Operation manual

15

EKHBH/X016BB

Indoor unit and options for air to water heat pump system

4PW62573-1 – 10.2010

Only for tank without electrical booster heater (EKHTS)

According to local and national regulations, it may be required to
disinfect the domestic hot water tank at a higher temperature
(>60°C). In that case Daikin suggests to install a shunt pump and a
heater element parallel on the domestic hot water tank according to
the figure below.

1

Domestic hot water tank

2

Shunt pump (field supply)

3

Heater element (field supply)

4

Non-return valve (field supply)

5

Shower (field supply)

6

Indoor unit

[3] Auto restart

When power returns after a power supply failure, the auto restart
function reapplies the user interface settings at the time of the power
supply failure.

Note that with the function disabled the schedule timer will not be
activated when power returns to the unit after a power supply failure.
Press the 

pr

 button to enable the schedule timer again.

[3-00] Status: defines whether the auto restart function is
turned 

ON (0)

 or 

OFF (1)

.

[4] Space heating off temperature

Space heating off temperature

[4-02] Space heating off temperature: outdoor temperature
above which space heating is turned off to avoid overheating.

[6] Scheduled storage and reheat domestic water heating

Scheduled domestic hot water storage

The storage set point can be accessed directly using the 

wi

 and

wj

 buttons.

[6-03] Scheduled storage: defines whether the scheduled
domestic water heating storage during night is enabled (1) or
not (0).

[6-04] Scheduled storage start time: time of the night at which
the domestic water should be heated.

Scheduled/continuous domestic hot water reheat

[6-05] Reheat: defines whether the scheduled domestic water
reheat during daytime is enabled (1) or continuous reheat is
enabled (2) or reheat is disabled (0)

[6-06] Scheduled reheat start time: time of the day at which the
domestic water should be heated.

[6-07] Domestic hot water reheat set point

[6-08] Domestic hot water reheat set point hysteresis

Example 1

: Scheduled storage [6-03]=1, scheduled reheat [6-05]=1,

disinfection function [2-01]=1 activated.

A Scheduled storage operation:

 activated at [6-04], heat 

up domestic hot water untill domestic hot water user 
interface set point T

DHW

 (e.g 55°C) is reached.

B Scheduled reheat operation

: activated at [6-06], heat up 

domestic hot water untill domestic hot water reheat set 
point [6-07] (e.g 45°C ) is reached. 

C Disinfection operation

 (if activated): activated at [2-02], 

heat up domestic hot water untill domestic hot water 
disinfection set point [2-03] (e.g 60°C) is reached. Refer to 

"[2] Disinfection function" on page 14

.

t

Time

T

Domestic hot water temperature

T

DHW

Domestic hot water user interface set point

Example 2

: Scheduled storage [6-03]=1, continuous reheat [6-05]=2,

disinfection function [2-01]=1 activated.

A Scheduled storage operation:

 activated at [6-04], heat 

up domestic hot water untill domestic hot water user 
interface set point T

DHW

 (e.g 55°C) is reached.

B Continuous reheat operation

: continues activated heat 

up domestic water till domestic hot water reheat set point 
[6-07] (e.g 45°C) is reached with a hysteresis of [6-08]. 

C Disinfection operation

 (if activated): activated at [2-02], 

heat up domestic hot water untill domestic hot water 
disinfection set point [2-03] (e.g 60°C) is reached. Refer to 

"[2] Disinfection function" on page 14

.

t

Time

T

Domestic hot water temperature

T

DHW

Domestic hot water user interface set point

WARNING

Never heat up the domestic water tank temperature higher
than 80°C. This will cause damage to the equipment and
potentially danger of leakage of hot water which can cause
burning wounds.

NOTICE

It is therefore recommended to leave the auto restart
function enabled.

NOTICE

If the benefit kWh rate power supply is of the type that
power supply is interrupted, then always allow the auto
restart function.

If you feel unsure about this topic, contact your installer for
advice and information.

INFORMATION

The scheduled storage and reheat domestic water heating
will only be carried out when [4-03]=4 or 5 and the
domestic water heating mode is enabled by the 

w

 button.

2

1

6

3

5

4

A

B

C

T

t

[2-03]

T

DHW

[6-07]

[6-04]

[6-06]

[2-02]

A

B

C

[6-08]

B

T

t

[2-03]

[6-07]

T

DHW

[6-04]

[2-02]

Содержание EKHBH016BB3V3

Страница 1: ...BB EKHBX016BB Indoor unit and options for air to water heat pump system EKHBH016BB3V3 EKHBH016BB6V3 EKHBH016BB6WN EKHBH016BB6T1 EKHBH016BB9WN EKHBH016BB9T1 EKHBX016BB3V3 EKHBX016BB6V3 EKHBX016BB6WN EK...

Страница 2: ...this manual are classified according to their severity and probability of occurrence Some types of danger are represented by special symbols 1 2 Meaning of used terms Installation manual Instruction m...

Страница 3: ...ent sizes 200 and 260 litre Solar kit for domestic hot water tank option For information concerning the EKSOLHW solar kit refer to the installation manual of that kit Room thermostat kit option An opt...

Страница 4: ...ipate this gas safely it is recommended that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there mu...

Страница 5: ...ATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whe...

Страница 6: ...orage set point of the domestic hot water temperature only for 4 03 4 or 5 The buttons are not used when the domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or disa...

Страница 7: ...int upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached Preferally this is done during the time...

Страница 8: ...ng operation 1 Press v for 5 seconds to activate powerful domestic water heating operation For EKHW only Icons w and m start flashing 1 For EKHTS only Icons w and start flashing 2 Powerful domestic wa...

Страница 9: ...iquid refrigerant temperature u The outdoor temperature w The domestic hot water temperature INFORMATION Only use the pr button to enable or disable the schedule timer The schedule timer overrules the...

Страница 10: ...m at the very end of this manual This form can help you define the required actions for each day Keep in mind that In the space heating and domestic water heating program 4 actions can be programmed p...

Страница 11: ...e programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the...

Страница 12: ...select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For quiet mode and booster heater...

Страница 13: ...button The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the but...

Страница 14: ...n 6 Repeat step 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user i...

Страница 15: ..._Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi2_A Note that the Hi2_Ti value should be lower than Lo2_Ti as for warmer out...

Страница 16: ...nt hysteresis Example 1 Scheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domest...

Страница 17: ...ng automatic storage during night default setting If it seems that the domestic hot water night storage operation is not sufficient for your needs an additional scheduled reheat during daytime can be...

Страница 18: ...it refer to the installation manual of that kit d Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent field setting is only relevant in case...

Страница 19: ...n All 01 Status 1 ON 0 1 02 Start time 23 00 0 00 23 00 1 00 hour 03 Set point only in combination with domestic hot water tank without electrical booster heater EKHTS 60 fixed 5 C 03 Set point only i...

Страница 20: ...related setting 9 Heating and cooling set point ranges 00 Heating set point upper limit 55 37 55 1 C 01 Heating set point lower limit 25 15 37 1 C 02 Cooling set point upper limit 22 18 22 1 C 03 Coo...

Страница 21: ...Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Do not change the default value depending on model 03 Liquid refrigerant temperature Re...

Страница 22: ...nt of oil and other parts must be done by a qualified installer in accordance with the applicable legislation Units must be treated at a specialized treatment facility for re use recycling and recover...

Страница 23: ......

Страница 24: ...4PW62573 1 10 2010 Copyright 2010 Daikin...

Отзывы: