4 Installation

Installation manual

21

D2CND024A1/4AB + D2TND012~024A4AB
Wall-mounted condensing boiler
3P469346-3N – 2019.11

a

a

60/100 to 80/125 adapter

80/125 flue parts to be used are shown below:

a

b

c

d

e

f

a

80/125 wall terminal kit (type C13)

b

80/125 roof terminal kit (type C33)

c

90° elbow 80/125

d

45° elbow 80/125

e

30° elbow 80/125

f

Extension 80/125
L = 500-1000 mm

Type C43x (concentric flue system)

Several heat sources draw combustion air from the outside through
the annular gap of the room sealed balanced flue system and expel
flue  gas  to  the  outside  via  the  roof,  through  a  moisture-resistant
internal pipe.

The multi-served chimney is a system that is part of the building and
has a separate CE marking. The connection between the boiler and
the  shaft  and,  the  connection  between  the  boiler  and  the  air  intake
system must be obtained via Daikin.

e

f

g

h

L

i

a b c

d

a

Tee flex boiler connection set 100 or 130

b

Extension 60 mm

c

Chimney connection 60/100

d

Elbow 60/100 90°

Optional:

e

90° elbow 60/100

f

45° elbow 60/100

g

Inspection elbow 60/100

h

30° elbow 60/100

i

Extension 60/100
L = 500-1000 mm

Maximum  allowable  length  of  the  flue  duct  up  to  common
chimney is 3  1 60/100 90° elbow.

In C43x type units, condensate flow into the unit is not allowed.

Type C63x (concentric flue system)

INFORMATION

C63 flue type is not applicable to Belgium.

To  install  the  boiler  as  a  C63x  option  the  following  data  must  be
used  to  determine  the  correct  diameters  and  lengths  of  the  flue
system.

For D2T/H*

▪ Nominal combustion products temperature: 77°C

▪ Combustion products mass flow rate: 10.75 g/s

▪ Overheat combustion products temperature: 90°C

▪ Minimum combustion products temperature: 20°C

▪ Maximum  allowable  pressure  difference  between  combustion  air

inlet and flue gas outlet (including wind pressures): 100 Pa

For D2C*

▪ Nominal combustion products temperature: 93°C

▪ Combustion products mass flow rate: 11.48 g/s

▪ Overheat combustion products temperature: 100°C

▪ Minimum combustion products temperature: 20°C

▪ Maximum  allowable  pressure  difference  between  combustion  air

inlet and flue gas outlet (including wind pressures): 125 Pa

For D2C* and D2T/H*

▪ Minimum combustion products mass flow rate: 1.32 g/s

▪ CO

2

 content at nominal heat input: 9.0%

▪ Maximum allowable draught: 200 Pa

▪ The  boiler  must  be  connected  to  a  system  with  the  following

characteristics: T120 P1 W

▪ Maximum allowable temperature of combustion air: 50°C

▪ Maximum  allowable  recirculation  rate  under  wind  conditions  is

10%

▪ The  terminals  for  the  supply  of  combustion  air  and  for  the

evacuation  of  combustion  products  shall  not  be  installed  on
opposite walls of the building.

▪ Condensate flow into the unit is allowed.

Type C53x (twin pipes flue system)

Air  supply  and  flue  gas  discharge  from  /  to  atmosphere  in  areas  of
different pressure. The boiler draws combustion air from outside via
a horizontal pipe fitted to the external wall and expels flue gas to the
outside via the roof.

The terminals for the supply of combustion air and for the evacuation
of combustion products shall not be installed on opposite walls of the
building.

Содержание D2CND024A4AB

Страница 1: ...Installation manual Wall mounted condensing boiler English Installation manual Wall mounted condensing boiler D2CND024A1AB D2CND024A4AB D2TND012A4AB D2TND018A4AB D2TND024A4AB...

Страница 2: ...tiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lie...

Страница 3: ...essure 29 Disposal Old units must be appropriately disposed of in accordance with local and national regulations The components are easy to separate and the plastics are marked This allows the various...

Страница 4: ...2 Safety instructions These instructions are exclusively designed for qualified competent persons Work on gas units must only be carried out by a qualified gas fitter Work on electrical equipment must...

Страница 5: ...rising Safety valve When the water pressure of the heating circuit exceeds 3 bar some water is automatically drained from the safety valve to keep the pressure below 3 bar thus protecting the boiler a...

Страница 6: ...TND012 024A4AB Wall mounted condensing boiler 3P469346 3N 2019 11 Bottom view of model D2CND024A4AB 53 161 7 105 8 101 4 22 4 65 61 71 9 65 1 Bottom view of models D2TND012A4AB D2TND018A4AB and D2TND0...

Страница 7: ...Return temperature sensor s Silencer t Automatic air vent pump u Water pressure sensor v By pass w Boiler pump x Domestic hot water flow sensor y Domestic hot water flow limiter z Internal filling val...

Страница 8: ...x m h 0 12 0 46 0 12 0 69 0 12 0 96 0 12 0 96 Combustion products mass flow rate min max G20 g s 1 32 5 12 1 32 7 78 1 32 10 75 1 32 10 75 Combustion products mass flow rate min max G31 g s 1 23 4 77...

Страница 9: ...aters 50 C return temperature at heater inlet 4 Installation 4 1 To open the unit WARNING Only qualified competent persons are allowed to open the unit Certain actions explained in this document such...

Страница 10: ...current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake air must not include chemicals that may cause corrosion toxic gas formation a...

Страница 11: ...height and related system charge pressure are given below h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0 bar 9 m 1 1 bar 10 m 1 2 bar 11 m 1 3 bar 12 m 1 4 bar 13 m 1 5 bar h h System water height m p System cha...

Страница 12: ...ted to 50 C and the pump operation temperature difference must be adjusted to 10 Kelvin in the service settings menu To change this setting refer to the servicing instructions WARNING Make sure parame...

Страница 13: ...d Note Optional Daikin connection kit can be used and it is recommended to use it 4 8 2 Guidelines when connecting the gas piping This unit is designed to be operated with natural gas or LPG The prese...

Страница 14: ...ar preheating of the domestic hot water from a solar tank install the thermostatic mixing valve at the domestic hot water outlet and inlet 4 8 4 Guidelines when connecting the electrical wiring DANGER...

Страница 15: ...the options that are to be connected to the internal connectors must pop out from the inside of the unit via cable glands Cable glands that are sent with the unit must be assembled to the bottom shee...

Страница 16: ...4AB Wall mounted condensing boiler 3P469346 3N 2019 11 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Models D2CND024A1AB and D...

Страница 17: ...Ext3 X1M Daikin room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1M X4 X11 X12 Low voltage terminal strip X2M X1 X2 High voltage terminal strip 4 8 7 Guidelines wh...

Страница 18: ...pes are written on the identification label Flue termination The positions of the terminals in the roof or in the wall with respect to openings for ventilation must be in accordance with national regu...

Страница 19: ...ith a negative pressure area and therefore a plume management kit MUST be fitted 4 8 10 Applicable flue systems In this part information about different flue systems are given The mounting instruction...

Страница 20: ...e Flat roof outlet kit f 90 elbow 60 100 g 45 elbow 60 100 h 30 elbow 60 100 i Extension 60 100 L 500 1000 mm Allowable flue length for C33x D2T H D2C Concentric 60 100 mm 12 5 m 7 6 m Concentric 80...

Страница 21: ...ne the correct diameters and lengths of the flue system For D2T H Nominal combustion products temperature 77 C Combustion products mass flow rate 10 75 g s Overheat combustion products temperature 90...

Страница 22: ...use flue outlet duct length must be shortened with the same length Type C83x twin pipes flue system The boiler draws combustion air from outside via a separate supply pipe routed through the external...

Страница 23: ...69 2 DN 80 Flex square and rough 130 17 0 60 0 DN 80 Flex square and rough 120 12 2 43 0 DN 80 Star square and rough 140 47 5 167 8 DN 80 Star square and rough 120 33 3 117 9 Allowable flue length fo...

Страница 24: ...EKFGP4801 1000 mm EKFGP4802 Flue part Order code Tile roof outlet kit 60 100 18 22 EKFGS0518 23 27 EKFGS0519 25 45 EKFGP7910 43 47 EKFGS0523 48 52 EKFGS0524 53 57 EKFGS0525 Tile roof outlet kit 80 12...

Страница 25: ...ition 4 Connect the filling loop to the valve 7 and valve 8 5 Set valves 1 3 5 6 and 8 to open position 6 Slowly open the valve 7 until pressure reaches a value around 0 8 bar for system heights up to...

Страница 26: ...3 Choose C parameters via left dial and press the Enter button 4 Choose CE and press the Enter button It will ask for password again Choose the password 115 and press the Enter button 5 Choose C0 and...

Страница 27: ...The status indicator will glow constantly in blue if flame is established icon will blink when central heating is active INFORMATION After first power ON the boiler does not increase its capacity abov...

Страница 28: ...5 Check that domestic hot water temperature rise is around 34 C 6 Hand over to the user After completing the installation and commissioning of the system the installer should hand over to the househo...

Страница 29: ...rson who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference GAS BOILER SYSTEM COMMISS...

Страница 30: ...co uk It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed Service Provider SERVICE RECORD SERVICE 01 AND Where Possible AND S...

Страница 31: ......

Страница 32: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P469346 3N 2019 11 Copyright 20...

Отзывы: