4 Installation

Installation manual

10

EHBH/X04+08DA*V7

Daikin Altherma 3 R W

4P618951-1 – 2020.03

Routing

Possible cables (depending on unit type
and installed options)

a

Low voltage

▪ Preferential power supply contact

▪ User  interface  used  as  room  thermostat

(option)

▪ Power  consumption  digital  inputs  (field

supply)

▪ Outdoor  ambient  temperature  sensor

(option)

▪ Indoor 

ambient 

temperature 

sensor

(option)

▪ Electrical meters (field supply)

▪ Safety thermostat (field supply)

b

High voltage power
supply

▪ Interconnection cable

▪ Normal kWh rate power supply

▪ Preferential kWh rate power supply

c

High voltage control
signal

▪ Heat pump convector (option)

▪ Room thermostat (option)

▪ Shut-off valve (field supply)

▪ Domestic hot water pump (field supply)

▪ Alarm output

▪ Changeover  to  external  heat  source

control

▪ Space cool/heat operation control

d

High voltage power
supply (factory-
mounted cable)

▪ Power supply for backup heater

CAUTION

Do NOT push or place redundant cable length in the unit.

4.5.3

To connect the main power supply

1

Connect the main power supply.

In case of normal kWh rate power supply

X2M

X1M

1 2 3

1 2 3
1 2 3

1 2 3

X1A

X11YB

X11YA X11Y

1 2 3

a

a

Interconnection cable (=main power supply)

In case of preferential kWh rate power supply

Connect X11Y to X11YB.

X5M

X2M

X1M

1 2 3

1 2

N L

N L

3

S1S

a

b

c

X11YA

X1A

X11YB X11Y

910

5

1 2 3

6

a

Interconnection cable (=main power supply)

b

Normal kWh rate power supply

c

Preferential power supply contact

2

Fix the cables with cable ties to the cable tie mountings.

INFORMATION

In  case  of  preferential  kWh  rate  power  supply,  connect
X11Y  to  X11YB.  The  necessity  of  separate  normal  kWh
rate  power  supply  to  indoor  unit  (b)  X2M/5+6  depends  on
the type of preferential kWh rate power supply.

Separate connection to the indoor unit is required:

▪ if  preferential  kWh  rate  power  supply  is  interrupted

when active, OR

▪ if no power consumption of the indoor unit is allowed at

the preferential kWh rate power supply when active.

INFORMATION

The  preferential  kWh  rate  power  supply  contact  is
connected to the same terminals (X5M/9+10) as the safety
thermostat.  Thus,  the  system  can  have  EITHER
preferential  kWh  rate  power  supply  OR  a  safety
thermostat.

4.5.4

To connect the backup heater power
supply

CAUTION

If the indoor unit has a tank with a built‑in electrical booster
heater, use a dedicated power circuit for the backup heater
and booster heater. NEVER use a power circuit shared by
another  appliance.  This  power  circuit  must  be  protected
with the required safety devices according to the applicable
legislation.

CAUTION

To  guarantee  the  unit  is  completely  earthed,  always
connect  the  backup  heater  power  supply  and  the  earth
cable.

The backup heater capacity can vary, depending on the indoor unit
model.  Make  sure  that  the  power  supply  is  in  accordance  with  the
backup heater capacity, as listed in the table below.

Содержание EHBH08DA6V7

Страница 1: ...Installation manual Daikin Altherma 3 R W English Installation manual Daikin Altherma 3 R W EHBH04DA6V7 EHBH08DA6V7 EHBH08DA9W7 EHBX04DA6V7 EHBX08DA6V7 EHBX08DA9W7...

Страница 2: ...u s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uput...

Страница 3: ...izard Main zone 17 5 2 6 Configuration wizard Additional zone 17 5 2 7 Detailed screen with weather dependent curve 18 5 2 8 Configuration wizard Tank 19 5 3 Settings menu 20 5 3 1 Main zone 20 5 3 2...

Страница 4: ...es Space heating operation 5 30 C Space cooling operation 5 35 C Domestic hot water production 5 35 C Mind the following spacing installation guidelines H 1150 200 200 500 mm 450 H Height measured fro...

Страница 5: ...ate the minimum opening area for natural ventilation between room A and room B VAmin cm2 Unit can be installed at room A if 2 ventilation openings permanently open are provided between room A and B 1...

Страница 6: ...ernal actuators Item Description Wires Maximum running current Outdoor unit and indoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit...

Страница 7: ...witch box cover 4 3 If you have to do work behind the switch box open the switch box 2 1 2 4 If you have to do work behind the user interface panel or upload new software into the user interface open...

Страница 8: ...2 2 To connect the drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable...

Страница 9: ...of maximum 10 bar 1 MPa must be installed on the domestic cold water inlet connection in accordance with the applicable legislation 4 4 2 To fill the water circuit To fill the water circuit use a fiel...

Страница 10: ...3 6 a Interconnection cable main power supply b Normal kWh rate power supply c Preferential power supply contact 2 Fix the cables with cable ties to the cable tie mountings INFORMATION In case of pre...

Страница 11: ...ace point between the user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessa...

Страница 12: ...case of an electricity meter with transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Connect the electricity me...

Страница 13: ...stat normally closed cable to the appropriate terminals as shown in the illustration below X5M 9 10 2 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install th...

Страница 14: ...You can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not appl...

Страница 15: ...t in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 2 3V 3 6V 4 9W Domestic hot water The following setting determines if the system can prepare domestic ho...

Страница 16: ...thermostatic valve to avoid too high temperatures towards a low temperature emitter Make sure you set the emitter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance w...

Страница 17: ...Enable leaving water temperature modulation and increase the maximum modulation 2 C Control Define how the operation of the unit is controlled Control In this control Leaving water Unit operation is d...

Страница 18: ...ecrease the temperature of the leaving water for different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so...

Страница 19: ...Domestic hot water tank 5 2 8 Configuration wizard Tank This part only applies to systems with an optional domestic hot water tank installed Heat up mode The domestic hot water can be prepared in 3 di...

Страница 20: ...ou can set additional settings using the main menu screen and its submenus The most important settings are presented here 5 3 1 Main zone Thermostat type Only applicable in external room thermostat co...

Страница 21: ...ilibrium temperature Operation 9 4 Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running...

Страница 22: ...age on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the ind...

Страница 23: ...test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In...

Страница 24: ...ult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 7 Hand over to the user On...

Страница 25: ...ing water IN a2 Space heating water OUT b1 Gas refrigerant IN heating mode condenser b2 Liquid refrigerant OUT heating mode condenser c1 Liquid refrigerant IN cooling mode evaporator c2 Gas refrigeran...

Страница 26: ...wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translati...

Страница 27: ...witch box 5 Ext thermistor 5 External thermistor SWB Switch box English Translation 6 Field supplied options 6 Field supplied options 12 V DC pulse detection voltage supplied by PCB 12 V DC pulse dete...

Страница 28: ...mostat A13P P1 P2 LAN adapter A14P P1 P2 user interface Optional parts Optional parts External room thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H onl...

Страница 29: ...H 1150 200 200 500 mm 450 8 4 Table 2 Minimum floor area indoor unit mc kg Minimum floor area m H 1150 mm H 1200 mm H 1300 mm H 1400 mm H 1500 mm H 1600 mm H 1700 mm H 1800 mm 1 84 8 57 7 84 6 64 5 92...

Страница 30: ...when H is between two H values from the table consider the value that corresponds to the lower H value from the table If H 1450 mm consider the floor area that corresponds to H 1400 mm For intermediat...

Страница 31: ......