9
Mixer module
Operating Instructions
53
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
9.3
Mixer module parameter settings
The parameters available for the mixer module are largely identical
to the parameter described in
lists the additional
parameters available for the mixer module.
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE HF
Min. mixer
valve pump
10 - 100%
[→ Main menu → System]
Minimum power of the pump in the mixer circuit.
30%
1%
N
E
Max. mixer
valve pump
20 – 100%
[→ Main menu → System]
Maximum power of the pump in the mixer circuit.
100%
1%
N
E
Slope offset
0 - 50 K
[→ Main menu → Heating]
Setting of the slope offset of the feed target temperature on the Daikin
Altherma EHS(X/H) in comparison with the feed target temperature determ-
ined for the mixer circuit.
5 K
1 K
N
E
Mixer temper-
ature, current
0 – 100 °C
[→ Main menu → Information → Values]
Current feed temperature in the mixer circuit
-
-
S
S
Mixer temper-
ature, target
0 – 90 °C
[→ Main menu → Information → Values]
Current target feed temperature in the mixer circuit
-
-
S
S
Mixer pump
status
On
[→ Main menu → Information → Values]
Current status of the mixer pump
-
-
S
S
Off
PWM mixer
pump
0 – 100%
[→ Main menu → Information → Values]
Current modulation of the mixer pump
-
-
S
S
Mixer valve
status
Neutral
[→ Main menu → Information → Values]
Current status of the mixer valve
-
-
S
S
Closed
Open
Tab. 9-2
Parameters of the mixer module
Содержание EHSHB04P30D
Страница 2: ......
Страница 354: ...11 Indice analitico Istruzioni per l uso 64 Daikin RoCon HP Daikin Regolazione RoCon HP 008 1444299_01 09 2018 IT...
Страница 530: ...11 Seznam hesel N vod k provozu 60 Daikin RoCon HP Daikin Regulace RoCon HP 008 1444299_01 09 2018 CS...
Страница 531: ...11 Seznam hesel N vod k provozu 61 Daikin RoCon HP Daikin Regulace RoCon HP 008 1444299_01 09 2018 CS...
Страница 532: ...008 1444299_01 09 2018 EN DE FR NL ES IT PT SV CS Copyright Daikin...