7
Parameter settings
Operating Instructions
39
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
7.6
Configuration
[→ Main menu → Configuration]
7.6.1
Menu: Sensors
[→ Main menu → Configuration → Sensors]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE HF
Outside tem-
perature
sensor (*)
Integrated sensor Selection of whether the sensor integrated in the outdoor unit or an optional
outside temperature sensor is used to determine the target feed temperat-
ures
-
N
E
Optional sensor
Tank temper-
ature sensor
Configuration of the domestic hot water preparation:
-
N
E
Inactive
No function for domestic hot water preparation.
Sensor
Function for domestic hot water preparation is activated. A storage temper-
ature sensor is evaluated for domestic hot water preparation (if no storage
temperature sensor is connected, an error message is generated).
Thermostat
Function for domestic hot water preparation is activated. A thermostatic
switch (ON/OFF) is evaluated for domestic hot water preparation, where an
"open terminal" is evaluated as "not required".
Water pres-
sure sensor
Configuration of the sensor for detecting the water pressure of the system.
-
N
E
Off
No sensor evaluation
On
Sensor evaluation activated (if no pressure sensor is connected, an error
message is generated.)
Adjustment
outside tem-
perature
-5.0 - +5.0 K
Individual adjustment for the measured value of the outside temperature
relevant for the control unit.
0.0 K
0.1 K
N
E
Water pres-
sure min.
0.1 - 5.0 bar
Defines the minimum water pressure.
Pressure monitor function (only with activated pressure sensor, [Water
pressure sensor]=On): If the measured value undercuts the set value, the
Daikin Altherma EHS(X/H) is shut off and an error message is generated.
0.5 bar
0.1 bar
N
E
Water pres-
sure max.
0.1 - 5.0 bar
Defines the maximum water pressure.
Pressure monitoring function (only with activated pressure sensor, [Water
pressure sensor]=On): If the measured value exceeds the set value, a
warning message is generated.
3.0 bar
0.1 bar
N
E
Water pres-
sure target
0.1 - 5.0 bar
Defines the target water pressure.
Pressure monitoring function (only with activated pressure sensor, [Water
pressure sensor] = on): If the measured value undercuts the value set in
the [Maximum pressure loss] parameter, a warning message is generated.
0.9 bar
0.1 bar
N
E
Max. pressure
drop
0.1 - 5.0 bar
Defines the maximum acceptable pressure loss in the heating system.
Pressure monitoring function (only with activated pressure sensor, [Water
pressure sensor]=On): If the measured value undercuts the value set in the
[Water pressure target] parameter by more than the set value, a warning
message is generated.
0.5 bar
0.1 bar
N
E
Tab. 7-20
Parameter in menu: "Sensors"
Содержание EHSHB04P30D
Страница 2: ......
Страница 354: ...11 Indice analitico Istruzioni per l uso 64 Daikin RoCon HP Daikin Regolazione RoCon HP 008 1444299_01 09 2018 IT...
Страница 530: ...11 Seznam hesel N vod k provozu 60 Daikin RoCon HP Daikin Regulace RoCon HP 008 1444299_01 09 2018 CS...
Страница 531: ...11 Seznam hesel N vod k provozu 61 Daikin RoCon HP Daikin Regulace RoCon HP 008 1444299_01 09 2018 CS...
Страница 532: ...008 1444299_01 09 2018 EN DE FR NL ES IT PT SV CS Copyright Daikin...