4 Installation

Installation manual

10

D2CND024A1/4AB + D2TND012~024A4AB

Wall-mounted condensing boiler

3P469346-3N – 2019.11

a

a

Vertical, flat wall

▪ The  boiler  can  be  installed  outdoors  in  a  partially  protected

location.  A  partially  protected  location  is  a  place  where  the  boiler
is  not  exposed  to  the  direct  action  and  to  the  penetration  of
atmospheric precipitation (rain, snow, hail,...).

The boiler can also be installed inside of an outside wall using the
appropriate in‑wall kit.

In  case  of  outdoor  installation,  use  the  antifreeze  kit
(DRANTIFREEZxx  )  to  prevent  the  piping  and  condensate  trap
from freezing.

▪ Flammable  fluids  and  materials  must  be  stored  at  least  1  metre

away from the boiler.

▪ The wall on which the unit is mounted should be strong enough to

carry the unit's weight. Build a reinforcement if necessary.

▪ The  following  minimum  clearances  are  required  for  servicing:

180  mm  above  the  casing*,  200  mm  below,  and  10  mm  at  each
side. 500 mm at the front clearance may be realised by opening a
cupboard door. See 

"Minimum installation clearances"

 [

4

 10].

▪ For  easier  use  of  control  panel,  it  is  recommended  that  boiler

bottom is 1500 mm from the floor, for easier part replacement side
clearances  should  be  50  mm  where  applicable.  See 

"Minimum

installation clearances"

 [

4

 10].

▪ If  the  boiler  is  installed  in  a  room  or  compartment,  it  does  not

require  a  dedicated  ventilation  for  combustion  air.  If  however
installed in a room containing a bath or a shower, then particular
reference  is  drawn  to  the  current  I.E.E.  Wiring  Regulations,  local
Building  Regulations  or  any  other  local  regulations  currently  in
service.

▪ The  intake  air  must  not  include  chemicals  that  may  cause

corrosion, toxic gas formation and even risk of explosion.

▪ If  the  wall  on  which  the  unit  is  mounted,  is  flammable,  a  non-

flammable material must be placed between the wall and the unit
and also at all locations through where the flue piping passes.

Minimum installation clearances

a

a

d

f

c

e

d

b

Minimum allowable clearances

a, sides

10 mm

b, Above the casing*

180 mm

c, below

200 mm

f, in front

500 mm

Recommended clearances for easy servicing

d, sides

50 mm

e, below (from the floor)

1500 mm

*

180 mm

 is for the case that 60/100 90° elbow is connected

to the flue outlet of the boiler.

b = 270 mm

 in case that 60/100 to 80/80 a 90°

elbow 80 are connected to the flue outlet of the boiler.

b = 280 mm

 in case that 60/100 to 80/125 a 90°

elbow 80/125 are connected to the flue outlet of the boiler.

4.3

To unpack the unit

1

Unpack  the  unit  as  shown  on  top  of  the  packing  case.  The
following items must be included in the package:

a

b

c

d

e

f

g

h

i

j

a

Combi boiler

b

Operation manual

c

Installation manual

d

Wall-mounting bracket

e

Installation template

f

Dowels and screws

g

Condensate hose

h

Cable glands 2×PG 7, 1×PG 9

i

Energy label

j

Storage tank temperature sensor (only for models
D2TND012A4AB, D2TND018A4AB and D2TND024A4AB)

2

Check the contents of the package. If any of them is damaged
or missing, contact your dealer.

CAUTION

Store  the  remaining  parts  of  the  package  (cardboard,
plastic,  etc.)  in  a  place  children  cannot  reach.  The
manufacturer  is  not  responsible  for  any  accidents  and/or
damage that may occur this way.

Содержание D2CND024A4AB

Страница 1: ...Installation manual Wall mounted condensing boiler English Installation manual Wall mounted condensing boiler D2CND024A1AB D2CND024A4AB D2TND012A4AB D2TND018A4AB D2TND024A4AB...

Страница 2: ...tiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lie...

Страница 3: ...essure 29 Disposal Old units must be appropriately disposed of in accordance with local and national regulations The components are easy to separate and the plastics are marked This allows the various...

Страница 4: ...2 Safety instructions These instructions are exclusively designed for qualified competent persons Work on gas units must only be carried out by a qualified gas fitter Work on electrical equipment must...

Страница 5: ...rising Safety valve When the water pressure of the heating circuit exceeds 3 bar some water is automatically drained from the safety valve to keep the pressure below 3 bar thus protecting the boiler a...

Страница 6: ...TND012 024A4AB Wall mounted condensing boiler 3P469346 3N 2019 11 Bottom view of model D2CND024A4AB 53 161 7 105 8 101 4 22 4 65 61 71 9 65 1 Bottom view of models D2TND012A4AB D2TND018A4AB and D2TND0...

Страница 7: ...Return temperature sensor s Silencer t Automatic air vent pump u Water pressure sensor v By pass w Boiler pump x Domestic hot water flow sensor y Domestic hot water flow limiter z Internal filling val...

Страница 8: ...x m h 0 12 0 46 0 12 0 69 0 12 0 96 0 12 0 96 Combustion products mass flow rate min max G20 g s 1 32 5 12 1 32 7 78 1 32 10 75 1 32 10 75 Combustion products mass flow rate min max G31 g s 1 23 4 77...

Страница 9: ...aters 50 C return temperature at heater inlet 4 Installation 4 1 To open the unit WARNING Only qualified competent persons are allowed to open the unit Certain actions explained in this document such...

Страница 10: ...current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake air must not include chemicals that may cause corrosion toxic gas formation a...

Страница 11: ...height and related system charge pressure are given below h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0 bar 9 m 1 1 bar 10 m 1 2 bar 11 m 1 3 bar 12 m 1 4 bar 13 m 1 5 bar h h System water height m p System cha...

Страница 12: ...ted to 50 C and the pump operation temperature difference must be adjusted to 10 Kelvin in the service settings menu To change this setting refer to the servicing instructions WARNING Make sure parame...

Страница 13: ...d Note Optional Daikin connection kit can be used and it is recommended to use it 4 8 2 Guidelines when connecting the gas piping This unit is designed to be operated with natural gas or LPG The prese...

Страница 14: ...ar preheating of the domestic hot water from a solar tank install the thermostatic mixing valve at the domestic hot water outlet and inlet 4 8 4 Guidelines when connecting the electrical wiring DANGER...

Страница 15: ...the options that are to be connected to the internal connectors must pop out from the inside of the unit via cable glands Cable glands that are sent with the unit must be assembled to the bottom shee...

Страница 16: ...4AB Wall mounted condensing boiler 3P469346 3N 2019 11 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Models D2CND024A1AB and D...

Страница 17: ...Ext3 X1M Daikin room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1M X4 X11 X12 Low voltage terminal strip X2M X1 X2 High voltage terminal strip 4 8 7 Guidelines wh...

Страница 18: ...pes are written on the identification label Flue termination The positions of the terminals in the roof or in the wall with respect to openings for ventilation must be in accordance with national regu...

Страница 19: ...ith a negative pressure area and therefore a plume management kit MUST be fitted 4 8 10 Applicable flue systems In this part information about different flue systems are given The mounting instruction...

Страница 20: ...e Flat roof outlet kit f 90 elbow 60 100 g 45 elbow 60 100 h 30 elbow 60 100 i Extension 60 100 L 500 1000 mm Allowable flue length for C33x D2T H D2C Concentric 60 100 mm 12 5 m 7 6 m Concentric 80...

Страница 21: ...ne the correct diameters and lengths of the flue system For D2T H Nominal combustion products temperature 77 C Combustion products mass flow rate 10 75 g s Overheat combustion products temperature 90...

Страница 22: ...use flue outlet duct length must be shortened with the same length Type C83x twin pipes flue system The boiler draws combustion air from outside via a separate supply pipe routed through the external...

Страница 23: ...69 2 DN 80 Flex square and rough 130 17 0 60 0 DN 80 Flex square and rough 120 12 2 43 0 DN 80 Star square and rough 140 47 5 167 8 DN 80 Star square and rough 120 33 3 117 9 Allowable flue length fo...

Страница 24: ...EKFGP4801 1000 mm EKFGP4802 Flue part Order code Tile roof outlet kit 60 100 18 22 EKFGS0518 23 27 EKFGS0519 25 45 EKFGP7910 43 47 EKFGS0523 48 52 EKFGS0524 53 57 EKFGS0525 Tile roof outlet kit 80 12...

Страница 25: ...ition 4 Connect the filling loop to the valve 7 and valve 8 5 Set valves 1 3 5 6 and 8 to open position 6 Slowly open the valve 7 until pressure reaches a value around 0 8 bar for system heights up to...

Страница 26: ...3 Choose C parameters via left dial and press the Enter button 4 Choose CE and press the Enter button It will ask for password again Choose the password 115 and press the Enter button 5 Choose C0 and...

Страница 27: ...The status indicator will glow constantly in blue if flame is established icon will blink when central heating is active INFORMATION After first power ON the boiler does not increase its capacity abov...

Страница 28: ...5 Check that domestic hot water temperature rise is around 34 C 6 Hand over to the user After completing the installation and commissioning of the system the installer should hand over to the househo...

Страница 29: ...rson who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference GAS BOILER SYSTEM COMMISS...

Страница 30: ...co uk It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed Service Provider SERVICE RECORD SERVICE 01 AND Where Possible AND S...

Страница 31: ......

Страница 32: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P469346 3N 2019 11 Copyright 20...

Отзывы: