[6] Domestic hot water storage and reheat operation

Scheduled domestic hot water storage

The storage setpoint can be accessed directly using the 

wi

 and

wj

 buttons.

[6-03] Scheduled storage: defines whether the scheduled
domestic water heating storage during night is enabled (1) or
not (0).

[6-04] Scheduled storage start time: time of the night at which
the domestic water should be heated.

Selecting powerful domestic water heating operation

1

Press 

v

 for 5 seconds to activate powerful domestic water

heating operation.

Icons 

w

 and 

)

 start flashing.

Powerful domestic water heating is deactivated automatically
when the set point for the domestic hot water is reached.

Scheduled/continuous domestic hot water reheat

[6-05] Reheat: defines whether the scheduled domestic water
reheat during daytime is enabled (1) or continuous reheat is
enabled (2) or reheat is disabled (0)

[6-06] Scheduled reheat start time: time of the day at which the
domestic water should be heated.

[6-07] Domestic hot water reheat sepoint

[6-08] Domestic hot water reheat sepoint hysteresis

Example 1

: Scheduled storage [6-03]=1, scheduled reheat [6-05]=1,

disinfection function [2-01]=1 activated.

Example 2

: Scheduled storage [6-03]=1, continuous reheat [6-05]=2,

disinfection function [2-01]=1 activated.

[9] Heating and cooling set point ranges

The purpose of this field setting is to prevent the user from selecting a
wrong (i.e., too hot or too cold) leaving water temperature. Thereto
the heating temperature set point range and the cooling temperature
set point range available to the user can be configured.

[9-00] Heating set point upper limit: maximum leaving water
temperature for heating operation.

[9-01] Heating set point lower limit: minimum leaving water
temperature for heating operation.

[9-02] Cooling set point upper limit: maximum leaving water
temperature for cooling operation.

[9-03] Cooling set point lower limit: minimum leaving water
temperature for cooling operation.

The storage and reheat domestic hot water will only be
carried out when the heating of the domestic hot water is
enabled by the 

w

 button.

A

Scheduled storage operation:

 activated at [6-04], heat up 

domestic hot water untill domestic hot water user interface set 
point Tdhw (e.g 55°C) is reached. 

B

Scheduled reheat operation

: activated at [6-06], heat up 

domestic hot water untill domestic hot water reheat set point 
[6-07] (e.g 45°C ) is reached. 

C

Disinfection operation

 (if activated): activated at [2-02], heat up 

domestic hot water untill domestic hot water disinfection set point 
[2-03] (e.g 60°C) is reached. Refer to 

"[2] Disinfection function" 

on page 14

.

t

Time

T

Domestic hot water temperature

Tdhw

Domestic hot water user interface set point

A

B

C

T

t

[2-03]

Tdhw

[6-07]

[6-04]

[6-06]

[2-02]

A

Scheduled storage operation

: activated at [6-04], heat up 

domestic water till domestic hot water user interface setpoint 
Tdhw (e.g 55°C), is reached. 

B

Continuous reheat operation

: continues activated heat up 

domestic water till domestic hot water reheat set point [6-07] (e.g 
45°C) is reached with a hysteresis of [6-08].

C

Disinfection operation (if activated): activated at [2-02] ,heat up 
domestic water till domestic hot water disinfection set point [2-03] 
(e.g 60°C) is reached. Refer to 

"[2] Disinfection function" on 

page 14

.

t

Time

T

Domestic hot water temperature

Tdhw

Domestic hot water user interface set point

Make sure the domestic water is only heated up to the
domestic hot water temperature you require.

Start with a low domestic hot water storage
temperature set point, and only increase if you feel
that the domestic hot water supply temperature is not
sufficient for your needs (this depends on your water
using pattern).

Make sure the domestic water is not heated
unnecessary. Start with activating automatic storage
during night (default setting). If it seems that the
domestic hot water night storage operation is not
sufficient for your needs, an additional scheduled
reheat during daytime can be set.

CAUTION

In case of a floor heating application, it is important to
limit the maximum leaving water temperature at
heating operation according to the specifications of
the floor heating installation.

In case of a floor cooling application, it is important to
limit the minimum leaving water temperature at
cooling operation (field setting of parameter [9-03]) to
16~18°C to prevent condensation on the floor.

A

B

C

[6-08]

B

T

t

[2-03]

[6-07]

Tdhw

[6-04]

[2-02]

Содержание EKHVH008BB6V3

Страница 1: ...OPERATION MANUAL EKHVH008BB6V3 EKHVX008BB6V3 EKHVH008BB6WN EKHVX008BB6WN EKHVH008BB9WN EKHVX008BB9WN Daikin Altherma indoor unit...

Страница 2: ...1 2 Meaning of used terms Installation manual Instruction manual speci ed for a certain product or application explaining how to install con gure and maintain it Operation manual Instruction manual s...

Страница 3: ...ual of the indoor unit and to the installation manual of the digital I O PCB for more information Refer to the wiring diagram or connection diagram for connecting this PCB to the unit Remote thermosta...

Страница 4: ...ough the tap it will probably make a sound as of air escaping 4 2 Operating the digital controller Operating the EKHV unit comes down to operating the digital controller Features and functions The dig...

Страница 5: ...timer 9 OFF ICON x This icon indicates that the OFF action is selected when programming the schedule timer 10 INSPECTION REQUIRED k and l These icons indicate that inspection is required on the instal...

Страница 6: ...nstalled 34 QUIET MODE BUTTON s This button enables or disables quiet mode If the controller is set in permission level 2 or 3 refer to Field settings on page 12 the quiet mode button will not be oper...

Страница 7: ...tons to set the desired water temperature Temperature range for heating 25 C to 55 C The temperature for heating can be set as low as 15 C see Field settings on page 12 However the temperature for hea...

Страница 8: ...programmed command of the schedule timer occurs The schedule timer is enabled p icon displayed or disabled p icon not displayed by pressing the pr button To set up the SCHEDULE TIMER refer to chapter...

Страница 9: ...grammed per weekday The same actions are repeated on a weekly basis In the space cooling and quiet mode program four actions can be programmed per mode The same actions are repeated on a daily basis T...

Страница 10: ...e programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the...

Страница 11: ...other actions of the selected mode When all actions have been programmed make sure that the display shows the highest action number you would like to save 10 Press the button for 5 seconds to store th...

Страница 12: ...essing the pr button 3 Press the button to con rm the selected mode The actual day is blinking 4 Select the day you would like to copy to the next day by means of the pi and pj buttons The selected da...

Страница 13: ...FIELD SET MODE The icon 3 will be displayed The current selected eld setting code is indicated 2 with the set value displayed to the right 1 2 Press the bgi button to select the appropriate eld settin...

Страница 14: ...low ambient temperature Lo_A Note that the Lo_Ti value should be higher than Hi_Ti as for colder outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_T...

Страница 15: ...temperature TU User set point temperature as set on the user interface TH High set point temperature 2 03 t Time WARNING Be aware that the domestic hot water temperature at the hot water tap will be e...

Страница 16: ...mestic hot water is enabled by the w button A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domestic hot water user interface set point Tdhw e g 55 C is reached B Sch...

Страница 17: ...hift value of the weather dependent set point around outdoor temperature of 0 C E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23...

Страница 18: ...without built in booster heater 4 05 5 60 40 60 5 min 3 Auto restart 00 Status 0 ON 0 1 4 Space heating off temperature 00 Installation related setting 01 Installation related setting 02 Space heating...

Страница 19: ...4 Installation related setting 05 Installation related setting D Bene t kWh rate power supply local shift value weather dependent 00 Installation related setting 01 Installation related setting 02 Ins...

Страница 20: ...th unsorted household waste Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a quali ed installer in accord...

Страница 21: ......

Страница 22: ...4PW64330 1 07 2010 Copyright 2010 Daikin...

Отзывы: