32

Operation 

(Reference)

System Setup 

Menu Item

Description

Change 
Over 
Settings

<Precautions when using this control>

1.Do not use the set temperature restriction function in indoor units which are subject 
   to control.
If it is used, operation modes will be switched and the set temperature will be changed 
repeatedly, 

possibly causing the air conditioners to break down.

(See P44 for how to set the set temperature restriction function.)

2.The following will happen if a communication error (the icon on the screen is blue) 
   occurs in the air conditioner being controlled.
  2-1.Fixed air conditioner
       If the main unit experiences a communication error, the automatic cooling/heating 
       switch group control will not happen.
  2-2.Operating Air Conditioner Selection Method
       Remove the air conditioner experiencing the communication error from selection 
       as the main unit, and select an air conditioner with normal communication.
  2-3.Average Method
       Remove the air conditioner experiencing the communication error from the
       calculation for the average, and only use air conditioners with normal 
       communication for calculating the average.

3.Control which matches the main unit’s operation mode
   (Control for when the operation mode of the main unit does not represent the 
    automatic cooling/heating switch group.)
   It is possible that only the operation mode for the main unit is changed when control 
   using this function is done based on the main group unit (when the control method is 
   fixed air conditioner or operating air conditioner). The following control is performed 
   because it is possible that the operation mode of air conditioners other than the 
   main unit in the group might be in violation of the purpose of control and not 
   automatically switch if the conditions for implementing control using this function are 
   not satisfied.

  [Example] Heating Mode-Matched Control
  When the main unit is already operating in heating mode, whether or not the 
  conditions for implementing a switch from cooling to heating (main room temperature 
  < main set temperature – temperature difference) depends on the state 
  (environment) of the main unit. (If only the main unit is in heating operation, it is 
  possible that the room temperature might not rise because of the indoor units other 
  than the main unit which are in cooling operation, and the above control conditions 
  might not be satisfied.)
  Therefore, only when control is performed based on the main group unit is the 
  control below performed depending on the operation mode of the main group unit.

Caution

Cooling Mode-Matched Control

Operation mode

Set temperature

Operation mode Cooling/Automatic cooling

Temperature

Main room temperature>main set temperature

Heating Mode-Matched Control

Operation mode

Set temperature

Operation mode Heating/Automatic heating
Temperature

Main room temperature<main set temperature

Instructions to indoor units registered in the 
automatic cooling/heating switch group

State of main unit (control conditions)

Heating

main set temperature

Instructions to indoor units registered in the 
automatic cooling/heating switch group

State of main unit (control conditions)

Cooling

main set temperature

Oper

ation

Содержание DCS601B51

Страница 1: ...e LCD Maintenance 57 When Leaving the Product Turned OFF for a Long Time 57 Troubleshooting 58 Maintenance For Your Information Before use Operation Before use Safety Instructions Be sure to follow the instructions below 1 System Overview 3 Features and Functions 4 Part Names and Functions 5 Part Names on the Monitoring Screen and the Functions List 9 Icon 11 Operation Operation Quick Reference 13...

Страница 2: ...on Be sure to follow the instructions below Safety Instructions Read the manual carefully in advance for correct use Warning Notes on use for users When any abnormality such as burnt smell is generated turn the power OFF and contact the dealer you purchased the product from Continuing to operate with the abnormality left unattended may cause failure electric shock or fire For remodelling or repair...

Страница 3: ...device may lead to electrical leak and failure in the electronic components inside Do not wipe the surface of the controller touch panel with benzine thinner or chemically treated dust cloth Failure to follow the instruction may lead to discoloring or peeling of the paint Any soiling must be wiped off with a piece of cloth soaked in a diluted neutral detergent and wrung sufficiently Wipe again wit...

Страница 4: ...e air conditioners With the optional DCS002A51 A group of indoor units include Zone control with the intelligent Touch Controller Zone control which allows collective settings for more than one group is available with the intelligent Touch Controller which facilitates the setting operations q One indoor unit without a remote control e Up to 16 indoor units controlled with one or two remote control...

Страница 5: ...cheduled operation by the group by the zone or collectively Up to 8 options for annual schedule can be set Each schedule can include four types of plans for Weekdays Holidays Special days 1 and Special days 2 Each of the plans allows setting of up to 16 operations Diversified Operation Modes Operation can be controlled both with the main unit and the remote control to provide diversified operation...

Страница 6: ...e and failure Note Part Names and Functions Color LCD with Touch Panel Provides a display for monitoring and operation Be sure to use the touch pen provided for operation The display shows the Monitoring and System Setup screens PCMCIA Card Slot Used when using the optional power distribution DCS002A51 or updating the intelligent Touch Controller software to a newer version ...

Страница 7: ...door when adjusting the contrast of the LCD or luminance of the backlight Touch Pen Use the touch pen for operation Be sure to use the touch pen for operation Use caution not to lose the touch pen When the pen is lost contact the dealer you purchased the product from Before use ...

Страница 8: ... remote control adapter to this connector for collective start of operation collective stop of operation or error monitoring remotely with a contact signal This port is not used with this model Connect a non voltage contact for collective stopping of operation with a contact signal 232C 1 232C 2 CN2 Ethernet LON L2 L1 COM Dil Pi3 COM Pi2 Pi1 F2 F1 ...

Страница 9: ...02A51 Terminals for communication with air conditioning system Terminal for the grounding wire Terminals for the power supply Connect single phase power of 100 to 240 VAC 50 60 Hz 232C 1 232C 2 CN2 Ethernet LON L2 L1 COM Dil Pi3 COM Pi2 Pi1 F2 F1 This port is not used with this model Before use ...

Страница 10: ...ation operation in the zone or in the group Monitoring Screen Legend Pressing the button shows more detailed legend Button to Switch to the System Setup Mode Use this button for settings including the time group zone and schedule Description of Zone Group Set the names in the Group Registration or Zone Registration in the System Setup Mode System Status Display Area Area for displaying the system ...

Страница 11: ...l When there is any air conditioner generating an error Yellow Abnormal When there is any air conditioner with communication error Blue Abnormal Start All Button Button to collectively start all the air conditioners connected to intelligent Touch Controller Stop All Button Button to collectively stop all the air conditioners connected to intelligent Touch Controller Group Zone Start Button Button ...

Страница 12: ...ystem Setup Mode Filter Element Sign Displayed when there is any air conditioner showing a filter or element sign in the zone or the group Target of Automatic Control Displayed when there is any air conditioner with the registration of scheduled or change over or temperature limit or heating mode optimization operation in the zone or in the group Monitoring Screen Legend Pressing the button shows ...

Страница 13: ...lue Abnormal Start All Button Button to collectively start all the air conditioners connected to intelligent Touch Controller Stop All Button Button to collectively stop all the air conditioners connected to intelligent Touch Controller Group Zone Start Button Button to start operation of the group zone selected Group Zone Stop Button Button to stop operation of the group zone selected Group Zone ...

Страница 14: ...r by group To monitor detailed information System Setup Menu To change the name of a group To change the zone setup To change the schedule setup To calibrate the touch panel To adjust the contrast of the screen To review the history of errors See page 14 15 to See page 16 See page 17 See page 18 See page To reset the filter or element sign 19 See page 20 See page 21 See page 22 See page 26 See pag...

Страница 15: ...g collective start or stop press the Cancel button Start or stop collectively the operation of devices connected On the Monitoring screen operation is allowed with either Zone or Group as the display mode and with either Icon or List as the display type In the example on the left the display mode is Group in the collective mode and the display type is Icon On Screen 1 Monitoring press the Start Al...

Страница 16: ...r Zone Name Canteen 2 Select a zone that includes the group of which the operation is to be started or stopped w 3 4 Select a group to be started or stopped as in e and press the Start r or Stop t button Starting Stopping Operation by the Group Screen 2 Monitoring Group 1 2 3 4 5 Select a group from the pull down menu q Screen 2 Monitoring Group appears Zone Name Canteen 1F North 1F West 1F South ...

Страница 17: ...a zone from the pull down menu q 2 Starting Stopping Operation by the Zone 3 4 1 2 Select the zone of which the operation is to be started stopped as shown in w 3 Press the Start e or Stop r button Start or stop by zone the operation of groups of air conditioners set in zones The example on the left shows a screen for starting or stopping the operation of air conditioners in the canteen Procedure ...

Страница 18: ...are Fan Cool Heat and Auto If Cool Heat option is not available for any air conditioner in the zone Fan and Set Point are the available operation modes 2 Select with w a zone or a group of which the operation mode is to be switched 3 Press the Set Prop button e Screen 2 Operation appears 4 Select Set for the Operation Mode r Select the operation mode to be set from the pull down menu t 5 Switching...

Страница 19: ...the Set Point r Set the integer part of the setting in t and the decimal part in y Ex For the following zone setting the temperature settings available are between 20 C and 30 C inclusive When the temperature setting is 30 C the actual temperature settings for air conditioners are as shown below Note Range of temperature settings available is the range specified in accordance with the following Ra...

Страница 20: ...filter or element sign is to be reset w 3 Press the Set Prop button e Screen 2 Operation appears 4 Press the Advanced Func button r Screen 3 Advance Function appears 5 To reset the filter sign select Yes for Filter Sign Reset t To reset the element sign select Yes for Element Sign Reset y Then press the OK button u To cancel the setting press the Cancel button Screen 2 Operation reappears Resettin...

Страница 21: ...ion reappears 5 Changing the Direction Fan Speed Screen 2 Operation 6 To cancel the setting press the Cancel button 1 2 3 4 10 Screen 3 Advanced Operation 5 7 9 8 6 The larger the value for wind direction setting 0 6 the closer to vertical the direction becomes The value 7 indicates automatic swing Note See the figure below The description given above may not exactly apply depending on the model C...

Страница 22: ...Prohibited Changing the Range of Operation Allowed with Remote Control Screen 2 Operation 6 1 2 3 4 10 Screen 3 Advanced Operation 9 5 6 7 8 To cancel the setting press the Cancel button Screen 2 Operation reappears To cancel the setting press the Cancel button Press the OK button o after setting y i Then press the OK button 0 on Screen 2 Operation Item Setting Meaning Start Stop Prohibited The re...

Страница 23: ...ouching the screen allows selecting another zone or group Display o shows the settings for the zone or group selected with i The settings include the following from left Zone or group name Display 0 is an indicator for checking at a glance the status of all air conditioners connected to the intelligent Touch Controller Meanings of indications are as shown below When operation is normal and any air...

Страница 24: ...representative group for a zone 1 Group name Group description 0 63 Air conditioner or device Address between 1 00 and 4 15 Enable Disabled Enabled Disabled Only displayed during control Enable Disable Only displayed during control Enable Disable Mst Slv With Without Address of the outdoor unit Normal Error code when any error is generated 2 digit error code when any error is generated 0 when ther...

Страница 25: ...le on the left shows the filter sign illuminated 3Shows the current wind volume Low or High is shown 4Shows the remote control setting for starting or stopping operation One of the following is shown Prohibited Stop Only Permitted 5Shows the remote control setting for the operation mode One of the following is shown Prohibited Permitted Screen 2 Operation on the previous page reappears Pressing th...

Страница 26: ...ng the clock is not performed Ex When an air conditioner is scheduled to start at 10 00 q If the time is adjusted to 10 05 at 9 55 the scheduled operation q is not performed The operation scheduled to run at a time reached again by turning back the clock is performed again Ex When an air conditioner is scheduled to start at 10 00 q If the time is adjusted to 9 55 at 10 05 the scheduled operation q...

Страница 27: ...ade Addresses for central management include up to 64 addresses 1 00 1 01 1 15 2 00 4 15 Note The temperature setting limit is a function to allow operation only within the preset temperature limit to prevent too much cooling or heating The limit function above does not work when the operation mode of the air conditioners is Auto Ex Temperature setting limit 25 35 C cooling If the temperature is s...

Страница 28: ... name Schedule Setup Setting can be made for up to 13 months in advance Each of the plans allows setting of up to 16 operations 2 Make Weekly Setup in accordance with the usage for one week of the zone above Day off Weekly Setup Calendar Setup Weekday Special 1 Weekday 3 Make Calendar Setup for special usage other than the weekly usage of the zone above 47 See page 47 Day off Day off Special 2 See...

Страница 29: ...Stop Pattern Setup for Day off Disabled means no change Disabled means no change Disabled means no change Disabled means no change Hour 9 00 17 00 Zone concerned Zone 2F Zone 2F Start Stop Disabled Stop Temperaturesetting Disabled Disabled Operation mode Disabled Disabled R C mode Permitted Prohibited Pattern Setup for Special 1 9 00 12 00 12 00 Zone 2F Zone 1F Zone 2F Start Heat 25 C Permitted R ...

Страница 30: ...tisfies both of these conditions is designated the main indoor unit and the set temperature and room temperature of that indoor unit are designated the main set temperature and main room temperature If none is found which satisfies these conditions the main set temperature and main room temperature are determined using the Fixed Air Conditioner Method shown above 3 Average Method All the indoor un...

Страница 31: ...ure 1 C 1 2 qConditions for switching from heating to cooling Main room temperature main set temperature temperature difference 1 C Example 28 1 C 26 C 1 C 1 C wConditions for switching from cooling to heating Main room temperature main set temperature temperature difference 1 C Example 24 9 C 27 C 1 C 1 C qConditions for switching from heating to cooling Main room temperature main set temperature...

Страница 32: ...t sending the same instruction based on the main indoor unit to all the air conditioners When implementing the control the following operation modes and set temperature instructions are executed When conditions are met for switching from heating to cooling Operation mode Set temperature Heating Automatic heating cooling main unit setting temperature temperature difference Cooling Automatic cooling...

Страница 33: ...nditioner or operating air conditioner The following control is performed because it is possible that the operation mode of air conditioners other than the main unit in the group might be in violation of the purpose of control and not automatically switch if the conditions for implementing control using this function are not satisfied Example Heating Mode Matched Control When the main unit is alre...

Страница 34: ...t temperature of the indoor unit at 1 02 will continue at 23 C although only the operation mode will change to cooling i e in a different operation mode from the other indoor units in Group 2 The operation mode will be determined by Group 1 Actions regarding set temperature If the room temperature of Group 2 rises group 2 will switch to cooling as per this control and the set temperature will beco...

Страница 35: ...imit The air conditioner is stopped once the room temperature rises sufficiently far above the lower temperature limit lower temperature limit 4 C or more during heating due to this control q Controlled air conditioners This controls auto start and auto stop for each air conditioner based on the temperature set for each room temperature limit control group This control is not applicable to air con...

Страница 36: ...tion of cooling operation Cooling operation is controlled when the room temperature is higher than the upper limit of room temperature and the unit is stopped wStart condition of heating operation Heating operation is controlled when the room temperature is lower than the lower limit of room temperature and the unit is stopped eStop condition The air conditioners under cooling heating control by t...

Отзывы: