Operating instructions

22

 Daikin Altherma EHS(X/H)

Daikin Altherma integrated solar unit

008.1420944 – 05/2014

x

 Operation

Select the 

"Setup"

 level with the rotary switch.

An overview is displayed.

Use the rotary switch to select and confirm the [Language], 
[Date] or [Time] parameters.

Select and change the value to be changed within the 
individual display using the rotary switch.

Confirm the changes with a brief push of the rotary switch.

Change has been accepted. Jump back to previous dis-
play.

More detailed explanations and possible setting values for this rotary switch setting 
can be seen in section 3.6 and in chapter 6.2.

3.4.9 Terminal function

In the rotary switch setting 

"Remote Param" 

, if terminal 

mode is activated, other controllers in the RoCon system can also 
be parameterised via the controller integrated in the CAN bus.

After activation of the "Bus - Scan" a list of the equipment that 
was recognised is shown for selection in the display (external 
equipment and local equipment).

After selection and acknowledgement of an external item of 
equipment, this is shown on the local Controller. The local control 
element acts as the remote control for the external equipment. In 
this case all the control functions are provided and saved 1:1 as 
on the external equipment. 

During this terminal function the header of the display carries ad-
ditional information on the remotely controlled equipment; the 
symbol 

#X indicates the bus ID setting for the remotely con-

trolled equipment.

The displayed values and symbols are always loaded from the 
selected equipment (such as the mixer circuit infeed temperature 
of the mixer module EHS157068).

For operation of the local equipment, this must be activated again 
in the selection list (parameter [No selection]).

Activating / Deactivating normal operation

Requirement: A valid terminal address is assigned to the 
RoCon B1 control element of the Daikin Altherma EHS(X/H) or 
the EHS157034 room station.

Use the rotary switch to select the parameter [New scan?] 
and confirm with "Yes".

Bus - Scan is performed.

An overview of all the equipment found is displayed.

Use the rotary switch to select the equipment for which the 
terminal function is to be performed.

Confirm the changes with a brief push of the rotary switch.

The local control element acts as the remote control for 
the external equipment.

To 

end

 

terminal mode

 and restore operation of the assigned 

equipment to the control element, at the 

level "

Remote Param

"

 

the 

parameter [No selection]

 

must be selected and acknowl-

edged

 (see fig. 3-10).

Fig. 3-9

Display example for a remotely controlled mixer module

If the message "n. A." is displayed at rotary switch set-
ting 

, the control unit has yet to be assigned a valid 

terminal address.

If the message "n. A." is still displayed it may be nec-
essary to update the device software before the ter-
minal function can be used. Contact the Daikin Service 
Team in such cases.

The terminal address can be set only after the Techni-
cian password has been input. Contact your specialist 
heating technician in this regard. 

Place the rotary switch in 
the 

"Remote Param"

 

 

position.

The level "

Remote 

Param

" is displayed.

Select the parameter 

[Bus - Scan] with the 
rotary switch.

Confirm the changes with 
a brief press of the rotary 
switch.

The context menu is 
displayed.

Fig. 3-10 Display of the level "Re-

mote Param" at commis-
sioning or temporary 
disconnection from the 
mains

Remote Param

Bus - Scan

No selection

Содержание EHSH04P30A

Страница 1: ...A EHS X H B04P30A EHS X H 08P30A EHS X H B08P30A EHS X H 08P50A EHS X H B08P50A EHS X H 16P50A EHS X H B16P50A Indoor unit for air water heat pumps Daikin Altherma integrated solar unit Operating instructions Daikin Altherma integrated solar unit English ...

Страница 2: ...Legionella protection 27 3 6 7 Reset to factory settings Reset 27 3 6 8 Settings for optional circulation pump 27 3 6 9 Remote control via Internet 28 4 Commissioning 29 4 1 Initial commissioning 29 4 2 Re commissioning 29 4 2 1 Requirements 29 4 2 2 Start up 29 5 Decommissioning 30 5 1 Temporary shutdown 30 5 1 1 Draining the storage tank 30 5 1 2 Draining the heating circuit and hot water circui...

Страница 3: ...me information in this manual has limited validity The validity is highlighted by a symbol 1 2 3 Handling instructions Instructions on actions are shown as a list Actions of which the sequential order must be maintained are numbered 1 3 Avoid danger The Daikin Altherma EHS X H is state of the art and is built to meet all recognised technical requirements However improper use may result in serious ...

Страница 4: ...wledge of the subject of proper and appropriate installation and maintenance of heating climate control and cooling installations and heat pumps Electrical installation may be carried out only by electrical engineers and in compliance with the valid electro technical guidelines as well as the regulations of the relevant energy supply company EVU Observe the current technological regulations to pre...

Страница 5: ...re the energy supply company EVU is afforded the opportunity to control their network utilisation by changing the heat pump oper ating mode Information on the prerequisites and connection pos sibilities are described in the enclosed installation manual 2 1 1 Mode of operation In room heating mode the refrigerant which was compressed in the refrigerant compressor in the heat pump external unit con ...

Страница 6: ...rig erant or undefined operating states a safety switch off is per formed A corresponding fault signal provides an engineer with all the necessary information for troubleshooting 2 1 4 Electronic control Depending on the heating unit the RoCon HP electronic digital controller automatically controls all the heating cooling and hot water functions for a direct heating circuit a storage tank charging...

Страница 7: ...grated solar unit 008 1420944 05 2014 Operating instructions 7 2 2 2 Device external and internal design Daikin Altherma EHS X H P30A Fig 2 2 Design and components of the Daikin Altherma EHS X H P30A external view and internal design For legend descriptions see tab 2 1 ...

Страница 8: ...rated solar unit 008 1420944 05 2014 2 x Product description 2 2 3 Device external and internal design Daikin Altherma EHS X H B P30A Fig 2 3 Design and components of the Daikin Altherma EHS X H B P30A external view and internal design For legend descriptions see tab 2 1 ...

Страница 9: ...grated solar unit 008 1420944 05 2014 Operating instructions 9 2 2 4 Device external and internal design Daikin Altherma EHS X H P50A Fig 2 4 Design and components of the Daikin Altherma EHS X H P50A external view and internal design For legend descriptions see tab 2 1 ...

Страница 10: ...grated solar unit 008 1420944 05 2014 2 x Product description 2 2 5 Device external and internal design Daikin Altherma EHS X H B P50A Fig 2 5 Design and components of the Daikin Altherma EHS X H B P50A external view and internal design For legend descriptions see tab 2 1 ...

Страница 11: ...l backup heater EKBUxx 19 Submersible sensor sleeve for storage tank temperature sensor tDHW1 and tDHW2 20 Unpressurised storage tank water 21 Solar zone 22 Hot water zone 23 Safety overflow connection 24 Mount for handle 25 Type plate 26 Protective cover 27 Solar Return 28 Solar Flow 3 4 IG nur Typ Daikin Altherma EHS X H B 29 Solar Return flow 3 4 IG nur Typ Daikin Altherma EHS X H B 30 Panel he...

Страница 12: ...Backup Heater is used at inflow target temperatures of over 50 C the efficiency COP of the Daikin Altherma EHS X H can be affected negatively depending on the outside temperature 1 Clear text display 2 Setting Configuration 3 Setting Remote Param 4 Rotary switch 5 Setting Info 6 Setting Operating Mode 7 Setting Set Temp Day 8 Setting Set Temp Night 9 Setting DHW Set Temp 10 Rotary button 11 Settin...

Страница 13: ... BH is displayed In the case of no demands from the heat pump the abbreviation ES is displayed instead of the current inflow temperature The control system has switched to energy saving mode see section 3 4 2 Superfluous elec tronic components are switched off 5 Mixer circuit The current inflow temperature of the se lected heating circuit is displayed 5 Room temperature sensor The current room tem...

Страница 14: ... is displayed first Select the language using the rotary switch Confirm the changes with a brief press of the rotary switch When the system is switched on based on the stipulations set in the Controller RoCon HP it fully automatically regulates the operation of the room heating room cooling and the sanitary hot water generation If the user enters a value manually this setting remains active until ...

Страница 15: ...n Info In this rotary switch position the rotary switch can be used to call up all the system temperatures the type of Daikin Altherma EHS X H various software information and the operating sta tuses of all system components one after the other The number of displayed parameters depends on the connected components No settings can be made to these values Place the rotary switch in the Info position...

Страница 16: ...rks in normal mode RT Parameter Room thermostat Interlink fct Off Parameter Room thermostat On Heating or cooling demand No heating demand Parameter Interlink fct On priority Only frost protection IL1 Normal inflow target temperature IL2 Increased inflow target temperature in heating operation Decreased inflow target temperature in cooling operation Pump Actual output of the internal heating circu...

Страница 17: ... operating mode with the rotary switch Confirm the changes with a brief push of the rotary switch Daikin Altherma EHS X H operates in accordance with the set operating mode The current operating mode is indicated by an appropriate symbol in the standard display Operating mode Standby Stand by In this mode the Daikin Altherma EHS X H is shifted to the stand by mode The frost protection function see...

Страница 18: ...nt temporary heating programmes available see tab 3 6 which run according to priority after they have been activated Tab 3 6 Overview of temporary timer programmes 3 4 3 Temperature setting Daytime room temperature The set room temperatures for room heating during the day are determined in the rotary switch setting Place the rotary switch in the Set Temp Day position An overview is displayed Selec...

Страница 19: ...rogram Various different timer programmes are available that are set in the factory but which can be adjusted to suit to provide conven ient and individual room and hot water temperature control The timer programmes regulate the associated heating circuit the storage tank charging circuit and an option connected circu lation pump in accordance with the stipulated switching times Adjustment In the ...

Страница 20: ...ime settings for one switching cycle in one weekday or block programme are also adopted for other time pe riods provided that they affect the same weekdays Ex amples referring to tab 3 7 a For the single working day Monday the start time for the 1st switching cycle changed from 06 00 to 05 00 In the time period Working week and Entire week the 1st switching cycle also changed from 06 00 to 05 00 b...

Страница 21: ...ode according to the room temperature set in the rotary switch setting Set Temp Night in the parameter T Absence Hot water generation according to the set temperatures and switching cycles in the hot water time programme DHW Program 1 see section 3 4 5 The calendar controlled programme Vacation is not started if the operating mode Standby or Manual Oper ation is active on the set start date 3 4 8 ...

Страница 22: ...ature of the mixer module EHS157068 For operation of the local equipment this must be activated again in the selection list parameter No selection Activating Deactivating normal operation Requirement A valid terminal address is assigned to the RoCon B1 control element of the Daikin Altherma EHS X H or the EHS157034 room station Use the rotary switch to select the parameter New scan and confirm wit...

Страница 23: ...ing the exit button again or Briefly pressing the rotary switch or Selecting a different menu using the rotary switch 3 5 1 Manual Operation Manual Operation is used to regulate the Daikin Altherma EHS X H manually to a specific flow temperature The manual mode should only be used for diagnostic purposes With hydraulically controlled priority operation for the hot water generation you must make su...

Страница 24: ...mperature limits that have been set for the corre sponding heating circuit The room temperature measured in the living area may differ from the desired room temperature these deviations can be kept to a minimum by installing a room station or a room thermostat The Controller is configured in the factory so that the heating curve does not adjust itself during operation The automatic heat curve adju...

Страница 25: ...osition or b via the room thermostat function cooling switching contact closed No heating demand active in the heating system The cooling characteristic curve is specified using the following four parameters 1 Start T Out Cooling 2 Max T Out Cooling 3 T Flow Cooling start 4 T Flow Cooling max During the weather controlled flow temperature regulation the user can adjust the inflow target temperatur...

Страница 26: ...tonomously control the assigned heating circuit fully independently of the Daikin Altherma EHS X H More detailed explanations and possible setting values for this function can be seen in sections 6 2 3 and 6 12 2 3 6 5 Frost protection function If the outdoor temperature is below the parameter value T Frost Protect the integrated heating circulation pump is switched on in order to prevent the heat...

Страница 27: ...cian access rights permit all customer specific pa rameter settings in the Special Level to be reset to the factory setting according to tab 6 1 to tab 6 11 Possibility 3 If fundamental changes to the Daikin Altherma EHS X H equipment for the function within the RoCon system are nec essary the Basic Configuration can be reset using Technician access rights to the Factory settings or can be redefin...

Страница 28: ...uated by the active hot water timer programme ON or from a separate timer programme OFF Circl Pump Interval Setting the interval control for an optional circulation pump Confirm the changes with a brief push of the rotary switch Setting parameters Confirm the changes with a brief push of the rotary switch The circulation pump is actuated in accordance with the settings made by the Controller RoCon...

Страница 29: ...ltherma EHS X H not put into operation properly can lead to damage to property and the envi ronment Minimum requirements regarding the quality of filling and supplementary water Water hardness calcium and magnesium cal culated as calcium carbonate 3 mmol l Conductivity 2700 μS cm Chloride 250 mg l Sulphate 250 mg l pH value heating water 6 5 8 5 If the above mentioned minimum water quality require...

Страница 30: ...tching of escaping water wearing appropriate protective clothing CAUTION A heating system that is shut down can freeze in the event of frost and may suffer damage If there is any risk of frost drain any water from the decommissioned heating system If the heating system is not drained and there is a risk of frost the power supplies must be secured and the external main switch must remain switched o...

Страница 31: ...so refer to fig 5 5 and drain the water content of the storage tank 5 1 2 Draining the heating circuit and hot water circuit Connect the drainage hose to the combined filling and drainage valve on the Daikin Altherma EHS X H Open the combined filling and drainage valve on the Daikin Altherma EHS X H Allow the heating and hot water circuit to drain Disconnect the heating flow and return flow as wel...

Страница 32: ...arried out by persons who are authorised and who have successfully completed qualifying technical or vocational training and who have taken part in advanced training sessions recognised by the relevant responsible authorities These include in particular certified heating engineers qualified electricians and HVAC specialists who on account of their professional training and expert knowledge have ex...

Страница 33: ...nutes E E Keylock Function Release of the keylock function Off Button block cannot be activated On The button block can be activated using the rotary switch see chapter 3 3 E E Off On Off Access Rights Entering access code Setting character by character like a combination lock see chapter 3 6 1 E E 0 9 0000 1 Tab 6 1 Parameter in rotary switch setting Configuration level Setup Parameter Descriptio...

Страница 34: ...e detected the measured val ue can be corrected by the set value E E 5 0 to 5 0 kW 0 0 K 1 K T Flow Day Only if the parameter HC Function 1 is in delivery status is this function activated It can only be changed with a technician code Contact your specialist heating technician in this regard Setting the inflow target temperature for the heating circuit during the heating time when in operating mod...

Страница 35: ...he heat pump in hot water charging E E 20 95 min 50 min 1 min Tab 6 5 Parameter in rotary switch setting DHW Install Parameter Designation Access Setting range Min Max Factory setting Incre ment BE HF Standby In this operating mode all internal functions are turned off Frost protection remains active and a blocking protection for the pump is guaranteed All controllers integrated in the RoCon syste...

Страница 36: ...g Set Temp Day Parameter Designation Access Setting range Min Max Factory setting Incre ment BE HF T Reduced Target room temperature for the setback times for the permanent timer programmes Automatic 1 and Automatic 2 E E 5 40 C 15 C 0 5 C T Absence Target room temperature for the setback times for the temporary timer programmes Away and Vacation E E 5 40 C 15 C 0 5 C Tab 6 8 Parameter in rotary s...

Страница 37: ...n hh mm hh mm Off Also the cycles can be parametrised from Monday to Friday Saturday to Sunday and Monday to Sunday E E see chapter 3 4 7 see tab 3 8 15 min DHW Program 1 In this menu we can parametrise the 1st timer programme for hot water generation 3 switching cycles with a resolution of 15 minutes can be set A separate entry for each weekday is possi ble Format On hh mm hh mm Off Also the cycl...

Страница 38: ...tion S S 0 100 1 Qboh The amount of heat in the additional heat generator for hot water generation is displayed in kWh S S kWh Qchhp The amount of heat in the additional heat generator for heating mode is displayed in kWh S S kWh Qsc The quantity of heat in the heat pump for cooling is displayed in kWh S S kWh Qch The quantity of heat in the heat pump for heating is displayed in kWh S S kWh QWP Th...

Страница 39: ...hapter 3 1 E E Off On Off Access Rights Entering access code Setting character by character like a combination lock see chapter 3 6 1 E E 0 9 0000 1 Tab 6 14 Parameter in rotary switch setting Configuration level Setup Parameter Description Access Setting range Min Max Factory setting Incre ment BE HF T Outside lim day Only if the parameter Pump Mode 1 is in delivery status is this function activa...

Страница 40: ...changed with a technician code Contact your specialist heating technician in this regard Setting from which outside temperature the cooling operation with the highest cooling infeed target temperature T Flow Cooling start starts Setting condition Operating mode Cooling E E 20 45 C 24 C 1 C Max T Out Cooling Can be used only if the assigned heat generator has a cooling function Only if the paramete...

Страница 41: ...tion and maintenance carried out by authorised and trained HVAC engineers once a year ideally before the heating period This can prevent faults during the heating period Daikin recommends an inspection and maintenance contract to ensure regular inspection and maintenance The European statutory investigation period applies for heat pumps from a total system coolant filling quantity of 3 kg or as of...

Страница 42: ...peration hot water temperatures 60 C arise Touching components during or after operation leads to a risk of burns Water discharged during maintenance and servic ing work can cause scalding on contact with the skin Before carrying out servicing and maintenance work allow the Daikin Altherma EHS X H to cool down sufficiently Wear protective gloves WARNING Live parts can cause an electric shock on co...

Страница 43: ... 2 Connect the filling hose fig 7 3 item 1 with back flush prevention 1 2 and an external pressure gauge on site to the KFE cock fig 7 3 item 2 and secure from slipping using a hose clamp 3 Open the water cock fig 7 3 item 4 in the supply line 4 Open KFE cock fig 7 3 item 2 and watch the pressure gauge 5 Fill the system with water until the system target pressure is reached on the pressure gauge S...

Страница 44: ... the external pressure gauge again Where necessary refill with water via the KFE cock fig 7 3 item 2 13 Close the water cock fig 7 3 item 4 in the supply line 14 Disconnect the filler hose fig 7 3 item 1 with flow back preventer from the KFE cock fig 7 3 item 2 Air Purge Can only be performed by an expert heating technician 1 Filler hose 2 KFE cock 3 Ball cock 4 Water cock 5 1 Valve drive 5 2 Unlo...

Страница 45: ...r possible causes are listed Tips to correct the faults are also provided Information messages which are displayed without red back lighting normally result in no permanent limitations on the op eration of the Daikin Altherma EHS X H Messages that are displayed with an error code E and red back lighting required error correction by an authorised and trained expert heating technician For informatio...

Страница 46: ...rol unit o do so disconnect the system from the power supply for at least 10 s and then switch on again Operating data are not updated Operating system of control unit crashed Carry out RESET of control unit To do so disconnect the system from the power supply for at least 10 s and then switch on again Have the heating system checked by a Daikin heating technician Heating does not warm up Heating ...

Страница 47: ...e primary pressure in the expansion container and the water pressure if necessary refill the heating water and reset the primary pressure see chapter 7 5 Hot water supply is taking too much of the out put of the heat pump Have the heating system checked by a Daikin heating technician Hot water does not warm up DIP switch configured incorrectly Have the heating system checked by a Daikin heating te...

Страница 48: ...etely open Fully vent the heating system and device internal circulation pump On the control unit rotary switch position Info check that there is sufficient water pressure 0 5 bar if necessary refill the heating water Have the heating system checked by a Daikin heating technician Water quantity in the heating system too low Check the primary pressure in the expansion container and the water pressu...

Страница 49: ...tank is defective Have the expansion tank checked by a Daikin specialist heating technician Water pressure in the heating system is too high On the control unit rotary switch position Info check that the water pressure lies beneath the stated maximum pressure If necessary bleed the water until the pressure lies in central permissible range Safety pressure relief valve is stuck Have the heating sys...

Страница 50: ...t water circuit e g filling the hot water storage tank Flow pipe Part of the hydraulic circuit that directs the heated water from heat generator to the heating surfaces Heat exchanger A part that transfers thermal energy from one circuit to another Both circuits are separated from each other hydraulically by a wall in the heat exchanger Heat pumping process In a closed coolant circuit the coolant ...

Страница 51: ... heating cooling economy and hot water cycles Water shortage overheating protection Safety device which switches off the heat generator automatically if there is a water shortage in order to avoid over heating Weather controlled flow tem perature regulation The inflow target temperature for temperature control in the heating unit is calculated from the measured value for the external temperature a...

Страница 52: ...C T Room 3 Setpoint ____ C Time period On Off On Off On Off HC Program 1 Monday Tuesday Wednesday Thursday Friday Saturday Sunday HC Program 2 Monday Tuesday Wednesday Thursday Friday Saturday Sunday Tab 10 1 Individual settings in the heating timer programmes Switching cycle 1 Switching cycle 2 Switching cycle 3 Temperature setting T DHW Setpoint 1 ____ C T DHW Setpoint 2 ____ C T DHW Setpoint 3 ...

Страница 53: ...dresses in the RoCon system Switching cycle 1 Switching cycle 2 Switching cycle 3 Time period On Off On Off On Off Circulation Time Monday Tuesday Wednesday Thursday Friday Saturday Sunday Tab 10 3 Individual settings of the circulation switching time programme Rotary switch setting Parameter levels Parameter Old value New value Date Comments Tab 10 4 Individual parameter modifications RoCon appli...

Страница 54: ...Operating instructions 54 Daikin Altherma EHS X H Daikin Altherma integrated solar unit 008 1420944 05 2014 10 x Notes 10 3 Other items ...

Страница 55: ...ortant information 4 I Inflow target temperature 18 in cooling mode 25 in heating mode 24 with weather dependent regulation 26 Information messages 38 Initial commissioning 29 K KFE filling connection 30 43 L Language setting 21 Low tariff mains connection 50 M Maintenance 41 Malfunctions 45 Manual operation 23 Mixer module 26 N Normal operation 22 O Off peak mains connection Functional descriptio...

Страница 56: ...008 1420944_08 05 2014 Copyright Daikin ...

Отзывы: