3 Preparation

Installation manual

6

EHBH/X04+08DA*V7

Daikin Altherma 3 R W

4P618951-1 – 2020.03

3.2

Preparing water piping

NOTICE

In  case  of  plastic  pipes,  make  sure  they  are  fully  oxygen
diffusion  tight  according  to  DIN  4726.  The  diffusion  of
oxygen into the piping can lead to excessive corrosion.

Valve  towards  expansion  vessel.

  The  valve  towards  the

expansion vessel (if equipped) MUST be open.

3.2.1

To check the water volume and flow rate

Minimum water volume

Check  that  the  total  water  volume  in  the  installation  is  minimum
10 litres, the internal water volume of the indoor unit NOT included.

NOTICE

When  circulation  in  each  space  heating/cooling  loop  is
controlled by remotely controlled valves, it is important that
the minimum water volume is guaranteed, even if all of the
valves are closed.

Minimum flow rate

Check that the minimum flow rate in the installation is guaranteed in
all  conditions.  This  minimum  flow  rate  is  required  during  defrost/
backup  heater  operation.  For  this  purpose,  use  the  overpressure
bypass valve delivered with the unit, and respect the minimum water
volume.

NOTICE

When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating or operation).

See the installer reference guide for more information.

Minimum required flow rate

12 l/min

See  the  recommended  procedure  as  described  in 

"6.2  Checklist

during commissioning" 

[

4

 22].

3.3

Preparing electrical wiring

3.3.1

Overview of electrical connections for
external and internal actuators

Item

Description

Wires

Maximum

running

current

Outdoor unit and indoor unit power supply

1

Power supply for
outdoor unit

2+GND

(a)

2

Power supply and
interconnection cable to
indoor unit

3

(g)

3

Power supply for
backup heater

See table below. —

4

Preferential kWh rate
power supply (voltage
free contact)

2

(e)

5

Normal kWh rate power
supply

2

6.3 A

Optional equipment

6

3‑way valve

3

100 mA

(b)

Item

Description

Wires

Maximum

running

current

7

Power supply for
booster heater and
thermal protection
(from indoor unit)

4+GND

(c)

8

Power supply for
booster heater (to
indoor unit)

2+GND

13 A

9

Domestic hot water
tank thermistor

2

(d)

10

User interface used as
room thermostat

2

(f)

11

Room thermostat

3 or 4

100 mA

(b)

12

Outdoor ambient
temperature sensor

2

(b)

13

Indoor ambient
temperature sensor

2

(b)

14

Heat pump convector

2

100 mA

(b)

Field supplied components

15

Shut-off valve

2

100 mA

(b)

16

Electricity meter

2 (per meter)

(b)

17

Domestic hot water
pump

2

(b)

18

Alarm output

2

(b)

19

Changeover to external
heat source control

2

(b)

20

Space cool/heat
operation control

2

(b)

21

Power consumption
digital inputs

2 (per input
signal)

(b)

22

Safety thermostat

2

(e)

(a)

Refer to name plate on outdoor unit.

(b)

Minimum cable section 0.75 mm².

(c)

Cable section 2.5 mm².

(d)

The thermistor and connection wire (12 m) are delivered
with the domestic hot water tank.

(e)

Cable section 0.75 mm² till 1.25 mm²; maximum length:
50 m. Voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.

(f)

Cable section 0.75 mm² till 1.25 mm²; maximum length:
500 m. Applicable for both single user interface and dual
user interface connection.

(g)

Cable section 1.5 mm².

NOTICE

More  technical  specifications  of  the  different  connections
are indicated on the inside of the indoor unit.

Backup heater

type

Power supply

Required number of

conductors

*6V

1N~ 230 V (6V)

2+GND

3~ 230 V (6T1)

3+GND

*9W

3N~ 400 V

4+GND

Содержание EHBH08DA6V7

Страница 1: ...Installation manual Daikin Altherma 3 R W English Installation manual Daikin Altherma 3 R W EHBH04DA6V7 EHBH08DA6V7 EHBH08DA9W7 EHBX04DA6V7 EHBX08DA6V7 EHBX08DA9W7...

Страница 2: ...u s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uput...

Страница 3: ...izard Main zone 17 5 2 6 Configuration wizard Additional zone 17 5 2 7 Detailed screen with weather dependent curve 18 5 2 8 Configuration wizard Tank 19 5 3 Settings menu 20 5 3 1 Main zone 20 5 3 2...

Страница 4: ...es Space heating operation 5 30 C Space cooling operation 5 35 C Domestic hot water production 5 35 C Mind the following spacing installation guidelines H 1150 200 200 500 mm 450 H Height measured fro...

Страница 5: ...ate the minimum opening area for natural ventilation between room A and room B VAmin cm2 Unit can be installed at room A if 2 ventilation openings permanently open are provided between room A and B 1...

Страница 6: ...ernal actuators Item Description Wires Maximum running current Outdoor unit and indoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit...

Страница 7: ...witch box cover 4 3 If you have to do work behind the switch box open the switch box 2 1 2 4 If you have to do work behind the user interface panel or upload new software into the user interface open...

Страница 8: ...2 2 To connect the drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable...

Страница 9: ...of maximum 10 bar 1 MPa must be installed on the domestic cold water inlet connection in accordance with the applicable legislation 4 4 2 To fill the water circuit To fill the water circuit use a fiel...

Страница 10: ...3 6 a Interconnection cable main power supply b Normal kWh rate power supply c Preferential power supply contact 2 Fix the cables with cable ties to the cable tie mountings INFORMATION In case of pre...

Страница 11: ...ace point between the user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessa...

Страница 12: ...case of an electricity meter with transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Connect the electricity me...

Страница 13: ...stat normally closed cable to the appropriate terminals as shown in the illustration below X5M 9 10 2 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install th...

Страница 14: ...You can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not appl...

Страница 15: ...t in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 2 3V 3 6V 4 9W Domestic hot water The following setting determines if the system can prepare domestic ho...

Страница 16: ...thermostatic valve to avoid too high temperatures towards a low temperature emitter Make sure you set the emitter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance w...

Страница 17: ...Enable leaving water temperature modulation and increase the maximum modulation 2 C Control Define how the operation of the unit is controlled Control In this control Leaving water Unit operation is d...

Страница 18: ...ecrease the temperature of the leaving water for different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so...

Страница 19: ...Domestic hot water tank 5 2 8 Configuration wizard Tank This part only applies to systems with an optional domestic hot water tank installed Heat up mode The domestic hot water can be prepared in 3 di...

Страница 20: ...ou can set additional settings using the main menu screen and its submenus The most important settings are presented here 5 3 1 Main zone Thermostat type Only applicable in external room thermostat co...

Страница 21: ...ilibrium temperature Operation 9 4 Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running...

Страница 22: ...age on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the ind...

Страница 23: ...test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In...

Страница 24: ...ult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 7 Hand over to the user On...

Страница 25: ...ing water IN a2 Space heating water OUT b1 Gas refrigerant IN heating mode condenser b2 Liquid refrigerant OUT heating mode condenser c1 Liquid refrigerant IN cooling mode evaporator c2 Gas refrigeran...

Страница 26: ...wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translati...

Страница 27: ...witch box 5 Ext thermistor 5 External thermistor SWB Switch box English Translation 6 Field supplied options 6 Field supplied options 12 V DC pulse detection voltage supplied by PCB 12 V DC pulse dete...

Страница 28: ...mostat A13P P1 P2 LAN adapter A14P P1 P2 user interface Optional parts Optional parts External room thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H onl...

Страница 29: ...H 1150 200 200 500 mm 450 8 4 Table 2 Minimum floor area indoor unit mc kg Minimum floor area m H 1150 mm H 1200 mm H 1300 mm H 1400 mm H 1500 mm H 1600 mm H 1700 mm H 1800 mm 1 84 8 57 7 84 6 64 5 92...

Страница 30: ...when H is between two H values from the table consider the value that corresponds to the lower H value from the table If H 1450 mm consider the floor area that corresponds to H 1400 mm For intermediat...

Страница 31: ......

Страница 32: ...4P618951 1 2020 03 Copyright 2020 Daikin 4P618951 1 0000000S Verantwortung f r Energie und Umwelt...

Отзывы: