3
|
Components
Service manual
98
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01D – 2022.02
CAUTION
Ensure that the system CANNOT start the fan. Disable all modes (heating, cooling, …)
on the unit. The unit MUST be kept powered.
14
Manually (slowly) rotate the fan blade propeller 1 turn and measure the
voltage on the DC fan motor connector pins 1-4.
Result:
4 pulses MUST be measured.
Pulses are measured during fan blade
propeller rotation?
Action
Yes
Perform a check of the main PCB, see
85].
No
Replace the DC fan motor, see
98].
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Repair procedures
To remove the propeller fan blade assembly
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
100].
2
Remove the nut that fixes the propeller fan blade assembly.
a
b
a
Nut
b
Propeller fan blade assembly
3
Pull and remove the propeller fan blade assembly from the DC fan motor
assembly.