D
–EIMAC00708-16EN - 39/76
EWAD 100E ÷ 400E-SL
Model
EWAD 100E-SL EWAD 120E-SL EWAD 130E-SL EWAD 160E-SS EWAD 180E-SL
Disconnect Switch Size
400 A
400 A
400 A
400 A
400 A
Short circuit rating (note 1)
25 kA
25 kA
25 kA
25 kA
25 kA
Recommended Fuses
125 A gG
160 A gG
160 A gG
200 A gG
200 A gG
Minimum Recommended Wire Size (note 2)
70 mm2
95 mm2
95 mm2
120 mm2
120 mm2
Maximum Wire Size (note 3)
2x185 mm2
2x185 mm2
2x185 mm2
2x185 mm2
2x185 mm2
Model
EWAD 210E-SL EWAD 250E-SL EWAD 300E-SL EWAD 350E-SL EWAD 400E-SL
Disconnect Switch Size
400 A
400 A
400 A
400 A
400 A
Short circuit rating (note 1)
25 kA
25 kA
25 kA
25 kA
25 kA
Recommended Fuses
200 A gG
250 A gG
315 A gG
355 A gG
355 A gG
Minimum Recommended Wire Size (note 2)
120 mm2
150 mm2
2x95 mm2
2x95 mm2
2x120 mm2
Maximum Wire Size (note 3)
2x185 mm2
2x185 mm2
2x185 mm2
2x185 mm2
2x185 mm2
Note 1:
Short-circuit current ratings are referred to a 0.25 s duration of short circuit.
Note 2:
Correct wire sizing must take into account the actual ambient temperature of the installation and the protection device insta lled on-site.
Recommended wire size is made according to standard EN60204-1
– Table 6.E with the following assumptions:
-
Recommended protection devices (fuses)
-
70°C PVC stranded copper conductors
-
40°C ambient temperature
Wire sizing is different as installation and operation conditions are different from the above mentioned values. The voltage drop from the
point of supply to the load must not exceed 5% of the nominal voltage under normal operating conditions. In order to co mply with this
requirement, it can be necessary to use conductors having a larger cross-sectional area than the minimum value reported on the above
table.
Note 3:
Maximum wire size is the maximum allowed by the disconnect switch terminals. In case a larger conductor size is needed, conta ct
factory for asking special incoming lugs.
ERAD 120E ÷490E-SS
Model
ERAD 120E-SS ERAD 140E-SS ERAD 170E-SS ERAD 200E-SS ERAD 220E-SS
Disconnect Switch Size
400 A
400 A
400 A
400 A
400 A
Short circuit rating (note 1)
25 kA
25 kA
25 kA
25 kA
25 kA
Recommended Fuses
125 A gG
160 A gG
160 A gG
200 A gG
200 A gG
Minimum Recommended Wire Size (note 2)
70 mm2
95 mm2
95 mm2
120 mm2
120 mm2
Maximum Wire Size (note 3)
2x185 mm2
2x185 mm2
2x185 mm2
2x185 mm2
2x185 mm2
Model
ERAD 250E-SS ERAD 310E-SS ERAD 370E-SS ERAD 440E-SS ERAD 490E-SS
Disconnect Switch Size
400 A
400 A
400 A
400 A
400 A
Short circuit rating (note 1)
25 kA
25 kA
25 kA
25 kA
25 kA
Recommended Fuses
200 A gG
250 A gG
315 A gG
355 A gG
355 A gG
Minimum Recommended Wire Size (note 2)
120 mm2
150 mm2
2x95 mm2
2x95 mm2
2x120 mm2
Maximum Wire Size (note 3)
2x185 mm2
2x185 mm2
2x185 mm2
2x185 mm2
2x185 mm2
Note 1:
Short-circuit current ratings are referred to a 0.25 s duration of short circuit.
Note 2:
Correct wire sizing must take into account the actual ambient temperature of the installation and the prote ction device installed on-site.
Recommended wire size is made according to standard EN60204-1
– Table 6.E with the following assumptions:
-
Recommended protection devices (fuses)
-
70°C PVC stranded copper conductors
-
40°C ambient temperature
Wire sizing is different as installation and operation conditions are different from the above mentioned values. The voltage drop from the
point of supply to the load must not exceed 5% of the nominal voltage under normal operating conditions. In order to co mply with this
requirement, it can be necessary to use conductors having a larger cross-sectional area than the minimum value reported on the above
table.
Note 3:
Maximum wire size is the maximum allowed by the disconnect switch terminals. In case a larger conductor size is needed, contact
factory for asking special incoming lugs.