60
Installation Settings
Fan Off Delay
(0s)
Runs the fan for a short time after Cooling or electric strip heat
turns off to increase system efficiency. (0 - 120 Secs.)
(Continued)
The installer or service
technician can use this
feature to test the
functions without any
time delays of the
thermostat.
Test Outputs
With a 1st stage cooling call, Y1 and G are active
Sensor Settings
Control Sensor
(thermostat )
When a remote sensor is connected to the thermostat, the user
may choose which sensor source is used to measure room temperature.
Wired Sensor Use
(remote)
The wired sensor may be used as follows:
The integral humidity sensor may be calibrated -20% to +20% RH
Calibrate Sensors
(0
˚
)
The thermostat and wired sensor may be calibrated -7 to +7 degrees F.
•
Thermostat sensor only
•
Remote Sensor only
•
Average remote/thermostat
•
Outdoor sensor
•
Remote Sensor
•
Supply Sensor
•
Return Sensor
Main Menu Buttons -
Settings