Operating instructions
38
Daikin Altherma EHS(X/H)
Daikin Altherma integrated solar unit
008.1420944 – 05/2014
6
x
Parameter settings
6.10 Rotary switch setting: Info
6.11 Exit button: Sonderfunktion
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
Overview
Display of different current operating data (see section 3.4.1).
S
S
-
-
-
Water Pressure
The current water pressure is displayed in bar.
S
S
0 - 4 bar
-
0.1 bar
T-HS
The current temperature (TVBH) of the heat generator is displayed in °C.
S
S
0 - 100 °C
-
1 °C
T-HS Setpoint
The current Inflow target temperature of the heat generator is displayed in °C (see
section 3.6.4).
S
S
0 - 90 °C
-
0.1 °C
T-Outside
The current external temperature is displayed °C.
S
S
-39 to +50°C
0.1 °C
T-DHW
The current temperature of the hot water storage tank is displayed in °C. If there is no hot water
function activated, "- - -" is displayed.
S
S
0 - 100 °C
-
0.1 °C
T-DHW Setpoint
The current target hot water temperature is displayed °C. If there is no hot water function acti-
vated, "- - -" is displayed. The current set value is here always the maximum value of all rele-
vant demands for this hot water circuit.
S
S
10 - 70°C
-
0.1 °C
T-Return
The current return flow temperature of the heat generator is displayed in °C. If there is no rel-
evant sensor connected to the heat generator, "- - -" is displayed.
S
S
0 - 100 °C
-
0.1 °C
Flow Rate
The filtered value of the current volume flow in litres per hour is displayed.
S
S
0 - 5100 l/h
-
l/h
T-HC
The inflow temperature in the direct heating circuit is displayed in °C.
S
S
0 - 100 °C
-
0.1 °C
T-HC Setpoint
The set temperature of the flow in the direct heating circuit is displayed in °C.
S
S
0 - 90 °C
-
0.1 °C
Status HS pump
The current status of the internal heat circulation pump in the Daikin Altherma EHS(X/H) is dis-
played.
S
S
Off
On
-
-
Runtime Compres-
sor
The running time of the refrigerant compressor is displayed in h.
S
S
-
-
h
Runtime Pump
The running time of the internal heating circulation pump is displayed in h.
S
S
-
-
h
Mixer Position
The current position of the 3UV DHW 3-way switch valve is displayed.
0%: Position A (room heating)
100%: Position B (domestic hot water generation)
S
S
0 - 100 %
-
1 %
Qboh
The amount of heat in the additional heat generator for hot water generation is displayed in
kWh.
S
S
-
-
kWh
Qchhp
The amount of heat in the additional heat generator for heating mode is displayed in kWh.
S
S
-
-
kWh
Qsc
The quantity of heat in the heat pump for cooling is displayed in kWh.
S
S
-
-
kWh
Qch
The quantity of heat in the heat pump for heating is displayed in kWh.
S
S
-
-
kWh
QWP
The total amount of heat in the heat pump is displayed in kWh.
S
S
-
-
kWh
Qdhw
The quantity of heat for hot water generation is displayed in kWh.
S
S
-
-
kWh
HS type
The heat generator type Daikin Altherma EHS(X/H) detected is displayed.
S
S
-
-
-
Sw Nr B1/U1
The software and version of the RoCon B1 operating unit is displayed.
S
S
-
-
-
Sw Nr Controller
The software number and the version of the RoCon BM1 circuit board are displayed.
S
S
-
-
-
Sw Nr RTX RT
The software number and the version of the RTX-AL4 circuit board are displayed.
S
S
-
-
-
Tab. 6-12 Parameter in rotary switch setting "Info"
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
Manual Operation
The direct heating circuit and the target hot water temperature are controlled according to the
temperature set in this parameter (see section 3.5.1).
E
E
20 - 80 °C
50 °C
1 °C
FA failure
Display of a current heat pump malfunction in the Daikin Altherma EHS(X/H).
If "----" is displayed there is no fault (see chapter 8).
E
E
-
-
-
Protocol
Display of protocol (error and information messages). Here we display the saved messages of
the Daikin Altherma EHS(X/H) and the connected data bus units with date a code, in each case
as a menu item. By selecting an entry with the rotary switch, all other corresponding information
is displayed concerning the selected fault message:
- Date and time of the message
- Code number (Information for the heating technician)
- Location (device) where the message originated
- Bus identification (device) where the message originated
E
E
-
-
-
Delete message
By setting this parameter to "On" and briefly pressing the rotary switch all the entries of the pro-
tocol, including the faults from connected data bus devices, are deleted.
E
E
Off
On
Off
-
Timeprog Reset
Resets all permanent time programmes to factory setting (see tab. 3-8).
E
E
Off
On
Off
-
Return
This parameter is used only to exit the special level.
E
E
Tab. 6-13 Parameter in the level "Sonderfunktion"