4.3 View/Set Circuit
In this section it is possible to select between the available circuits and access data available for the circuit
selected.
Setpoint/Sub-Menu
Default
Range
Description
Circuit #1
Menu for Circuit #1
Circuit #2
Menu for Circuit #2
The submenus accessed for each circuit are identical but the content of each of them reflects the status of the
corresponding circuit. In the following the submenus will be explained only once. If only one circuit is available
the item Circuit #2 in the above table will be hidden and not accessible.
Each of the above links will jump to the following submenu:
Setpoint/Sub-Menu
Default
Description
Data
Thermodynamic data
Compressor
Status of the compressor and electrical data
Condenser
Status of the condenser fan regulation (A/C Only)
EXV
Status of the expansion valve regulation
Economizer
Status of the economizer (A/C Only)
Settings
Settings
In any of the above submenus each item shows a value and a link to another page. In that page the same data
will be represented for both circuits as a reference as shown in the below example.
Setpoint/Sub-Menu
Default
Description
Comp 1 Run Hours
-
Indication of the data represented
Circuit #1=
0h
Data related to Circuit #1
Circuit #2=
0h
Data related to Circuit #2
4.3.1
Data
In this page all relevant thermodynamic data are displayed.
Setpoint/Sub-Menu
Default
Range
Description
Circuit Status=
Status of the circuit
Off:VFD Heating
Off:
Ready
Off:
Stage Up Delay
Off:
Cycle Timer
Off:
BAS Disable
Off:
Keypad Disable
Off:
Circuit Switch
Off:
Oil Heating
Off:
Alarm
Off:
Test Mode
EXV
Preopen
Run:
Pumpdown
Run:
Normal
Run:
Disch SH Low
Run:
Evap Press Low
Run:
Cond Press High
Run:
High LWT Limit
Run:
High VFD Amps
Run:
High VFD Temp
Off:
Max Comp Starts
Off:
VFD Heating
Off:
Maintenance
Capacity=
0.0%
Circuit capacity
Evap Pressure=
220.0kPa
Evaporating Pressure
Cond Pressure=
1000.0kPa
Condensing Pressure
Suction Temp=
5.0°c
Suction Temperature
Discharge Temp=
45.0°C
Discharge Temperature
Suction SH=
5.0°C
Suction Superheat
Discharge SH=
23.0°C
Discharge Superheat
Oil Pressure=
1000.0kPa
Oil Pressure
Oil Pr Diff=
0.0kPa
Oil Pressure differential
EXV Position=
50%
Expansion valve position
Econ Sv Output=
Off
Economizer status
Liq Inj=
Off
Liquid Injection status