Piping installation
Installer reference guide
103
ERGA04~V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1 – 2022.01
Typical workflow
Connecting the water piping typically consists of the following stages:
1
Connecting the water piping to the outdoor unit.
2
Connecting the water piping to the indoor unit.
3
Connecting the recirculation piping.
4
Install pressure vessel at special connection.
5
Connecting the drain hose to the drain.
6
Filling the water circuit.
7
Filling the heat exchanger coils inside the storage tank.
8
Filling the storage tank.
9
Insulating the water piping.
8.6.2 Precautions when connecting the water piping
INFORMATION
Also read the precautions and requirements in the following chapters:
▪
"2 General safety precautions"
▪
8.6.3 To connect the water piping
NOTICE
Do NOT use excessive force when connecting the field piping and make sure the
piping is aligned properly. Deformation of the piping can cause malfunctioning of the
unit.
1
Remove the thermal insulation of the hydraulic block. Open the vent valve on
the pump by one turn. Afterwards put the thermal insulation back on the
hydraulic block.
NOTICE
The thermal insulation can easily be damaged if NOT handled correctly.
▪
ONLY remove parts in the order and direction as indicated here,
▪
do NOT use force,
▪
do NOT use tools,
▪
re-install the thermal insulation in reverse order.