10/12
Breadcrumb
Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0D]
R/W
0: Reheat only
3 scheduled reheat
9.I
[6-0E]
R/W
E-07 = 4
40~ 75°C, step: 1°C
60°C
9.I
[7-00]
R/W
0~4°C, step: 1°C
0°C
9.I
[7-01]
R/W
2~40°C, step: 1°C
2°C
9.I
[7-02]
R/W
0: Single zone
1: Dual zone
9.I
[7-03]
2,5
9.I
[7-04]
0
9.I
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
9.I
[7-06]
R/W
0: Disabled
1: Enabled
9.I
[7-07]
R/W
0: No
1: Yes
9.I
[7-08]
R/W
0
9.I
[7-09]
20%
9.I
[7-0A]
R/W
20~95%, step 5%
95%
9.I
[7-0B]
R/W
20~95%, step 5%
95%
9.I
[7-0C]
R/W
20~300 seconds, step 5 sec
125 seconds
9.I
[7-0D]
R/W
2~20, step 0,5 °C
4 °C
9.I
[7-0E]
R/W
2~22, step 0,5 °C
7 °C
9.I
[8-00]
R/W
0~20 min, step 1 min
1 min
9.I
[8-01]
R/W
5~95 min, step: 5 min
30 min
9.I
[8-02]
R/W
0~10 hour, step: 0,5 hour
0,5 hour
9.I
[8-03]
R/W
20~95 min, step: 5 min
50 min
9.I
[8-04]
R/W
0~95 min, step: 5 min
95 min
9.I
[8-05]
R/W
0: No
1: Yes
9.I
[8-06]
R/W
0~10°C, step: 1°C
5°C
9.I
[8-07]
R/W
[9-03]~[9-02], step: 1°C
18°C
9.I
[8-08]
R/W
[9-03]~[9-02], step: 1°C
20°C
9.I
[8-09]
R/W
[9-01]~[9-00], step: 1°C
35°C
9.I
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
33°C
9.I
[8-0B]
13
9.I
[8-0C]
10
9.I
[8-0D]
16
9.I
[9-00]
R/W ([2-
0C] ≠ 2)
R/O ([2-
0C] = 2)
[2-0C]=2:
37~60, step: 1°C
65°C
[2-0C]≠2:
37~55, step: 1°C
55°C
9.I
[9-01]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-02]
R/W
18~22°C, step: 1°C
22°C
9.I
[9-03]
R/W
5~18°C, step: 1°C
5°C
9.I
[9-04]
R/W
1~4°C, step: 1°C
2°C
9.I
[9-05]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-06]
R/W ([2-
0C] ≠ 2)
R/O ([2-
0C] = 2)
[2-0C]=2:
37~60, step: 1°C
65°C
[2-0C]≠2:
37~55, step: 1°C
55°C
9.I
[9-07]
R/W
5~18°C, step: 1°C
5°C
9.I
[9-08]
R/W
18~22°C, step: 1°C
22°C
9.I
[9-09]
R/W
1~18°C, step: 1°C
18°C
9.I
[9-0A]
R/W
[3-07]
~
[3-06]°C, step: 0,5°C
23°C
9.I
[9-0B]
R/W
[3-09]
~
[3-08]°C, step: 0,5°C
23°C
9.I
[9-0C]
R/W
1~6°C, step: 0,5°C
1 °C
What is the desired eco storage temperature?
What is the desired reheat temperature?
BBR16 activation*
*BBR16 settings are only visible when the language of the user interface is set to
Swedish.
Minimum running time for domestic hot water operation.
How much is the minimum pump PWM value.
Additional zone fixed pump PWM, in case a bizone kit is installed.
Main zone fixed pump PWM, in case a bizone kit is installed.
Time needed by the mixing valve to turn from one side to the other, in case a bizone
kit is installed.
Offset on the setpoint to determine when the tank is high enough to go the excess
state
What is the desired DHW production type?
Hysteresis value used to control the tank bivalent in case it’s supporting space
heating operation
What is the allowed LWT undershoot during cooling start-up?
What is the desired eco main LWT in heating?
--
--
Maximum running time for domestic hot water operation.
What is the mimimum desired LWT for add. zone in heating?
What is the desired comfort main LWT in cooling?
What is the desired comfort main LWT in heating?
What is the mimimum desired LWT for main zone in heating?
What is the maximum desired LWT for main zone in cooling?
What is the desired eco main LWT in cooling?
What is the maximum temperature setpoint?
Domestic hot water booster heater overshoot temperature.
Domestic hot water booster heater hysteresis.
How many leaving water temperature zones are there?
--
--
Boiler efficiency
Compressor forced OFF
--
What is the room buffering temperature in heating?
What is the room buffering temperature in Cooling?
Anti-recycling time.
Booster heater delay timer.
Additional running time for the maximum running time.
Allow modulation of the LWT to control the room temp?
Leaving water temperature maximum modulation.
--
What is the maximum desired LWT for main zone in heating?
What is the maximum desired LWT for add. zone in heating?
What is the mimimum desired LWT for add. zone in cooling?
What is the maximum desired LWT for add. zone in cooling?
Room temperature hysteresis.
What is the mimimum desired LWT for main zone in cooling?
Leaving water temperature overshoot temperature.
4P681207-1 - 2021.12
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*6) *EKECBUA3V*_(*7) *EKECBUA6V*_(*8) *EKECBUA9W*_(*9) BUH less_