7 Configuration

Installation manual

24

ET9W

Daikin Altherma 3 H HT F

4P644730-1 – 2021.02

#

Code

Description

N/A

[E-0D]

Glycol Filled system

: Is the system

filled with glycol?

▪ 0: 

No

▪ 1: 

Yes

7.2.4

Configuration wizard: Backup heater

The  backup  heater  is  adapted  to  be  connected  to  most  common
European  electricity  grids.  If  the  backup  heater  is  available,  the
voltage,  configuration  and  capacity  must  be  set  on  the  user
interface.

The  capacities  for  the  different  steps  of  the  backup  heater  must  be
set  for  the  energy  metering  and/or  power  consumption  control
feature  to  work  properly.  When  measuring  the  resistance  value  of
each heater, you can set the exact heater capacity and this will lead
to more accurate energy data.

Voltage

▪ For a 

6V

 model, this can be set to:

230V, 1ph

230V, 3ph

▪ For a 

9W

 model, this is fixed to 

400V, 3ph

.

#

Code

Description

[9.3.2]

[5‑0D]

▪ 0: 

230V, 1ph

▪ 1: 

230V, 3ph

▪ 2: 

400V, 3ph

Configuration

The  backup  heater  can  be  configured  in  different  ways.  It  can  be
chosen to have a 1-step only backup heater or a backup heater with
2 steps. If 2 steps, the capacity of the second step depends on this
setting.  It  can  also  be  chosen  to  have  a  higher  capacity  of  the
second step in emergency.

#

Code

Description

[9.3.3]

[4‑0A]

▪ 0: Relay 1

▪ 1: Relay 1 / Relay 1+2

▪ 2: Relay 1 / Relay 2

▪ 3: Relay 1 / Relay 2 

Emergency

 Relay

1+2

INFORMATION

Settings  [9.3.3]  and  [9.3.5]  are  linked.  Changing  one
setting influences the other. If you change one, check if the
other is still as expected.

INFORMATION

During normal operation, the capacity of the second step of
the  backup  heater  at  nominal  voltage  is  equal  to
[6‑03]+[6‑04].

INFORMATION

If  [4‑0A]=3  and  emergency  mode  is  active,  the  power
usage  of  the  backup  heater  is  maximal  and  equal  to
2×[6‑03]+[6‑04].

INFORMATION

Only for systems with integrated domestic hot water tank: If
the  storage  temperature  setpoint  is  higher  than  50°C,
Daikin  recommends  NOT  to  disable  the  backup  heater
second  step  because  it  will  have  a  big  impact  on  the
required time for the unit to heat up the domestic hot water
tank.

Capacity step 1

#

Code

Description

[9.3.4]

[6‑03]

▪ The  capacity  of  the  first  step  of  the

backup heater at nominal voltage.

Additional capacity step 2

#

Code

Description

[9.3.5]

[6‑04]

▪ The  capacity  difference  between  the

second  and  first  step  of  the  backup
heater  at  nominal  voltage.  Nominal
value  depends  on  backup  heater
configuration.

7.2.5

Configuration wizard: Main zone

The most important settings for the main leaving water zone can be
set here.

Emitter type

Heating  up  or  cooling  down  the  main  zone  can  take  longer.  This
depends on:

▪ The water volume of the system

▪ The heater emitter type of the main zone

The  setting 

Emitter  type

  can  compensate  for  a  slow  or  a  quick

heating/cooling system during the heat up/cool down cycle. In room
thermostat  control, 

Emitter 

type

  influences  the  maximum

modulation  of  the  desired  leaving  water  temperature,  and  the
possibility  for  usage  of  the  automatic  cooling/heating  changeover
based on the indoor ambient temperature.

It is important to set 

Emitter type

 correctly and in accordance with

your system layout. The target delta T for the main zone depends on
it.

#

Code

Description

[2.7]

[2‑0C]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:

Description

Space heating

setpoint range

Target delta T in

heating

0: 

Underfloor

heating

Maximum 55°C

Variable

1: 

Fancoil unit

Maximum 55°C

Variable

2: 

Radiator

Maximum 70°C

Fixed 10°C

NOTICE

Average 

emitter 

temperature

 

Leaving 

water

temperature – (Delta T)/2

This  means  that  for  a  same  leaving  water  temperature
setpoint,  the  average  emitter  temperature  of  radiators  is
lower  than  that  of  underfloor  heating  because  of  a  bigger
delta T.

Example radiators: 40–10/2=

35°C

Example underfloor heating: 40–5/2=

37.5°C

To compensate, you can:

▪ Increase 

the 

weather-dependent 

curve 

desired

temperatures [2.5].

▪ Enable  leaving  water  temperature  modulation  and

increase the maximum modulation [2.C].

Control

Define how the operation of the unit is controlled.

Содержание ETVZ16S23EA9W

Страница 1: ...https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVZ16S18EA6V ETVZ16S23EA6V ETVZ16S18EA9W ETVZ16S23EA9W...

Страница 2: ...imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16...

Страница 3: ...figuration wizard 22 7 2 1 Configuration wizard Language 22 7 2 2 Configuration wizard Time and date 22 7 2 3 Configuration wizard System 22 7 2 4 Configuration wizard Backup heater 24 7 2 5 Configura...

Страница 4: ...NING Field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 48 WARNING Install the tundish away from any electrical device Possible consequence Elec...

Страница 5: ...underfloor heating in the main zone this is the zone with the lowest water temperature radiators in the additional zone this is the zone with the highest water temperature 4 1 1 Installation site req...

Страница 6: ...the cables from the back of the user interface panel to prevent damage 2 1 1 3 4 X14Y X1A 3 Remove the switch box cover 4 T25 4 If necessary remove the front plate This is for example necessary in the...

Страница 7: ...e pallet and place it on the floor Also see 3 1 2 To handle the indoor unit 45 2 Connect the drain hose to the drain See 4 3 2 To connect the drain hose to the drain 47 3 Slide the indoor unit into po...

Страница 8: ...the water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the outdoor unit NOT included NOTICE When ci...

Страница 9: ...o domestic cold water in and domestic hot water out connections These shut off valves are field supplied NOTICE Overpressure bypass valve delivered as accessory We recommend to install the overpressur...

Страница 10: ...nce the presence may lead to the precipitation of certain components in the glycol s corrosion inhibitor NOTICE Glycol absorbs water from its environment Therefore do NOT add glycol that has been expo...

Страница 11: ...ual of the outdoor unit or the installer reference guide 6 Electrical installation DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables CAUTION Do NOT push or place...

Страница 12: ...aximum length 500 m 2 9 Control 1 6 Room sensor offset Item Description WLAN module See Installation manual of the WLAN module Addendum book for optional equipment Use the cable delivered with the WLA...

Страница 13: ...connect X11Y to X11YB The necessity of separate normal kWh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indoor unit i...

Страница 14: ...Q1DI a b a Factory mounted cable connected to the contactor of the backup heater inside the switch box K5M b Field wiring see table below Model power supply Connections to backup heater power supply 6...

Страница 15: ...th transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Open the following see 4 2 1 To open the indoor unit 46 1...

Страница 16: ...P1HBAA is required A Y1 7 B A B 7 9 X2M A4P Y1 YC X1M a b a Installation of EKRP1HBAA is required b Prewiring between X2M 7 9 and Q1L thermal protector backup heater Do NOT change 3 Fix the cable with...

Страница 17: ...2 3 2 User interface panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below A X1 X2 L N B A B A4P X2M X1...

Страница 18: ...ION Installation of a safety thermostat field supply is required for the main zone otherwise the unit will NOT operate NOTICE A safety thermostat MUST be installed on the main zone to avoid too high w...

Страница 19: ...kit EKRELSG The 2 incoming Smart Grid contacts can activate the following Smart Grid modes Smart Grid contact Smart Grid operation mode 1 2 0 0 Free running 0 1 Forced off 1 0 Recommended on 1 1 Force...

Страница 20: ...P 2 Low voltage connections STEP 3 High voltage connections 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 a b Coil sides of relays c d Contact sides of relays e Jumper factor...

Страница 21: ...wizard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the configuration wizard To restart the configuration wizard go to I...

Страница 22: ...tton to go back to the home screen INFORMATION When you change the overview settings and you go back to the home screen the user interface will show a popup screen and request to restart the system Wh...

Страница 23: ...ure of the user interface only INFORMATION If a heat pump failure occurs and Emergency is set to Manual the room frost protection function the underfloor heating screed dryout function and the water p...

Страница 24: ...have a big impact on the required time for the unit to heat up the domestic hot water tank Capacity step 1 Code Description 9 3 4 6 03 The capacity of the first step of the backup heater at nominal vo...

Страница 25: ...set or custom Code Description 2 1 N A 0 No 1 Yes 7 2 6 Configuration wizard Additional zone The most important settings for the additional leaving water zone can be set here Emitter type For more inf...

Страница 26: ...North wall of the building If the outdoor temperature drops or rises the unit compensates instantly Thus the unit does not have to wait for feedback by the thermostat to increase or decrease the tempe...

Страница 27: ...s of outdoor ambient temperature Item Description Y1 Y2 Y3 Y4 Examples of desired tank temperature or leaving water temperature The icon corresponds to the heat emitter for that zone Underfloor heatin...

Страница 28: ...esented here 7 4 1 Main zone Thermostat type Only applicable in external room thermostat control Following combinations are possible to control the unit not applicable when C 07 0 C 07 2 Room thermost...

Страница 29: ...ctrical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze preventi...

Страница 30: ...local supply panel and the indoor unit Between the indoor unit and the valves if applicable Between the indoor unit and the room thermostat if applicable The system is properly earthed and the earth t...

Страница 31: ...the menu go to Stop test run 2 Select OK to confirm INFORMATION If the outdoor temperature is outside the range of operation the unit may NOT operate or may NOT deliver the required capacity To monit...

Страница 32: ...2 06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make...

Страница 33: ...e main mixed zone a2 Space heating additional direct zone Water OUT screw connection 1 M3S 3 way valve space heating domestic hot water b1 Space heating main mixed zone Water IN screw connection 1 R1T...

Страница 34: ...10 Technical data Installation manual 34 ETVZ16S18 23EA6V 9W Daikin Altherma 3 H HT F 4P644730 1 2021 02 q Loose nut 1...

Страница 35: ...stor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermost...

Страница 36: ...oltage Smart Grid For safety thermostat For safety thermostat For safety thermostat For safety thermostat For smartgrid For Smart Grid Inrush Inrush current Max load Maximum load Normally closed Norma...

Страница 37: ...core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A14P P1 P2 user interface Only for Human Comfort Interface Only for KRTR wireles...