Communication is achieved by taking the difference between
a positive dc signal and a negative dc signal. The positive dc
signal is termed “data 1” or “1’. Data 1 is positive with respect
to ground (or common). The negative dc signal is termed
“data 2” or “2”. Data 2 is negative with respect to ground (or
common).
Data 1 should be approximately 2.8 volts dc. Data 2 should
be approximately 2.2 volts dc. The voltage difference between
data 1 and data 2 should be approximately 0.6 volts dc.
Verify that the bus DS1 dip switches are in the ON position.
OFF ON
1
TERM
2
The ComfortNet™ system is a fully communicating system,
constituting a network. Occasionally the need to troubleshoot
the network may arise. The integrated control module has
some onboard tools that can be used to troubleshoot the
network. These tools are: red communications LED, green
receive (Rx) LED, and the learn button.
•
Red communications LED – Indicates the status of the
network. The table below indicates the LED status and
the corresponding potential problem.
• Green receive LED – Indicates network traffic. The table
below indicates the LED status and the corresponding
potential problem.
•
LEARN button – Used to reset the network. Depress the
button for approximately 5 seconds to reset the network.
dipswitch default factory Settings
Switch #
Setting
Purpose
od dS1
1
ON
CT Communication Enabled
2
ON
CT Communication Enabled
od dS2
1
OFF
Cooling Emergency Mode for
Future Use*
2
OFF
Cooling Emergency Mode for
Future Use*
*OD DS2 switch 1 and 2 both must be turned off during normal
operation mode
LED COLOR
LED Status
Indication
Probable Causes
Corrective Actions
Red Communications LED
(H1P)
Off
Nominal condition
•
None
•
None
1 Flash
Communications Failure
•
Unknown packet is received
•
Depress learn button
2 Flash
Out-of-box reset
•
Control power up
•
Learn button depressed
•
None
Green Receive LED (H2P)
Off
No power
Communications error
•
No power to Outdoor unit
•
Open fuse
•
Communication error
•
Check circuit breakers and fuses; Replace if needed
•
Reset network by depressing learn button
•
Check communication wires (data 1/ data 2 wires);
Replace if needed
1 Steady Flash
No network found
•
Broken/ disconnected communication
wire(s)
•
AC is installed as a legacy/ traditional
system
•
Check communication wires (data 1/ data 2 wires);
Replace if needed
•
Check installation type (legacy/ traditional or com-
municating)
•
Check data 1/ data 2 voltages
Rapid Flashing
Nominal network traffic
• Control is “talking” on network as expected
•
None
On Solid
Data 1/Data 2 miss-wire
•
Data 1 and data 2 wires reversed at indoor
unit, thermostat, or outdoor unit
•
Short between data 1 and data 2 wires
•
Short between data 1 or data 2 wires
•
Check communication wires (data 1/ data 2 wires);
Replace if needed
•
Check data 1/ data 2 voltages