Circuit 1 2 Label On the refrigerant side connections panel Water outlet On the unit panel near the outle...

Страница 54: ...D EIMHP01505 22_00EN 54 59 Figure 28 Labels on the outdoor unit Figure 29 Labels on the indoor unit...

Страница 55: ...D EIMHP01505 22_00EN 55 59 Figure 30 Labels on the indoor unit Electric panel side...

Страница 56: ...trols 3way valves bypass valves etc operable Flow switch installed Water system operated and flow balanced to meet unit design requirements Condenser Water Yes No N A Cooling tower flushed filled and...

Страница 57: ...of the classification established by the European Directive 2014 68 EU PED For units belonging to these categories some local regulations require a periodic inspection by an authorized person Please c...

Страница 58: ...Notes...

Страница 59: ...contents All data and specifications contained therein may be subject to change without notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A explicitly rejects an...

Отзывы: