English
1-9
IMPORTANT:
* These values are for information only. They should be checked and selected to comply with local and/or
national codes and/or national codes and regulations. They are also subject to the type of installation and
size of conductors.
** The appropriate voltage range should be checked with label data on the unit.
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated
in the
fi
xed wiring in accordance with the relevant local and national legislation.
FWPMM3A(Z)V1 / FWPMM4A(Z)V1 / FWPMM6A(Z)V1 / FWPMM7A(Z)V1 / FWPMM8A(Z)V1 /
FWPMM9A(Z)V1 / FWPMM11A(Z)V1 / FWPMM12A(Z)V1 / FWPMM14A(Z)V1 / FWPMM16A(Z)V1
(with controller)
X1
3WV
Chiller
VALVE
L
N
220-240V/1ø/50Hz or
208-230V/1ø/60Hz
L
N
X2
3WV
VALVE
L
N
220-240V/1ø/50Hz or
208-230V/1ø/60Hz
L
N
X3
3WV
VALVE
L
N
220-240V/1ø/50Hz or
208-230V/1ø/60Hz
L
N
3WV
3 way valve
Field supply
X1, X2, X3, Relay (220 ~ 240V, 10A)
FCU 1
FCU 2
FCU 3
Note:
This is a proposed wiring connection. It may change subject to the chiller unit and must comply with the local and national
code and regulations.
Model
Indoor
FWPMM3A(Z)V1 FWPMM4A(Z)V1 FWPMM6A(Z)V1 FWPMM7A(Z)V1 FWPMM8A(Z)V1
Voltage Range**
Indoor
220V-240V/1Ph/50Hz +
!
or 208V-230V/1Ph/60Hz +
!
Power Supply Cable Size*
mm
2
Number of Conductors
1.5
3
1.5
3
1.5
3
1.5
3
1.5
3
Recommended Time Delay Fuse*
A
1
2
4
4
6
Model
Indoor
FWPMM9A(Z)V1 FWPMM11A(Z)V1 FWPMM12A(Z)V1 FWPMM14A(Z)V1 FWPMM16A(Z)V1
Voltage Range**
Indoor
220V-240V/1Ph/50Hz +
!
or 208V-230V/1Ph/60Hz +
!
Power Supply Cable Size*
mm
2
Number of Conductors
1.5
3
1.5
3
1.5
3
1.5
3
1.5
3
Recommended Time Delay Fuse*
A
8
10
10
10
12
!
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
All power line must be from
the same phase.