Spring Force + Oil Pressure
Suction/Discharge Differential Pressure = Slide valve moves toward unload
Suction/Discharge Differential Pressure > Spring Force = Slide valve moves toward load
C
APACITY
C
ONTROL
A
CTION
S
OLENOID VALVE
A
1
S
OLENOID VALVE
B
Load compressor
Oil is vented from the capacity control cylinder. The suction/discharge differential
pressure overcomes the force of the spring and moves the slide valve towards the
maximum load position.
Energised (open)
Deenergised
(closed)
Unload compressor
Highpressure oil is admitted to the capacity control cylinder. The force of the
spring supplemented by oil pressure overcomes the suction/discharge differential
pressure and moves the slide valve towards the minimum load position.
Deenergised
(closed)
Energised (open)
Hold slide valve position
The slide valve is hydraulically locked at the desired load position.
Deenergised
(closed)
Deenergised
(closed)
Fig. 16 - Capacity control mechanism
Compressor unloading
De-Energised
(closed)
Energised
(open)
Oil vent
Oil supply
Permanent vent to suction
Unload
Carico Compressore
Load
Oil vent
Oil supply
Energised
(open)
De-Energised
(closed)
Permanent vent to suction
Compressor loading
Содержание EWLD160~550G-SS
Страница 14: ...D EIMWC00208 16EN 14 48 Fig 7 Condenser Located above Chiller Unit Fig 8 Condenser Located below Chiller Unit...
Страница 21: ...D EIMWC00208 16EN 21 48 Fig 10 Refrigeration cycle EWWD G SS EWWD G XS 23 5 bar...
Страница 22: ...D EIMWC00208 16EN 22 48 Fig 11 Refrigeration cycle EWWD G SS EWWD G XS Partial Heat recovery 23 5 bar...
Страница 23: ...D EIMWC00208 16EN 23 48 Fig 12 Refrigeration cycle EWLD G SS OPTIONAL 23 5 bar...
Страница 45: ...D EIMWC00208 16EN 45 48...
Страница 46: ...D EIMWC00208 16EN 46 48...
Страница 47: ...D EIMWC00208 16EN 47 48...