D-EIMHP01505-22_00EN 16/59
4.3. Outdoor Unit Positioning and assembly
All the outdoor units are designed for installation outdoors, either on balconies or on the ground, provided that the
installation area is free of obstacles that could reduce air flow to the condensers coil.
The unit must be installed on a robust and perfectly level foundation; should the unit be installed on balconies or roofs, it
might be necessary to use weight distribution beams.
For installation on the ground, a strong concrete base, at least 150 mm thickness and wider than the unit must be provided.
This base must be able to support the weight of the unit. In heavy snowfall areas, this thickness should be increased.
The frame of the unit must be levelled using metal plate spaces.
Figure 4
– MONO unit positioning
Figure 5
– DUAL unit positioning
The base can be installed either longitudinally or transversely. In the following figures are illustrated the mounting holes
location:
Figure 6
– Mounting holes location (bottom view)
Unit mounting holes ø
12mm