background image

English

English

10

6. 

Drain piping

1) Connect the drain hose, as described right.

The drain hose should 
be inclined downward.

No trap is permitted.

Do not put the end 
of the hose in water.

2) Remove the air filters and pour some water into the drain pan to check the water flows 

smoothly.

3) If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.

[Figure of hose front end]

ϕ

18

ϕ

16

4) When extending the drain hose, use a commercially available 

extension hose with an inner diameter of 16mm.
Be sure to thermally insulate the indoor section of the extension 
hose.

ϕ

16

Drain hose supplied 
with the indoor unit

Indoor unit 
drain hose

ϕ

16

Extension drain hose

Heat insulation tube

(field supply)

5) When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 13mm) directly to the drain 
hose attached to the indoor unit as with embed

-

ded piping work, use any commercially available 
drain socket (nominal diameter 13mm) as a joint.

Commercially available drain 
socket 
(nominal diameter 13mm)

Commercially available rigid 
polyvinyl chloride pipe
(nominal diameter 13mm)

Drain hose supplied 
with the indoor unit

ϕ

18

Refrigerant Piping Work

1. 

Flaring the pipe end

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward 

so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

Set exactly at the position shown below.

A

Flaring

Die

A

0-0.5mm

Clutch-type

Flare tool for R410A

1.0-1.5mm

Clutch-type (Rigid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

(Cut exactly at 

right angles.)

 Remove burrs.

Check

Flare’s inner 
surface must 

be flaw-free.

The pipe end must 

be evenly flared in 

a perfect circle.

Make sure that the 

flare nut is fitted.

WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Do never install a drier to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.

01_EN_3P297034-1.indd   10

10/12/2011   11:37:07 AM

Содержание CTXS15K2V1B

Страница 1: ...CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Installationsanleitung Manuel dinstallation Installatiehandleiding Manual de instalación Manuale dinstallazione Εγχειρίδιο εγκατάστασης Manual de instalação Руководство по монтажу Montaj kılavuzları Manuel dinstallation Manuale dinstallazione 00_CV_3P297034 1 indd 1 10 31 2011 2 09 38 PM ...

Страница 2: ...oltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB65451 1 FTXS20K2V1B FTXS25K2V1B CTXS15K2V1B CTXS35K2V1B Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N20 09 2011 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 1 fm Page 1 Thursday October 27 2011 4 40 PM ...

Страница 3: ...Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan FTXS20K2V1B FTXS25K2V1B CTXS15K2V1B CTXS35K2V1B 3SB65451 2 Shinri Sada Manager Quality Control Department 3SB65451 2 fm Page 1 Thursday October 27 2011 4 43 PM ...

Страница 4: ...3SB65451 2 fm Page 2 Thursday October 27 2011 4 43 PM ...

Страница 5: ...wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation...

Страница 6: ...ot in the path of direct sunlight 4 the unit is away from the source of heat or steam 5 there is no source of machine oil vapour this may shorten indoor unit life 6 cool warm air is circulated throughout the room 7 the unit is away from electronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote controller range 8 the unit is at least 1m away from any tel...

Страница 7: ...e mark of the front grille there are 3 upper hooks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand Upper hook mark area 3 locations Push down Upper hook When there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the center of the front grille and while pushin...

Страница 8: ...ervice lid is opening closing type Opening method 1 Remove the service lid screw 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down The mounting plate should be installed on a wall which can support the weight of the indoor unit 30mm or more from ceiling Front panel 50mm or more from walls on both sides Air filters A Mounting plate A Mounting plate Mounting plate fi...

Страница 9: ... hole ϕ65mm 2 Boring a wall hole and installing wall embedded pipe For walls containing metal frame or metal board be sure to use a wall embedded pipe and wall cover in the feed through hole to prevent possible heat electrical shock or fire Be sure to caulk the gaps around the pipes with caulking material to prevent water leakage 1 Bore a feed through hole of 65mm in the wall so it has a down slop...

Страница 10: ...here for right side piping Remove pipe port cover here for right bottom piping 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as a guide Mounting plate A 4 Open the front panel then open the service lid Refer to preparation before installation 5 Pass the inter unit wire from ...

Страница 11: ...ong the pipe path marking on the mounting plate 4 Pass drain hose and refrigerant pipes through the wall hole then set the indoor unit on mounting plate hooks using the markings at the top of indoor unit as a guide 5 Pull in the inter unit wire 6 Connect the inter unit pipes Drain hose Caulk this hole with putty or caulking material Bind with adhesive vinyl tape A Mounting plate Wrap insulating ta...

Страница 12: ...use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Do not connect the power wire to the indoor unit Doing so may cause electric shock or fire 5 When connecting to a wired remote controller If work space is available on the right side of the indoor unit the work can be performed w...

Страница 13: ... the connection cord as shown in Figure 3 5 8 Install the electrical component box in its original position 1 Install the electrical component box 1 screw 2 Install the thermistor in its original position on the heat exchanger 3 Connect the earth wire 4 Install the connector S200 in its original position 5 Connect the inter unit wire in its original position 6 Install the flap 5 9 Install the fron...

Страница 14: ...lly available rigid polyvinyl chloride pipe nominal diameter 13mm Drain hose supplied with the indoor unit ϕ18 Refrigerant Piping Work 1 Flaring the pipe end 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the pipe 3 Put the flare nut on the pipe 4 Flare the pipe 5 Check that the flaring is properly made Set exactly at the po...

Страница 15: ...Protect the open end of the pipe against dust and moisture 2 All pipe bends should be as gentle as possible Use a pipe bender for bending Wall If no flare cap is available cover the flare mouth with tape to keep dirt or water out Be sure to place a cap Rain 2 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation materia...

Страница 16: ...e original operation mode when the circuit breaker is opened again Trial operation from remote controller 1 Press ON OFF button to turn on the system 2 Press TEMP button 2 locations and MODE button at the same time 3 Press TEMP button and select T 4 Press MODE button 5 Trial operation terminates in approx 30 minutes and switches into normal mode To quit a trial operation press ON OFF button 2 Test...

Страница 17: ...Two dimensional bar code is a code for manufacturing 3P297034 1 M11B099 1111 HT 00_CV_3P297034 1 indd 2 10 31 2011 2 09 38 PM ...

Отзывы: