8 Technical data

Installation manual

26

EHBH/X04+08DA*V7

Daikin Altherma 3 R W

4P618951-1 – 2020.03

8.2

Wiring diagram: Indoor unit

See  the  internal  wiring  diagram  supplied  with  the  unit  (on  the  inside  of  the  indoor  unit  upper  front  panel).  The  abbreviations  used  are  listed
below.

Notes to go through before starting the unit

English

Translation

Notes to go through before
starting the unit

Notes to go through before
starting the unit

X1M

Main terminal

X2M

Field wiring terminal for AC

X5M

Field wiring terminal for DC

X6M

Backup heater power supply
terminal

X7M, X8M

Booster heater power supply
terminal

Earth wiring

Field supply

1

Several wiring possibilities

Option

Not mounted in switch box

Wiring depending on model

PCB

Note 1: Connection point of the
power supply for the BUH/BSH
should be foreseen outside the
unit.

Note 1: Connection point of the
power supply for the backup
heater/booster heater should be
foreseen outside the unit.

Backup heater power supply

Backup heater power supply

 1N~, 230 V

 1N~, 230 V

 3~, 230 V

 3~, 230 V

 3N~, 400 V

 3N~, 400 V

User installed options

User installed options

 LAN adapter

 LAN adapter

 Domestic hot water tank

 Domestic hot water tank

 Remote user interface

 User interface used as room

thermostat

 Ext. indoor thermistor

 External indoor thermistor

 Ext outdoor thermistor

 External outdoor thermistor

 Digital I/O PCB

 Digital I/O PCB

 Demand PCB

 Demand PCB

Main LWT

Main leaving water temperature

 On/OFF thermostat (wired)

 On/OFF thermostat (wired)

 On/OFF thermostat (wireless)

 On/OFF thermostat (wireless)

 Ext. thermistor

 External thermistor

 Heat pump convector

 Heat pump convector

Add LWT

Additional leaving water
temperature

 On/OFF thermostat (wired)

 On/OFF thermostat (wired)

 On/OFF thermostat (wireless)

 On/OFF thermostat (wireless)

 Ext. thermistor

 External thermistor

 Heat pump convector

 Heat pump convector

Position in switch box

English

Translation

Position in switch box

Position in switch box

Legend

A1P

Main PCB

A2P

* On/OFF thermostat (PC=power circuit)

A3P

* Heat pump convector

A4P

* Digital I/O PCB

A8P

* Demand PCB

A9P

Status indicator

A10P

MMI (= user interface connected to the
indoor unit) – Power supply unit PCB

A11P

MMI (= user interface connected to the
indoor unit) – Main PCB

A12P

MMI display PCB

A13P

* LAN adapter

A14P

* User interface used as room thermostat –

PCB

A15P

* Receiver PCB (wireless On/OFF thermostat)

B1L

Flow sensor

B1PR

Refrigerant pressure sensor

B1PW

Water pressure sensor

BSK (A3P)

Solar pump station relay

CN* (A4P)

* Connector

DS1(A8P)

* DIP switch

E1H

Backup heater element (1 kW)

E2H

Backup heater element (2 kW)

E3H

Backup heater element (3 kW)

E4H

* Booster heater (3 kW)

E*P (A9P)

Indication LED

F1B

# Overcurrent fuse backup heater

F2B

# Overcurrent fuse booster heater

F1T

Thermal fuse backup heater

F1U, F2U (A4P)

* Fuse 5 A 250 V for digital I/O PCB

FU1 (A1P)

Fuse T 5 A 250 V for PCB

FU2 (A10P)

Fuse T 1.6 A 250 V for PCB

K1M, K2M

Contactor backup heater

K3M

* Contactor booster heater

K5M

Safety contactor backup heater

K*R (A1P-A4P)

Relay on PCB

M1P

Main supply pump

M2P

# Domestic hot water pump

M2S

# 2-way valve for cooling mode

M3S

* 3-way valve for floor heating/domestic hot

water

P1M

MMI display

PC (A15P)

* Power circuit

PHC1 (A4P)

* Optocoupler input circuit

Q1L

Thermal protector backup heater

Q2L

* Thermal protector booster heater

Q4L

# Safety thermostat

Q*DI

# Earth leakage circuit breaker

R1H (A2P)

* Humidity sensor

R1T (A1P )

Outlet water heat exchanger thermistor

R1T (A2P)

* Ambient sensor On/OFF thermostat

R1T (A14P)

* Ambient sensor user interface

R2T (A1P)

Outlet backup heater thermistor

R2T (A2P)

* External sensor (floor or ambient)

Содержание EHBH08DA6V7

Страница 1: ...Installation manual Daikin Altherma 3 R W English Installation manual Daikin Altherma 3 R W EHBH04DA6V7 EHBH08DA6V7 EHBH08DA9W7 EHBX04DA6V7 EHBX08DA6V7 EHBX08DA9W7...

Страница 2: ...u s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uput...

Страница 3: ...izard Main zone 17 5 2 6 Configuration wizard Additional zone 17 5 2 7 Detailed screen with weather dependent curve 18 5 2 8 Configuration wizard Tank 19 5 3 Settings menu 20 5 3 1 Main zone 20 5 3 2...

Страница 4: ...es Space heating operation 5 30 C Space cooling operation 5 35 C Domestic hot water production 5 35 C Mind the following spacing installation guidelines H 1150 200 200 500 mm 450 H Height measured fro...

Страница 5: ...ate the minimum opening area for natural ventilation between room A and room B VAmin cm2 Unit can be installed at room A if 2 ventilation openings permanently open are provided between room A and B 1...

Страница 6: ...ernal actuators Item Description Wires Maximum running current Outdoor unit and indoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit...

Страница 7: ...witch box cover 4 3 If you have to do work behind the switch box open the switch box 2 1 2 4 If you have to do work behind the user interface panel or upload new software into the user interface open...

Страница 8: ...2 2 To connect the drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable...

Страница 9: ...of maximum 10 bar 1 MPa must be installed on the domestic cold water inlet connection in accordance with the applicable legislation 4 4 2 To fill the water circuit To fill the water circuit use a fiel...

Страница 10: ...3 6 a Interconnection cable main power supply b Normal kWh rate power supply c Preferential power supply contact 2 Fix the cables with cable ties to the cable tie mountings INFORMATION In case of pre...

Страница 11: ...ace point between the user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessa...

Страница 12: ...case of an electricity meter with transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Connect the electricity me...

Страница 13: ...stat normally closed cable to the appropriate terminals as shown in the illustration below X5M 9 10 2 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install th...

Страница 14: ...You can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not appl...

Страница 15: ...t in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 2 3V 3 6V 4 9W Domestic hot water The following setting determines if the system can prepare domestic ho...

Страница 16: ...thermostatic valve to avoid too high temperatures towards a low temperature emitter Make sure you set the emitter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance w...

Страница 17: ...Enable leaving water temperature modulation and increase the maximum modulation 2 C Control Define how the operation of the unit is controlled Control In this control Leaving water Unit operation is d...

Страница 18: ...ecrease the temperature of the leaving water for different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so...

Страница 19: ...Domestic hot water tank 5 2 8 Configuration wizard Tank This part only applies to systems with an optional domestic hot water tank installed Heat up mode The domestic hot water can be prepared in 3 di...

Страница 20: ...ou can set additional settings using the main menu screen and its submenus The most important settings are presented here 5 3 1 Main zone Thermostat type Only applicable in external room thermostat co...

Страница 21: ...ilibrium temperature Operation 9 4 Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running...

Страница 22: ...age on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the ind...

Страница 23: ...test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In...

Страница 24: ...ult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 7 Hand over to the user On...

Страница 25: ...ing water IN a2 Space heating water OUT b1 Gas refrigerant IN heating mode condenser b2 Liquid refrigerant OUT heating mode condenser c1 Liquid refrigerant IN cooling mode evaporator c2 Gas refrigeran...

Страница 26: ...wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translati...

Страница 27: ...witch box 5 Ext thermistor 5 External thermistor SWB Switch box English Translation 6 Field supplied options 6 Field supplied options 12 V DC pulse detection voltage supplied by PCB 12 V DC pulse dete...

Страница 28: ...mostat A13P P1 P2 LAN adapter A14P P1 P2 user interface Optional parts Optional parts External room thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H onl...

Страница 29: ...H 1150 200 200 500 mm 450 8 4 Table 2 Minimum floor area indoor unit mc kg Minimum floor area m H 1150 mm H 1200 mm H 1300 mm H 1400 mm H 1500 mm H 1600 mm H 1700 mm H 1800 mm 1 84 8 57 7 84 6 64 5 92...

Страница 30: ...when H is between two H values from the table consider the value that corresponds to the lower H value from the table If H 1450 mm consider the floor area that corresponds to H 1400 mm For intermediat...

Страница 31: ......

Страница 32: ...4P618951 1 2020 03 Copyright 2020 Daikin 4P618951 1 0000000S Verantwortung f r Energie und Umwelt...

Отзывы: