5 Starting up the outdoor unit
Installation manual
10
ERGA04~08DAV3
Daikin Altherma – Low temperature split
4P489913-1B – 2017.10
2×
2
Connect the interconnection cable and power supply as follows.
Ensure stress relief by using the wire clamp.
a
c
d
1N~ 50 Hz
220-240 V
b
a
Interconnection cable
b
Power supply cable
c
Fuse
d
Earth leakage circuit breaker
1 2 3
L
N
L N PWR
12 3
3×
a
a
Wire clamp
3
Reattach the switch box cover.
4
Optional: Attach the wire clamp (accessory) to the screw of the
refrigerant piping cover, and fix the cables to it with a cable tie.
1×
1×
5
Connect an earth leakage circuit breaker and fuse to the power
supply line.
4.7
Finishing the outdoor unit
installation
4.7.1
To finish the outdoor unit installation
1
Insulate and fix the refrigerant piping and interconnection cable
as follows:
f
b
a
e
d
c
a
Gas pipe
b
Gas pipe insulation
c
Interconnection cable
d
Liquid pipe
e
Liquid pipe insulation
f
Finishing tape
2
Install the service cover.
5
Starting up the outdoor unit
See the indoor unit installation manual for configuration and
commissioning of the system.
6
Technical data
A
subset
of the latest technical data is available on the regional Daikin website (publicly accessible). The
full set
of latest technical data is
available on the Daikin extranet (authentication required).