4/9
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
9.1
[4-0A]
R/O
0~3
0: 1
9.1
[6-03]
R/W
0~10kW, step: 0,2kW
3kW
9.1
[6-04]
R/O
0~10kW, step: 0,2kW
3kW
└─ Main zone
9.1
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
9.1
R/W
0: Fixed
2: Weather dependent
9.1
R/W
0: No
1: Yes
9.1
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
9.1
[1-01]
R/W
10~25°C, step: 1°C
15°C
9.1
[1-02]
R/W
[9-01]~[9-00], step: 1°C
35°C
9.1
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
9.1
[1-06]
20
9.1
[1-07]
35
9.1
[1-08]
22
9.1
[1-09]
18
└─ Additional zone
9.1
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1
R/W
0: Fixed
2: Weather dependent
9.1
R/W
0: No
1: Yes
9.1
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
9.1
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
50°C
9.1
[0-02]
R/W
10~25°C, step: 1°C
15°C
9.1
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
9.1
[0-04]
8
9.1
[0-05]
12
9.1
[0-06]
35
9.1
[0-07]
20
└─ Tank
9.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
9.1
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
9.1
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.1
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
└─ Domestic hot water
9.2.1
[E-05]
[E-06]
[E-07]
R/O
3: Integrated
9.2.2
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
9.2.4
[D-07]
R/W
0: No
1: Yes
└─ Back up heater
9.3.1
[E-03]
R/W
0: No heater
1: External heater
2: 3V
3: 6V
4: 9W
9.3.2
[5-0D]
R/O
0~2
0: 230V, 1~
9.3.3
[4-0A]
R/O
0~3
0: 1
9.3.4
[6-03]
R/W
0~10kW, step: 0,2kW
3kW
9.3.5
[6-04]
R/O
0~10kW, step: 0,2kW
3kW
9.3.6
[5-00]
R/W
0: Allowed
1: Not allowed
9.3.7
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.3.8
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
└─ Booster heater
9.4.1
[6-02]
R/W
0~10kW, step: 0,2kW
2,4kW
9.4.3
[8-03]
R/W
20~95 min, step: 5 min
50 min
9.4.4
[4-03]
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
Configuration
Capacity step 1
Additional capacity step 2
Emitter type
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
--
Control
Setpoint mode
Schedule
--
--
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
--
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Schedule
Emitter type
Setpoint mode
--
--
--
--
Heat up mode
Comfort setpoint
Eco setpoint
Reheat setpoint
Domestic hot water
DHW pump
Solar
BUH type
Voltage
Configuration
Capacity step 1
Additional capacity step 2
Equilibrium
Equilibrium temperature
Operation
Capacity
BSH eco timer
Operation
4P499575-1A - 2017.11
(#) Setting is not applicable for this unit.
Содержание ERGA06DAV3A