background image

5 Piping installation

Installation manual

10

ET9W

Daikin Altherma 3 H HT F

4P644730-1 – 2021.02

5.2.3

To fill the water circuit

To  fill  the  water  circuit,  use  a  field  supply  filling  kit.  Make  sure  you
comply with the applicable legislation.

NOTICE

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

All  automatic  air  purge  valves  must  remain  open  after
commissioning.

5.2.4

To protect the water circuit against
freezing

About freeze protection

Frost can damage the system. To prevent the hydraulic components
from  freezing,  the  software  is  equipped  with  special  frost  protection
functions such as water pipe freeze prevention and drain prevention
(see the installer reference guide) that include the activation of pump
in case of low temperatures.

However,  in  case  of  a  power  failure,  these  functions  cannot
guarantee protection.

Do one of the following to protect the water circuit against freezing:

▪ Add  glycol  to  the  water.  Glycol  lowers  the  freezing  point  of  the

water.

▪ Install freeze protection valves. Freeze protection valves drain the

water from the system before it can freeze.

NOTICE

If  you  add  glycol  to  the  water,  do  NOT  install  freeze
protection  valves. 

Possible  consequence: 

Glycol  leaking

out of the freeze protection valves.

Freeze protection by glycol

About freeze protection by glycol

Adding glycol to the water lowers the freezing point of water.

WARNING

Ethylene glycol is toxic.

WARNING

Due  to  the  presence  of  glycol,  corrosion  of  the  system  is
possible.  Uninhibited  glycol  will  turn  acidic  under  the
influence  of  oxygen.  This  process  is  accelerated  by  the
presence  of  copper  and  high  temperatures.  The  acidic
uninhibited  glycol  attacks  metal  surfaces  and  forms
galvanic  corrosion  cells  that  cause  severe  damage  to  the
system. Therefore it is important that:

▪ the water treatment is correctly executed by a qualified

water specialist,

▪ a  glycol  with  corrosion  inhibitors  is  selected  to

counteract acids formed by the oxidation of glycols,

▪ no  automotive  glycol  is  used  because  their  corrosion

inhibitors  have  a  limited  lifetime  and  contain  silicates
which can foul or plug the system,

▪ galvanized pipes are NOT used in glycol systems since

the  presence  may  lead  to  the  precipitation  of  certain
components in the glycol's corrosion inhibitor.

NOTICE

Glycol  absorbs  water  from  its  environment.  Therefore  do
NOT add glycol that has been exposed to air. Leaving the
cap  off  the  glycol  container  causes  the  concentration  of
water  to  increase.  The  glycol  concentration  is  then  lower
than  assumed.  As  a  result,  the  hydraulic  components
might freeze up after all. Take preventive actions to ensure
a minimal exposure of the glycol to air.

Types of glycol

The types of glycol that can be used depend on whether the system
contains a domestic hot water tank:

If…

Then…

The system contains a domestic
hot water tank

Only use propylene glycol

(a)

The system does NOT contain a
domestic hot water tank

You can use either propylene
glycol

(a)

 or ethylene glycol

(a)

Propylene glycol, including the necessary inhibitors, classified as
Category III according to EN1717.

Required concentration of glycol

The  required  concentration  of  glycol  depends  on  the  lowest
expected  outdoor  temperature,  and  on  whether  you  want  to  protect
the  system  from  bursting  or  from  freezing.  To  prevent  the  system
from freezing, more glycol is required.

Add glycol according to the table below.

Lowest expected
outdoor
temperature

Prevent from
bursting

Prevent from
freezing

–5°C

10%

15%

–10°C

15%

25%

–15°C

20%

35%

–20°C

25%

–25°C

30%

–30°C

35%

INFORMATION

▪ Protection  against  bursting:  the  glycol  will  prevent  the

piping  from  bursting,  but  NOT  the  liquid  inside  the
piping from freezing.

▪ Protection  against  freezing:  the  glycol  will  prevent  the

liquid inside the piping from freezing.

NOTICE

▪ The  required  concentration  might  differ  depending  on

the type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the  glycol  manufacturer.  If  necessary,  meet  the
requirements set by the glycol manufacturer.

▪ The  added  concentration  of  glycol  should  NEVER

exceed 35%.

▪ If the liquid in the system is frozen, the pump will NOT

be  able  to  start.  Mind  that  if  you  only  prevent  the
system from bursting, the liquid inside might still freeze.

▪ When  water  is  at  standstill  inside  the  system,  the

system is very likely to freeze and get damaged.

Glycol and the maximum allowed water volume

Adding  glycol  to  the  water  circuit  reduces  the  maximum  allowed
water volume of the system. For more information, see the installer
reference guide (topic "To check the water volume and flow rate").

Содержание ETVZ16S23EA9W

Страница 1: ...https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVZ16S18EA6V ETVZ16S23EA6V ETVZ16S18EA9W ETVZ16S23EA9W...

Страница 2: ...imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16...

Страница 3: ...figuration wizard 22 7 2 1 Configuration wizard Language 22 7 2 2 Configuration wizard Time and date 22 7 2 3 Configuration wizard System 22 7 2 4 Configuration wizard Backup heater 24 7 2 5 Configura...

Страница 4: ...NING Field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 48 WARNING Install the tundish away from any electrical device Possible consequence Elec...

Страница 5: ...underfloor heating in the main zone this is the zone with the lowest water temperature radiators in the additional zone this is the zone with the highest water temperature 4 1 1 Installation site req...

Страница 6: ...the cables from the back of the user interface panel to prevent damage 2 1 1 3 4 X14Y X1A 3 Remove the switch box cover 4 T25 4 If necessary remove the front plate This is for example necessary in the...

Страница 7: ...e pallet and place it on the floor Also see 3 1 2 To handle the indoor unit 45 2 Connect the drain hose to the drain See 4 3 2 To connect the drain hose to the drain 47 3 Slide the indoor unit into po...

Страница 8: ...the water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the outdoor unit NOT included NOTICE When ci...

Страница 9: ...o domestic cold water in and domestic hot water out connections These shut off valves are field supplied NOTICE Overpressure bypass valve delivered as accessory We recommend to install the overpressur...

Страница 10: ...nce the presence may lead to the precipitation of certain components in the glycol s corrosion inhibitor NOTICE Glycol absorbs water from its environment Therefore do NOT add glycol that has been expo...

Страница 11: ...ual of the outdoor unit or the installer reference guide 6 Electrical installation DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables CAUTION Do NOT push or place...

Страница 12: ...aximum length 500 m 2 9 Control 1 6 Room sensor offset Item Description WLAN module See Installation manual of the WLAN module Addendum book for optional equipment Use the cable delivered with the WLA...

Страница 13: ...connect X11Y to X11YB The necessity of separate normal kWh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indoor unit i...

Страница 14: ...Q1DI a b a Factory mounted cable connected to the contactor of the backup heater inside the switch box K5M b Field wiring see table below Model power supply Connections to backup heater power supply 6...

Страница 15: ...th transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Open the following see 4 2 1 To open the indoor unit 46 1...

Страница 16: ...P1HBAA is required A Y1 7 B A B 7 9 X2M A4P Y1 YC X1M a b a Installation of EKRP1HBAA is required b Prewiring between X2M 7 9 and Q1L thermal protector backup heater Do NOT change 3 Fix the cable with...

Страница 17: ...2 3 2 User interface panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below A X1 X2 L N B A B A4P X2M X1...

Страница 18: ...ION Installation of a safety thermostat field supply is required for the main zone otherwise the unit will NOT operate NOTICE A safety thermostat MUST be installed on the main zone to avoid too high w...

Страница 19: ...kit EKRELSG The 2 incoming Smart Grid contacts can activate the following Smart Grid modes Smart Grid contact Smart Grid operation mode 1 2 0 0 Free running 0 1 Forced off 1 0 Recommended on 1 1 Force...

Страница 20: ...P 2 Low voltage connections STEP 3 High voltage connections 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 a b Coil sides of relays c d Contact sides of relays e Jumper factor...

Страница 21: ...wizard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the configuration wizard To restart the configuration wizard go to I...

Страница 22: ...tton to go back to the home screen INFORMATION When you change the overview settings and you go back to the home screen the user interface will show a popup screen and request to restart the system Wh...

Страница 23: ...ure of the user interface only INFORMATION If a heat pump failure occurs and Emergency is set to Manual the room frost protection function the underfloor heating screed dryout function and the water p...

Страница 24: ...have a big impact on the required time for the unit to heat up the domestic hot water tank Capacity step 1 Code Description 9 3 4 6 03 The capacity of the first step of the backup heater at nominal vo...

Страница 25: ...set or custom Code Description 2 1 N A 0 No 1 Yes 7 2 6 Configuration wizard Additional zone The most important settings for the additional leaving water zone can be set here Emitter type For more inf...

Страница 26: ...North wall of the building If the outdoor temperature drops or rises the unit compensates instantly Thus the unit does not have to wait for feedback by the thermostat to increase or decrease the tempe...

Страница 27: ...s of outdoor ambient temperature Item Description Y1 Y2 Y3 Y4 Examples of desired tank temperature or leaving water temperature The icon corresponds to the heat emitter for that zone Underfloor heatin...

Страница 28: ...esented here 7 4 1 Main zone Thermostat type Only applicable in external room thermostat control Following combinations are possible to control the unit not applicable when C 07 0 C 07 2 Room thermost...

Страница 29: ...ctrical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze preventi...

Страница 30: ...local supply panel and the indoor unit Between the indoor unit and the valves if applicable Between the indoor unit and the room thermostat if applicable The system is properly earthed and the earth t...

Страница 31: ...the menu go to Stop test run 2 Select OK to confirm INFORMATION If the outdoor temperature is outside the range of operation the unit may NOT operate or may NOT deliver the required capacity To monit...

Страница 32: ...2 06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make...

Страница 33: ...e main mixed zone a2 Space heating additional direct zone Water OUT screw connection 1 M3S 3 way valve space heating domestic hot water b1 Space heating main mixed zone Water IN screw connection 1 R1T...

Страница 34: ...10 Technical data Installation manual 34 ETVZ16S18 23EA6V 9W Daikin Altherma 3 H HT F 4P644730 1 2021 02 q Loose nut 1...

Страница 35: ...stor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermost...

Страница 36: ...oltage Smart Grid For safety thermostat For safety thermostat For safety thermostat For safety thermostat For smartgrid For Smart Grid Inrush Inrush current Max load Maximum load Normally closed Norma...

Страница 37: ...core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A14P P1 P2 user interface Only for Human Comfort Interface Only for KRTR wireles...

Страница 38: ......

Страница 39: ......

Страница 40: ...4P644730 1 2021 02 Copyright 2021 Daikin 4P644730 1 0000000M Verantwortung f r Energie und Umwelt...

Отзывы: