background image

x

 Operation, Parameters

DAIKIN EKHHP(3/5)00AA2V3 
DAIKIN Hot water heat pump
008.1423444_05 – 08/2016

Installation and operating instructions

23

50 - Display Service technician required

This icon shows that the system must be checked. Get in touch 
with your heating specialist or nearest DAIKIN contractual 
partner.

51 - Display Parameter code or Fault code 

This display represenst the code from the parameter setting (see 
Section 7.5) or the error code (see Section 8.2).

52 - Keys Setting hot water temperature

 

 a

nd 

These keys are used to adjust the set temperature for hot water 
generation.

53 - Key operating mode "Automatic" 

This key activates and deactivates the automatic mode. this op-
erating mode, the integrated Booster-Heater (BSH) in the storage 
tank of the DAIKIN EKHHP can be added in for the heating up 
process if required.

54-  Key Programming 

This multifunction key is used to program the switching times.

55 - Key operating mode "High Output" 

This key activates and deactivates the accelerated heating 
mode. Heating up is by heat pump and integrated Booster-Heater 
(BSH).

56 - Key activation/deactivation of timer programme 

The main function of this multifunction key is to activate/deac-
tivate the timer programme. The key is also used to programme 
the parameters.

57 - Key operating mode "Low Noise" 

This key activates and deactivates the low noise mode. In this op-
erating mode the output of the system is reduced so that the op-
erating noise of the external heat pump unit is reduced.

58- Key Time setting

 

 and 

These keys have several functions such as:
– Setting the time.
– Switching between the display of outside temperature and the 

storage tank temperature (see Section 7.2.3).

– Setting the switching times for the timer programme.

59 - Key error code / parameter setting 

This key has several functions:
– Extended key push (>5 sec.): Setting the parameters
– Brief key push: Display of last fault code

7.2 Basic functions

Certain menu items in the controller are only accessible to the 
specialist heating technician. This security measure ensures that 
no undesirable malfunctions arise through incorrect configu-
ration.

7.2.1 Switching the system on and off

Press the 

 key.

The operation LED lights up red.

During start-up, the icon 

 is shown in the display 

of the controller.

After start-up, the current operating mode is shown in the display 
of the controller.

When you press the key 

 again, the system is shut down and 

the Operation LED goes out.

7.2.2 Setting the clock

Setting the time

Press 

 key for at least 5 s.

The time and display of the weekday starts flashing.

Use the keys 

 and 

 to set the time.

The time is increased/decreased by 1 min.
Holding the key  

 or 

 pressed 

increases/reduces the time by 10 min.

Press the 

 key to save or press the 

 key again to 

cancel the setting.

Setting the weekday

Press 

 key for at least 5 s.

The time and display of the weekday starts flashing.

Use the keys 

 and 

 to set the weekday.

The weekday is increased/decreased by 1 min.

Press the 

 key to save or press the 

 key again to 

cancel the setting.

7.2.3 Display of the current Temperature

Press the key 

 for 5 s.

The icon 

 and the outside temperature are displayed.

The icons 

 + 

 flash in the display on the controller.

The display (Fig. 7-1, Item 34) shows the sensor number 

001

.

Use the keys 

 and 

 to select the following 

temperatures:

Tab. 7-1 Temperature displays

If no button is pressed within 30 s, the control leaves display 
mode.

7.2.4 Defrost 

At low outdoor temperatures and corresponding humidity values, 
the external heat pump unit may ice up. This icing impairs effi-
cient operation. The system detects this condition automatically 
and starts the melting operation 

During the melting operation the heat pump internal unit 
(EKHHP) has heat extracted from it and the Booster-Heater 
(BSH) is added in, if required.

After 8 minutes at most, the system returns to normal mode.

7.3 Operating modes

Sensor 

No.

Temperature sensor

Icon flashes

001

External temperature

002

003

004

Storage tank temperature

005

MAXIMUM ENERGY UTILISATION

The most effective energy utilisation is achieved by the 
DAIKIN at the lowest possible hot water temperatures.

At temperatures in excess of 50 °C, the effectiveness (COP) of 
the DAIKIN hot water heat pump could be made worse by the 
support of the electric immersion heater (Booster-Heater), de-
pending on the outdoor temperature.

Содержание EKHHP300AA2V3

Страница 1: ...Installation and operating instructions EKHHP300AA2V3 EKHHP500AA2V3 Hot water heat pump indoor unit Installation and operating instructions Hot water heat pump indoor unit English...

Страница 2: ...BSH 15 4 8 2 High low tariff mains connection HT NT 15 4 8 3 Connection EVU receiver intelligent regulator Smart Grid SG 16 4 8 4 Optional Connection of an external heat generator16 5 Start up 17 5 1...

Страница 3: ...tructed in the safe use of the equipment and under stand the dangers arising therefrom Children must not play with the equipment Cleaning and user maintenance must not be carried out by children witho...

Страница 4: ...ised safety related and occupational medical rules 2 3 Intended use The DAIKIN EKHHP system may only be used for the generation of hot water and only set up connected and operated in accordance with t...

Страница 5: ...e category III Means with contact separation in all poles that provide full disconnection must be incorpo rated in the fixed wiring in accordance with the wiring rules Compare the mains voltage 230 V...

Страница 6: ...tary water Water hardness calcium and magnesium calculated as calcium carbonate 3 mmol l Conductivity 1500 ideal 100 S cm Chloride 250 mg l Sulphate 250 mg l pH value 6 5 8 5 Using filling water and t...

Страница 7: ...escription DAIKIN EKHHP 3 5 00AA2V3 DAIKIN Hot water heat pump 008 1423444_05 08 2016 Installation and operating instructions 7 3 Product description 15 17 Fig 3 1 Structure of the DAIKIN EKHHP legend...

Страница 8: ...changer stainless steel for storage tank charging by hot water heat pump liquifier 42 Display external signal HT NT Smart Grid 14 Heat exchanger stainless steel for storage tank charging by pressurise...

Страница 9: ...on the DAIKIN EKHHP such as setup servicing connection and initial start up is only to be carried out by persons who are authorised and who have successfully completed qualifying technical or vocatio...

Страница 10: ...plosion risk environments is not permitted The DAIKIN EKHHP must only be set up in non hermetically closed rooms The electronic control system must not be subjected to atmospheric factors under any ci...

Страница 11: ...s and corrosion Observe the requirements for storage tank water see Section 2 4 6 CAUTION If the DAIKIN EKHHP is connected to a cold water line where steel pipes are used chips can enter the special s...

Страница 12: ...d solar heat exchanger Fig 3 1 and Tab 3 1 give the position and dimensions of the connections CArry out hydraulic system incorporation in accordance with Fig 4 5 Pay attention to the stipulated tight...

Страница 13: ...unit Open stop valve on exterior unit completely until the stop Tighten loosely Reassemble valve caps A DAIKIN EWQ B DAIKINEKHHP C Gas line D Liquid line E Oil trap arc H height to 1st oil trap max 1...

Страница 14: ...d before the storage tank The heat exchanger for connecting an optional heat generator Fig 3 1 Item 14 only EKHHP500AA2V3 also needs to be filled if no optional heat generator is connected to it This...

Страница 15: ...ND IN1 of the DAIKIN EKHHP see Fig 4 12 When the parameter 7 00 0 is set certain system compo nents are switched off in high tariff times see Section 7 5 The potential free switching contact GND IN1 c...

Страница 16: ...of the pa rameter 7 00 the heat pump is operated differently see Tab 7 3 4 8 4 Optional Connection of an external heat generator When using an external heat generator this can be connected using a pot...

Страница 17: ...tion Select a higher set hot water temperature so that the heating function is acti vated see Section 7 3 1 Sign the check list together with the operator Only if it is possible to answer all items on...

Страница 18: ...estic hot water heating in the DAIKIN EKHHP full and has it been bled Yes 4 1 Only EKHHP500AA2V3 Is the heat exchanger filled for the connection of an optional heat generator Yes 5 Is the storage tank...

Страница 19: ...ter connections due to escaping hot water Draining the storage tank only after it has cooled down for a longe nough period with a suitable device for the safe draining or catching of escaping water we...

Страница 20: ...nal heat pump unit When disposing of the machine or replacing parts in the coolant system Suction the coolant from the machine and recycle see instal lation and operating guide for the particular exte...

Страница 21: ...n it off and recycle using a suitable recycling device Always recycle coolant in so doing keeping it separated from oils and other additives Only store different types of coolant separately in suitabl...

Страница 22: ...urrent day of the week The set day is in dicated in the display in the programming mode 37 Display refrigerant compressor active This icon shows that the refrigerant compressor is active in the extern...

Страница 23: ...lfunctions arise through incorrect configu ration 7 2 1 Switching the system on and off Press the key The operation LED lights up red During start up the icon is shown in the display of the controller...

Страница 24: ...t pump external unit the controller switches over to the integrated Booster Heater BSH The Booster Heater BSH is only switched on if the hot water temperature has been set above the maximum temperatur...

Страница 25: ...parameter settings If the Booster Heater BSH is added in the controller dispaly shows the symbol 7 4 1 Display switching times 1 Press the key The current operating mode flashes 2 Use the and keys to...

Страница 26: ...5 secs confirms the end of the programming The fourth switching time and if there is one the fifth switch ing time will be deleted Deleting all switching times of an operating mode Only all switching...

Страница 27: ...p stops the reheating procedure 0 04 Activation temperature heat retention function Deter mines whether automatic reheating takes place if the temper ature falls below the parameter value 0 02 0 Funct...

Страница 28: ...tted 4 03 is not set to 0 6 03 Priority of High Output operating mode stipulates the priority if the operating modes Low Noise and High Output are active at the same time 6 04 Stages in the operating...

Страница 29: ...y setting 2 K 7 02 Emergency operation The parameter 7 02 is set to 0 in the factory If there is a fault in the heat pump external unit the parameter 7 02 1 can be set In addition the unit must be set...

Страница 30: ...atic restart after a power failure 1 0 1 1 01 Access authorisation 3 2 3 1 02 Hot water set temperature 60 C 0 0 1 1 4 03 Simultaneous operation of the electrical Booster Heater BSH and heat pump 0 0...

Страница 31: ...ed temperature C C C C C TUE switching time Action On Off ON OFF ON OFF ON OFF ON OFF ON OFF feed temperature C C C C C WED switching time Action On Off ON OFF ON OFF ON OFF ON OFF ON OFF feed tempera...

Страница 32: ...ammed switching times are being carried out at the wrong time Day of the week and time are not correctly set Set the weekday Set time Check week day switching time allocation Switching time function d...

Страница 33: ...h optional external heat generator Optional external heat gener ator switched in but cannot guarantee ade quate heat delivery Check heat delivery by the optional auxiliary heater increase if necessary...

Страница 34: ...iggered E1 PCB fault heat pump external unit E6 Refrigerant compressor blocked E7 Fan block in the external heat pump unit E8 Flow rate too high in heat pump external unit EC Temperature in internal h...

Страница 35: ...frigerant with fluorinated greenhouse gases which damage the environment if released Coolant type R410A GWP value 2087 5 GWP Global Warming Potential Work on fixed cooling systems heat pumps and air c...

Страница 36: ...aining connection on the DAIKIN EKHHP see Fig 3 1 Item 10 bzw Mit Solarsystem Mount the KFE filling connection accessory KFE BA to the connection bracket of the control and pump unit EKSRPS4A Connect...

Страница 37: ...ing at a draw off rate of 12 l min TS 50 C litres 180 2 300 2 Hot water quantity without re heating at a flow rate of 12 l min TS 60 C litres 150 2 310 2 Hot water quantity without re heating at a flo...

Страница 38: ...e 1 TCW Cold water input temperature 10 C TDHW Hot water draw off temperature 40 C TS Storage target temperature charge state before drawing off 2 Charge hot water storage tank only with heat pump wit...

Страница 39: ...11 x Notes DAIKIN EKHHP 3 5 00AA2V3 DAIKIN Hot water heat pump 008 1423444_05 08 2016 Installation and operating instructions 39 11 Notes...

Страница 40: ...Installation and operating instructions 40 DAIKIN EKHHP 3 5 00AA2V3 DAIKIN Hot water heat pump 008 1423444_05 08 2016 11 x Notes...

Страница 41: ...11 x Notes DAIKIN EKHHP 3 5 00AA2V3 DAIKIN Hot water heat pump 008 1423444_05 08 2016 Installation and operating instructions 41...

Страница 42: ...uter layer of storage tank 14 35 Filling water 6 H Handle 8 Heat pump indoor unit 4 heating support 12 High Output 25 High low tariff mains connection 15 28 30 HT NT signal 15 Hydraulic connection Imp...

Страница 43: ...12 x List of keywords DAIKIN EKHHP 3 5 00AA2V3 DAIKIN Hot water heat pump 008 1423449_05 08 2016 Installation and operating instructions 43...

Страница 44: ...008 1423444_05 08 2016 Copyright Daikin...

Отзывы: