Operating instructions
40
Daikin Altherma EHS(X/H)
Daikin Altherma integrated solar unit
008.1420944 – 05/2014
6
x
Parameter settings
T-Room Adj
Only if the room station
is connected and assigned to the heating circuit.
Individual adaptation of the room temperature relevant for control.
Should a systematic deviation of the room temperature as measured by the EHS157034 from
the actual temperature in the living area of this room be detected, the measured value can be
corrected by the set value.
E
E
-5.0 to +5.0 kW
0.0 K
1 K
T-Flow Day
Only if the parameter [HC Function] = 1 is in delivery status is this function activated. It can only
be changed with a technician code. Contact your specialist heating technician in this regard:
Setting the inflow target temperature for the heating circuit during the heating time when in op-
erating mode: "Automatic 1", "Automatic 2", "Heating".
E
E
20 - 90°C
40 °C
1 °C
T-Flow Night
Only if the parameter [HC Function] = 1 is in delivery status is this function activated. It can only
be changed with a technician code. Contact your specialist heating technician in this regard:
Setting the inflow target temperature for the heating circuit during the setback time when in op-
erating mode: "Automatic 1", "Automatic 2", "Reducing".
E
E
10 - 90°C
10 °C
1 °C
T-Frost Protect
Off: No frost protection of the heating circuit
Otherwise: If the outside temperature falls below the programmed value, the system switches
into the frost protection mode (switches the pumps on). The function ceases once the outside
temperature has risen to the set value +1 K.
E
E
Off,
-5 to +5 °C
0 °C
1 °C
Insulation
Setting the insulation standard of the building. This affects the way the heating curve and the
heating times automatically adapt to the outside temperature.
E
E
Off
Low
Normal
Good
Very good
Normal
-
Start T-Out Cooling
Can be used only if the assigned heat generator has a cooling function
.
Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It can only
be changed with a technician code. Contact your specialist heating technician in this regard:
Setting from which outside temperature the cooling operation with the highest cooling infeed
target temperature [T-Flow Cooling start] starts (Setting condition: Operating mode "Cooling").
E
E
20 - 45°C
24 °C
1 °C
Max T-Out Cooling
Can be used only if the assigned heat generator has a cooling function
.
Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It can only
be changed with a technician code. Contact your specialist heating technician in this regard:
Setting to determine from which outdoor temperature the lowest cooling flow temperature
[T-Flow Cooling max] is stipulated (Setting condition: Operating mode "Cooling").
E
E
20 - 45°C
35 °C
1 °C
T-Flow Cooling start Can be used only if the assigned heat generator has a cooling function
.
Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It can only
be changed with a technician code. Contact your specialist heating technician in this regard:
Setting the cooling inflow target temperature at the start of cooling mode (outside
temperature = parameter [Start T-Out Cooling]).
E
E
5 - 25°C
18 °C
1 °C
T-Flow Cooling max Can be used only if the assigned heat generator has a cooling function
.
Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It can only
be changed with a technician code. Contact your specialist heating technician in this regard:
Setting the minimum cooling inflow target temperature. This is kept constant relative to the out-
side temperature (parameter [Max T-Out Cooling]).
E
E
5 - 25°C
18 °C
1 °C
T-Flow Cooling
Can be used only if the assigned heat generator has a cooling function
.
Only if the parameter [HC Function] = 1 is in delivery status is this function activated. It can only
be changed with a technician code. Contact your specialist heating technician in this regard:
Setting the cooling inflow target temperature (fixed value) when cooling mode is active.
E
E
8 - 30°C
18 °C
1 °C
Tab. 6-15
Parameter in rotary switch setting "Configuration" level "Mixer Config"
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF