SERVICING
61
Service Problem
No Heat
Unsatisfactory Heat
POSSIBLE CAUSE
DOTS IN ANALYSIS
GUIDE INDICATE
"POSSIBLE CAUSE"
SYM
P
T
O
M
S
y
s
tem
Wi
ll
N
o
t St
ar
t
Bu
rn
er
W
o
n
't Ig
n
it
e
B
u
rn
er
I
g
n
it
e
s-
L
o
cks Ou
t
Bu
rn
er
Shu
ts
O
ff
p
ri
o
r t
o
T'
S
tat
bei
ng S
a
ti
s
fi
e
d
Sh
or
t C
y
c
les
Lo
ng C
y
c
les
S
oot
and
/
o
r Fu
m
e
s
To
o
M
u
c
h
H
e
a
t
N
o
t En
oug
h H
e
at
Test Method
Remedy
S
ee S
erv
ice
P
roced
ur
e Refe
re
nce
Power Failure
•
Test Voltage
S-1
Blown Fuse
•
Test Voltage
S-4
Loose Connection
•
Check Wiring
S-2
Shorted or Broken Wires
•
Check Wiring
S-3A
No Low Voltage
•
Check Transformer
S-4
Faulty Thermostat
•
• •
• •
Check Thermostat
S-3A
Faulty Transformer
•
Check Transformer
S-4
Poor or High Resistance Ground
•
Measure Ground Resistance
S-17B
Improper Heat Anticipator Setting
• •
• •
Adjust Heat Anticipator Setting
S-3B
Improper Thermostat Location
• •
• •
Relocate Thermostat
S-316
Faulty Limit or Roll Out Switch
•
•
Test Control
S-300 / S-302
Faulty Flame Sensor
•
Test Flame Sensor
S-314
Faulty Ignition Control
• • •
Test Control
S-313
Gas Valve or Gas Supply Shut Off
•
Turn Valves to On Position
S-317
Faulty Induced Draft Blower
•
•
Test Induced Draft Motor
S-303
Faulty Blower Motor (PSC & ECM)
•
•
Test Blower Motor (PSC & ECM)
S-16A,B,C
Broken or Shorted Ignitor
•
Test Ignitor
S-308
Dirty Flame Sensor, Low UA
•
Clean Flame Sensor
S-314
Stuck Gas Valve
•
• •
Replace Gas Valve
S-304
Faulty Gas Valve
•
•
•
Replace Gas Valve
S-304
Open Auxiliary Limit
•
•
Reset Control
S-301
Improper Air Flow or Distribution
•
•
Check Duct Static
S-200
Cycling on Limit
• •
•
Check Controls & Temperature Rise
S-201 / S-300
Delayed Ignition
•
Test for Delayed Ignition
S-312
Flashback
•
Test for Flashback
S-309 / S-311
Orifice Size
• • •
Check Orifices
S-306 / S-311
Gas Pressure
•
• • •
Check Gas Pressure
S-307
Cracked Heat Exchanger
•
Check Burner Flames
S-305
Furnace Undersized
•
•
Replace with Proper Size Furnace
S-318
Furnace Oversized
•
Replace with Proper Size Furnace
S-318
Faulty Pressure Switch
• • •
Test Pressure Switch
S-310
Blocked or Restricted Flue
•
Check Flue/Drawdown Pressure
S-310
Open Roll Out Switch
• •
Test Flame Roll Out Control
S-302
Bouncing On Pressure Switch
•
Test Negative Pressure
S-310