 Set-up and installation

4.7 Filling the system with water

Observe the information on the water connection and water 
quality in accordance with Chap. 2.4.5 and 4.4.

4.7.1 Filling the hot water heat exchanger

1. Open the shutoff valve for the cold water supply pipe.

2. Open the hot water tap connections so that the draw-off 

volume can be set as high as possible.

3. Once water has been discharged from the tap connections, 

do not interrupt the cold water flow; this will ensure that the 
heat exchanger will be fully vented and that any impurities or 
residue will be discharged.

4.7.2 Filling the storage tank 

See Section 9.2.

4.8 Electrical connection

– Network connections need to be executed as independent 

power circuits.

– Ensure power cables, sensor cables and data bus cables are 

laid separately from each other.

– Use only cable trunking with separate trays or cable trunking 

with separators that ensure at least 2 cm spacing.

– Cable cross-overs are not permissible.
– For all the cables connected to the DAIKIN EKHHP effective 

tension relief must be ensured in the controller housing using 
cable ties (see Figures 4-8 to 4-10).

WARNING!

If you operate the DAIKIN EKHHP when the 
storage tank is not completely full, damage to 
the equipment may occur.

Fill the DAIKIN EKHHP only after all the 
hydraulic installation work has been 
completed.

Observe the sequence during the filling 
process.

Commissioning only after all the installation 
work has been completed and only after 
filling the storage tank completely.

The corrugated pipe heat exchangers must be filled 
before the storage tank.

The heat exchanger for connecting an optional heat 

generator (Fig. 3-1, Item 14, only EKHHP500AA2V3) also 
needs to be filled if no optional heat generator is connected to it. 
This heat exchanger, and the heating circuit of the external heat 
generator connected to it, should be filled first.

UK only!

CAUTION!

If filling or topping up the storage tank is done by 
means of the boiler filling and drain valve, a 
temporary filling loop must be used with the 
appropriate backflow prevention device in 
accordance with clause G24.2, Guidance to the 
Water Supply (Water Fittings) Regulations 
1999.

WARNING!

Touching live parts can result in an 

electric 

shock 

and lead to potentially fatal injuries and 

burns.

Before beginning work on live parts, 

disconnect

 all of the systems circuits 

from 

the power supply 

(switch off main switch, 

disconnect fuse) and secure against uninten-
tional restart.

The electrical connection and working on the 
electrical components should only be 
performed by 

qualified electrical engineers

 

in compliance with valid standards and 
guidelines as well as the specifications of the 
energy supply company and the instructions 
given in this manual.

Never carry out any structural changes to 
plug sockets or other electrical equipment 
components.

The 

equipment covers and maintenance 

opening covers 

must be 

re-fitted 

immedi-

ately after completion of the work.

CAUTION!

In the controller housing of the 

DAIKIN

 

EKHHP

, in continuous running, 

elevated tem-

peratures

 can be generated. This can result in 

currently-carrying wires 

from reaching higher 

temperatures during operation due to self-
heating. For this reason, these 

lines need to

 

have a 

continuous use temperature of 90 °C

.

For the following connections, use only 
cables with a long-term use temperature 

90 °C:

– Exterior heat pump unit
– Voltage supplyBooster-Heater
– Contacts (connection HT/NT/Smart Grid)

Содержание EKHHP300AA2V3

Страница 1: ...Installation and operating instructions EKHHP300AA2V3 EKHHP500AA2V3 Hot water heat pump indoor unit Installation and operating instructions Hot water heat pump indoor unit English...

Страница 2: ...BSH 15 4 8 2 High low tariff mains connection HT NT 15 4 8 3 Connection EVU receiver intelligent regulator Smart Grid SG 16 4 8 4 Optional Connection of an external heat generator16 5 Start up 17 5 1...

Страница 3: ...tructed in the safe use of the equipment and under stand the dangers arising therefrom Children must not play with the equipment Cleaning and user maintenance must not be carried out by children witho...

Страница 4: ...ised safety related and occupational medical rules 2 3 Intended use The DAIKIN EKHHP system may only be used for the generation of hot water and only set up connected and operated in accordance with t...

Страница 5: ...e category III Means with contact separation in all poles that provide full disconnection must be incorpo rated in the fixed wiring in accordance with the wiring rules Compare the mains voltage 230 V...

Страница 6: ...tary water Water hardness calcium and magnesium calculated as calcium carbonate 3 mmol l Conductivity 1500 ideal 100 S cm Chloride 250 mg l Sulphate 250 mg l pH value 6 5 8 5 Using filling water and t...

Страница 7: ...escription DAIKIN EKHHP 3 5 00AA2V3 DAIKIN Hot water heat pump 008 1423444_05 08 2016 Installation and operating instructions 7 3 Product description 15 17 Fig 3 1 Structure of the DAIKIN EKHHP legend...

Страница 8: ...changer stainless steel for storage tank charging by hot water heat pump liquifier 42 Display external signal HT NT Smart Grid 14 Heat exchanger stainless steel for storage tank charging by pressurise...

Страница 9: ...on the DAIKIN EKHHP such as setup servicing connection and initial start up is only to be carried out by persons who are authorised and who have successfully completed qualifying technical or vocatio...

Страница 10: ...plosion risk environments is not permitted The DAIKIN EKHHP must only be set up in non hermetically closed rooms The electronic control system must not be subjected to atmospheric factors under any ci...

Страница 11: ...s and corrosion Observe the requirements for storage tank water see Section 2 4 6 CAUTION If the DAIKIN EKHHP is connected to a cold water line where steel pipes are used chips can enter the special s...

Страница 12: ...d solar heat exchanger Fig 3 1 and Tab 3 1 give the position and dimensions of the connections CArry out hydraulic system incorporation in accordance with Fig 4 5 Pay attention to the stipulated tight...

Страница 13: ...unit Open stop valve on exterior unit completely until the stop Tighten loosely Reassemble valve caps A DAIKIN EWQ B DAIKINEKHHP C Gas line D Liquid line E Oil trap arc H height to 1st oil trap max 1...

Страница 14: ...d before the storage tank The heat exchanger for connecting an optional heat generator Fig 3 1 Item 14 only EKHHP500AA2V3 also needs to be filled if no optional heat generator is connected to it This...

Страница 15: ...ND IN1 of the DAIKIN EKHHP see Fig 4 12 When the parameter 7 00 0 is set certain system compo nents are switched off in high tariff times see Section 7 5 The potential free switching contact GND IN1 c...

Страница 16: ...of the pa rameter 7 00 the heat pump is operated differently see Tab 7 3 4 8 4 Optional Connection of an external heat generator When using an external heat generator this can be connected using a pot...

Страница 17: ...tion Select a higher set hot water temperature so that the heating function is acti vated see Section 7 3 1 Sign the check list together with the operator Only if it is possible to answer all items on...

Страница 18: ...estic hot water heating in the DAIKIN EKHHP full and has it been bled Yes 4 1 Only EKHHP500AA2V3 Is the heat exchanger filled for the connection of an optional heat generator Yes 5 Is the storage tank...

Страница 19: ...ter connections due to escaping hot water Draining the storage tank only after it has cooled down for a longe nough period with a suitable device for the safe draining or catching of escaping water we...

Страница 20: ...nal heat pump unit When disposing of the machine or replacing parts in the coolant system Suction the coolant from the machine and recycle see instal lation and operating guide for the particular exte...

Страница 21: ...n it off and recycle using a suitable recycling device Always recycle coolant in so doing keeping it separated from oils and other additives Only store different types of coolant separately in suitabl...

Страница 22: ...urrent day of the week The set day is in dicated in the display in the programming mode 37 Display refrigerant compressor active This icon shows that the refrigerant compressor is active in the extern...

Страница 23: ...lfunctions arise through incorrect configu ration 7 2 1 Switching the system on and off Press the key The operation LED lights up red During start up the icon is shown in the display of the controller...

Страница 24: ...t pump external unit the controller switches over to the integrated Booster Heater BSH The Booster Heater BSH is only switched on if the hot water temperature has been set above the maximum temperatur...

Страница 25: ...parameter settings If the Booster Heater BSH is added in the controller dispaly shows the symbol 7 4 1 Display switching times 1 Press the key The current operating mode flashes 2 Use the and keys to...

Страница 26: ...5 secs confirms the end of the programming The fourth switching time and if there is one the fifth switch ing time will be deleted Deleting all switching times of an operating mode Only all switching...

Страница 27: ...p stops the reheating procedure 0 04 Activation temperature heat retention function Deter mines whether automatic reheating takes place if the temper ature falls below the parameter value 0 02 0 Funct...

Страница 28: ...tted 4 03 is not set to 0 6 03 Priority of High Output operating mode stipulates the priority if the operating modes Low Noise and High Output are active at the same time 6 04 Stages in the operating...

Страница 29: ...y setting 2 K 7 02 Emergency operation The parameter 7 02 is set to 0 in the factory If there is a fault in the heat pump external unit the parameter 7 02 1 can be set In addition the unit must be set...

Страница 30: ...atic restart after a power failure 1 0 1 1 01 Access authorisation 3 2 3 1 02 Hot water set temperature 60 C 0 0 1 1 4 03 Simultaneous operation of the electrical Booster Heater BSH and heat pump 0 0...

Страница 31: ...ed temperature C C C C C TUE switching time Action On Off ON OFF ON OFF ON OFF ON OFF ON OFF feed temperature C C C C C WED switching time Action On Off ON OFF ON OFF ON OFF ON OFF ON OFF feed tempera...

Страница 32: ...ammed switching times are being carried out at the wrong time Day of the week and time are not correctly set Set the weekday Set time Check week day switching time allocation Switching time function d...

Страница 33: ...h optional external heat generator Optional external heat gener ator switched in but cannot guarantee ade quate heat delivery Check heat delivery by the optional auxiliary heater increase if necessary...

Страница 34: ...iggered E1 PCB fault heat pump external unit E6 Refrigerant compressor blocked E7 Fan block in the external heat pump unit E8 Flow rate too high in heat pump external unit EC Temperature in internal h...

Страница 35: ...frigerant with fluorinated greenhouse gases which damage the environment if released Coolant type R410A GWP value 2087 5 GWP Global Warming Potential Work on fixed cooling systems heat pumps and air c...

Страница 36: ...aining connection on the DAIKIN EKHHP see Fig 3 1 Item 10 bzw Mit Solarsystem Mount the KFE filling connection accessory KFE BA to the connection bracket of the control and pump unit EKSRPS4A Connect...

Страница 37: ...ing at a draw off rate of 12 l min TS 50 C litres 180 2 300 2 Hot water quantity without re heating at a flow rate of 12 l min TS 60 C litres 150 2 310 2 Hot water quantity without re heating at a flo...

Страница 38: ...e 1 TCW Cold water input temperature 10 C TDHW Hot water draw off temperature 40 C TS Storage target temperature charge state before drawing off 2 Charge hot water storage tank only with heat pump wit...

Страница 39: ...11 x Notes DAIKIN EKHHP 3 5 00AA2V3 DAIKIN Hot water heat pump 008 1423444_05 08 2016 Installation and operating instructions 39 11 Notes...

Страница 40: ...Installation and operating instructions 40 DAIKIN EKHHP 3 5 00AA2V3 DAIKIN Hot water heat pump 008 1423444_05 08 2016 11 x Notes...

Страница 41: ...11 x Notes DAIKIN EKHHP 3 5 00AA2V3 DAIKIN Hot water heat pump 008 1423444_05 08 2016 Installation and operating instructions 41...

Страница 42: ...uter layer of storage tank 14 35 Filling water 6 H Handle 8 Heat pump indoor unit 4 heating support 12 High Output 25 High low tariff mains connection 15 28 30 HT NT signal 15 Hydraulic connection Imp...

Страница 43: ...12 x List of keywords DAIKIN EKHHP 3 5 00AA2V3 DAIKIN Hot water heat pump 008 1423449_05 08 2016 Installation and operating instructions 43...

Страница 44: ...008 1423444_05 08 2016 Copyright Daikin...

Отзывы: