Table 19 - Electrical Data ERAD 120E ÷ 220E-SS
Unit Size
120
140
170
200
220
Power Supply
Phase
---
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
Voltage
V
400
400
400
400
400
Voltage Tolerance
Minimum
%
-10%
-10%
-10%
-10%
-10%
Maximum
%
+10%
+10%
+10%
+10%
+10%
Unit
Maximum starting current
A
159
159
207
207
304
Nominal running current cooling
A
72
87
98
110
127
Maximum running current
A
88
104
119
133
161
Maximum current for wires sizing
A
97
114
131
146
177
Fans
Nominal running current in cooling
A
8
8
12
12
16
Compressor
Phase
No.
3
3
3
3
3
Voltage
V
400
400
400
400
400
Voltage Tolerance
Minimum
%
-10%
-10%
-10%
-10%
-10%
Maximum
%
+10%
+10%
+10%
+10%
+10%
Maximum running current
A
80
96
107
121
145
Starting method
---
W ye
– Delta type (Y – Δ)
Notes
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest comp fans current
Nominal current in cooling mode is referred to the following conditions: SS T 7°C; ambient 35°C;
comp fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans
absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load fans current) x 1.1.
Table 20 - Electrical Data ERAD 250E ÷ 490E-SS
Unit Size
250
310
370
440
490
Power Supply
Phase
---
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
Voltage
V
400
400
400
400
400
Voltage Tolerance
Minimum
%
-10%
-10%
-10%
-10%
-10%
Maximum
%
+10%
+10%
+10%
+10%
+10%
Unit
Maximum starting current
A
304
354
434
434
434
Nominal running current cooling
A
131
156
203
243
265
Maximum running current
A
161
195
248
288
288
Maximum current for wires sizing
A
177
215
273
317
317
Fans
Nominal running current in cooling
A
16
24
24
24
24
Compressor
Phase
No.
3
3
3
3
3
Voltage
V
400
400
400
400
400
Voltage Tolerance
Minimum
%
-10%
-10%
-10%
-10%
-10%
Maximum
%
+10%
+10%
+10%
+10%
+10%
Maximum running current
A
145
171
224
264
264
Starting method
---
W ye
– Delta type (Y – Δ)
Notes
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the compressor at 75%
maximum load + fans current
Nominal current in cooling mode is referred to the following conditions: evaporator 12°C/7°C; ambient
35°C; compr fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans
absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load fans current) x 1,1.