background image

Operation manual

11

EKHBH/X016BB

Indoor unit and options for air to water heat pump system

4PW62573-1 – 10.2010

Programming space cooling, quiet mode, or booster heater
mode

(1)

Programming space cooling, quiet mode, or booster heater mode

(1)

is carried out as follows:

1

Press the 

<

 button.

The actual mode is blinking.

2

Use the 

pi

 and 

pj

 buttons to select the mode you want

to program (space cooling

 c

, quiet mode 

s

, or booster heating

m

(1)

).

The selected mode is blinking.

3

Press the 

<

 button to confirm the selected mode.

The first programmed action is displayed.

4

Use the 

pi

  and 

pj

  buttons to consult the programmed

actions.

This is called the readout mode. Empty program actions (e.g. 3
and 4) are not displayed.

5

Press the 

<

  button for 5 seconds to enter the programming

mode.

6

Use the 

<

 button to select the action number you would like to

program or to modify.

7

Use the 

pi

 and 

pj

 buttons to set the correct action time.

8

Use the 

ba

 button to select:

For space cooling:
-

x

: switch cooling and the controller off.

-

9

: set the temperature by means of the 

bi

 and 

bj

 buttons.

-

a

: to select automatic temperature calculation.

For quiet mode and booster heater mode

(1)

:  use the 

ba

button to enable or disable the 

x

 action.

9

Repeat steps 

6

 to 

8

 to program the other actions of the selected

mode.

When all actions have been programmed, make sure that the
display shows the highest action number you would like to save.

10

Press the 

<

  button for 5 seconds to store the programmed

actions.

If the 

<

  button is pressed when action number 3 is displayed,

actions 1, 2 and 3 are stored but 4 is deleted.
You automatically return to step 

4

.  By pressing the 

pr

  button

several times, you return to previous steps in this procedure and
finally return to normal operation.

(1) Only applicable for tank with built-in electrical booster heater (EKHW*).

5 sec

5 sec

5 sec

5 sec

INFORMATION

Returning to previous steps in the programming procedure
without saving modified settings is done by pressing the

pr

 button.

INFORMATION

Programming the booster heater operation

(1)

  time is only

valid if field setting [4-03]=1, 2, or 3.

Содержание EKHBH016BB3V3

Страница 1: ...BB EKHBX016BB Indoor unit and options for air to water heat pump system EKHBH016BB3V3 EKHBH016BB6V3 EKHBH016BB6WN EKHBH016BB6T1 EKHBH016BB9WN EKHBH016BB9T1 EKHBX016BB3V3 EKHBX016BB6V3 EKHBX016BB6WN EK...

Страница 2: ...this manual are classified according to their severity and probability of occurrence Some types of danger are represented by special symbols 1 2 Meaning of used terms Installation manual Instruction m...

Страница 3: ...ent sizes 200 and 260 litre Solar kit for domestic hot water tank option For information concerning the EKSOLHW solar kit refer to the installation manual of that kit Room thermostat kit option An opt...

Страница 4: ...ipate this gas safely it is recommended that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there mu...

Страница 5: ...ATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whe...

Страница 6: ...orage set point of the domestic hot water temperature only for 4 03 4 or 5 The buttons are not used when the domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or disa...

Страница 7: ...int upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached Preferally this is done during the time...

Страница 8: ...ng operation 1 Press v for 5 seconds to activate powerful domestic water heating operation For EKHW only Icons w and m start flashing 1 For EKHTS only Icons w and start flashing 2 Powerful domestic wa...

Страница 9: ...iquid refrigerant temperature u The outdoor temperature w The domestic hot water temperature INFORMATION Only use the pr button to enable or disable the schedule timer The schedule timer overrules the...

Страница 10: ...m at the very end of this manual This form can help you define the required actions for each day Keep in mind that In the space heating and domestic water heating program 4 actions can be programmed p...

Страница 11: ...e programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the...

Страница 12: ...select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For quiet mode and booster heater...

Страница 13: ...button The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the but...

Страница 14: ...n 6 Repeat step 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user i...

Страница 15: ..._Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi2_A Note that the Hi2_Ti value should be lower than Lo2_Ti as for warmer out...

Страница 16: ...nt hysteresis Example 1 Scheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domest...

Страница 17: ...ng automatic storage during night default setting If it seems that the domestic hot water night storage operation is not sufficient for your needs an additional scheduled reheat during daytime can be...

Страница 18: ...it refer to the installation manual of that kit d Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent field setting is only relevant in case...

Страница 19: ...n All 01 Status 1 ON 0 1 02 Start time 23 00 0 00 23 00 1 00 hour 03 Set point only in combination with domestic hot water tank without electrical booster heater EKHTS 60 fixed 5 C 03 Set point only i...

Страница 20: ...related setting 9 Heating and cooling set point ranges 00 Heating set point upper limit 55 37 55 1 C 01 Heating set point lower limit 25 15 37 1 C 02 Cooling set point upper limit 22 18 22 1 C 03 Coo...

Страница 21: ...Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Do not change the default value depending on model 03 Liquid refrigerant temperature Re...

Страница 22: ...nt of oil and other parts must be done by a qualified installer in accordance with the applicable legislation Units must be treated at a specialized treatment facility for re use recycling and recover...

Страница 23: ......

Страница 24: ...4PW62573 1 10 2010 Copyright 2010 Daikin...

Отзывы: