Installer reference guide
5
DCC601A51
intelligent Tab Controller
4P420109-1 – 2015.10
5.
Before installation
Before you start installing the intelligent Tab Controller, complete the
following preparations:
Check that the intelligent Tab Controller kit comes with all
accessories. Refer to
"3.1. Contents of the kit" on page 2
.
Check that you have all equipment necessary to install the
intelligent Tab Controller kit modules. Refer to
.
Check that an appropriate space for installing the intelligent Tab
Controller modules is available. Refer to
Familiarise yourself with the location of the terminals and
switches of the intelligent Tab Controller modules. Refer to
"5.3. The location of terminals and switches" on page 6
.
5.1.
Necessary equipment
Use the following equipment to install the intelligent Tab Controller kit
modules:
A flat-blade screwdriver
A Philips screwdriver
The necessary amount of electrical wires and appropriate wiring
tools. For more info on what wires to use, refer to
5.2.
Determining installation place
Make sure to install the intelligent Tab Controller components in a
place that complies with the conditions described in the following
sections.
5.2.1.
Installation place and mounting direction
Make sure the installation place complies with the following
requirements:
Location: Indoor, inside an electrical cabinet.
The electrical cabinet:
must be lockable or designed to be opened only with a
special tool. The key or tool should be available only to
service personnel.
must be installed in a space with no access for the general
public.
must comply with the applicable legislation.
must have ingress protection class of IP4X or higher
(however, make sure enough ventilation is provided to
prevent overheating of the equipment).
must have impact protection class of IK07 or higher (see
international standard IEC 62262 - 2002).
must have a minimum height of 290 mm and minimum width
of 410 mm to allow for the clearance specified in
"5.2.2. Required space" on page 5
Mounting direction: vertical only
Make sure the installation place complies with the environmental
conditions, specified in
"15.2. Environmental conditions" on
5.2.2.
Required space
The following figure indicates the minimum space required for
installation.
Make sure there is a minimum clearance of 60 mm between
both the CPU module, the I/O module and the wiring ducts and a
minimum clearance of 80 mm between the modules and the
electrical cabinet in the vertical direction.
Make sure there is a minimum vertical clearance of 70 mm
between the WAGO PSU and the wiring ducts.
The CPU module and I/O module can be installed without
clearance in the horizontal direction, but make sure there is a
minimum clearance of 20 mm between the modules and the
electrical cabinet.
The WAGO PSU requires a minimum clearance of 15 mm on
both sides in the horizontal direction.
a
Wire duct
b
Electrical cabinet
Observe the depth of these modules and make sure you provide the
necessary amount of space in depth in the electrical cabinet.
Module
Depth
CPU module
45 mm
I/O module
39 mm
WAGO PSU
92 mm
152
152
a
b
a
I/O
CPU
+ + - -
L N
(mm)