Installation and operating instructions
30
DAIKIN EKHHP(3/5)00AA2V3
DAIKIN Hot water heat pump
008.1423444_05 – 08/2016
7
x
Operation, Parameters
7.5.3 Parameter factory settings
Code 1
Code 2
Parameter name
Standard factory settings
Value
Range
Increment
Unit
0 00 Hot water set temperature for the operating mode "High Output"
55
40 - 60
1
°C
01 Hot water set temperature for thermal disinfection
65
50 - 75
1
°C
02 Heat retention function switch-on temperature
40
35 - 55
1
°C
03 Heat retention switch-off temperature
45
35 - 55
1
°C
04 Actvation / deactivation of heat retention function
0
0 - 1
1
—
2 00 Start day thermal disinfection (Legionella protection)
FR
every day
—
—
01 Automatic thermal disinfection with hot water heat pump switched on
0
0 - 1
0
—
02 Start time thermal disinfection
23:00
0:00 - 23:00
1:00
h
03 Automatic thermal disinfection in "Stand-by" mode
0
0 - 1
1
—
04 Holding time thermal disinfection temperature [0-01]
10
5 - 60
1
Min.
3 00 Automatic restart after a power failure
1
0 - 1
1
—
01 Access authorisation
3
2, 3
1
—
02 Hot water set temperature >60 °C
0
0 - 1
1
—
4 03 Simultaneous operation of the electrical Booster Heater (BSH) and
heat pump
0
0 - 3
1
—
6 00 Switchng hysteresis of heat pump
14
2 - 20
1
K
01 Heat pump switch-off temperature difference
0
0 - 15
1
K
02 ECO-Timer (BSH)
120
5 - 120
1
Min.
03 Priority of operating mode "High Output"
1
0 - 1
1
—
04 Steps in the operating mode "Low Noise"
1
1 - 3
1
—
7 00 Behaviour in high/low tariff (HT/NT) - / Smart Grid (SG) mode
0
0 - 3
1
—
01 Switching hysteresis Booster-Heater (BSH) when hot water set tem-
perature is above the maximum possible hot water temperature in
exclusively heat pump mode.
2
2 - 20
1
°C
02 Setting Emergency mode (use of BSH permitted or not)
0
0 - 1
1
—
04 Lower external temperature limit for heat pump operation
-15
-25 - 10
1
°C
C 00 Not used
0
—
—
—
E Display unit information
00 Software version
Information value, cannot be changed.
01 EEPROM version
Information value, cannot be changed.
02 Model ID
Information value, cannot be changed.
These parameters are only accessible in the "Advanced Mode" (see Section 7.5.1).
Tab. 7-5 Overview parameter settings