background image

English

1-11

OVERALL CHECKING

Ensure the following, in particular:-

The unit is mounted solidly and rigid in position.
Piping and connections are leak proof after charging.
Proper wiring has been done.

Drainage check:- Pour some water into left side of drain pan (drainage are in right side of unit).

Note:

The installation guide above covers only the fan coil unit. For installation guide of outdoor (chiller mini etc) please refer 
to the installation guide for such unit.
The installation of fan coil unit may vary according to the type of outdoor unit.
Installation must be done by quali

fi

 ed personnel who are familiar with this type of product.

1.
2.
3.


SERVICE AND MAINTENANCE

Service Parts

Maintenance Procedures

Period

Indoor Air Filter

Remove any dust adhered on the 

fi

 lter by using a vacuum cleaner or wash 

in lukewarm water (below 40°C) with neutral cleaning detergent.
Rinse the 

fi

 lter well and dry before placing it back onto the unit.

Do not use gasoline, volatile substances or chemical to clean the 

fi

 lter.

1.

2.
3.

At least once every 
2 weeks.

More frequently if 
necessary.

Indoor Unit

Clean any dirt or dust on the grille or panel by wiping it off with soft cloth 
soaked in lukewarm water (below 40°C) with neutral detergent solution.
Do not use gasoline, volatile substances or chemicals to clean the indoor 
unit. 

1.

2.

At least once every 
2 weeks.

More frequently if 
necessary.

Indoor Fan

Check for any abnormal noise. 

1.

When necessary

For any enquiries on spare part please contact your authorized dealer. When any malfunction of the air 
conditioner unit is noted, immediately switch off the power supply to the unit. Check the following fault 
conditions and causes for some simple troubleshooting tips.

If the fault persists, please call your local dealer / serviceman.

TROUBLESHOOTING

Fault

Causes / Action

The air conditioner unit does not operate.

1.

Power failure, or the fuse need to be replaced.
The power plug is disconnected.
It is possible that your delay timer has been set incorrectly.



The air 

fl

 ow is too low.

2.

The air 

fi

 lter is dirty.

The air suction and discharge are clogged.
 The regulated temperature is not high enough. 
 (applicable for auto fan mode only)



Discharge air 

fl

 ow has bad odor.

3.

Odors may be caused by cigarettes, smoke particles, perfume 
etc. which might have adhered onto the coil.

Condensation on the front air grille of the indoor 
unit.

4.

This is caused by air humidity after an extended long period 
of operation.
The set temperature is too low, increase the temperature 
setting and operate the unit at high fan speed.

Water 

fl

 owing out from the air conditioner unit.

5.

Switch off unit and call local dealer / serviceman.

IM-CCCW 0308(5)DK(asean)-EN.indd11   11

IM-CCCW 0308(5)DK(asean)-EN.indd11   11

11/29/13   8:37:32 AM

11/29/13   8:37:32 AM

Содержание C-Series

Страница 1: ...D CHILLED WATER FAN COIL UNIT C Series INSTALLATION MANUAL IM CCCW 0308 5 DAIKIN ASEAN Part No R08019031562E CVR IM CCCW 0308 5 DK asean ind1 1 CVR IM CCCW 0308 5 DK asean ind1 1 11 29 13 8 34 18 AM 11 29 13 8 34 18 AM ...

Страница 2: ...CVR IM CCCW 0308 5 DK asean ind2 2 CVR IM CCCW 0308 5 DK asean ind2 2 11 29 13 8 34 19 AM 11 29 13 8 34 19 AM ...

Страница 3: ... M L K G D 150 31 10 51 10 150 31 E A B C F 131 P 40 36 40 20 10 N O Q 178 133 39 131 40 10 63 WATEROUTLET All dimensions are in mm I J I H LEFT PIPING WATERINLET All dimensions are in mm 10 D H 31 150 51 31 150 10 I J I K L M F C B A E P 131 40 40 20 36 10 N O 63 10 40 131 40 133 178 Q G RIGHT PIPING WATEROUTLET WATERINLET IM CCCW 0308 5 DK asean EN indd1 1 IM CCCW 0308 5 DK asean EN indd1 1 11 2...

Страница 4: ...A FOR FWPMM4 121 179 133 84 60 M L K D H 31 51 10 10 31 R G I J I Q 131 40 40 40 131 40 P N O 10 10 36 E C B A F R LEFT PIPING WATEROUTLET WATERINLET WATEROUTLET WATERINLET WATEROUTLET WATERINLET All dimensions are in mm 31 10 SEE DETAILA FOR FWPMM4 SEE DETAIL B FOR FWPMM6 7 DETAIL B FOR FWPMM6 7 DETAIL A FOR FWPMM4 I J I 10 R G M L K D H R 31 51 F C B A P 40 131 40 10 N O 40 131 40 Q 36 10 60 133...

Страница 5: ... 31 FWPMM11AV1 97 638 559 186 233 563 156 148 97 149 51 All dimensions are in mm 25 W 160 22 V U T C O 15 15 S 15 P M L E B A F K D G 371 40 15 16 50 25 R H Q N I J I LEFT PIPING WATEROUTLET WATERINLET 16 50 W 15 25 R H K L M G D 371 40 F C B A E P S 15 15 15 N O 25 U T V 22 160 Q I J I All dimensions are in mm RIGHT PIPING WATEROUTLET WATERINLET IM CCCW 0308 5 DK asean EN indd3 3 IM CCCW 0308 5 D...

Страница 6: ...59 159 109 196 FWPMM12AV1 173 541 462 173 307 467 359 159 109 196 FWPMM14AV1 173 541 462 173 307 594 359 156 106 196 FWPMM16AV1 183 541 462 173 307 694 359 154 104 196 Q 15 59 188 60 U T N O 15 40 93 40 P E C B A F G R 40 I J I H D 25 50 15 M L K S All dimensions are in mm LEFT PIPING WATEROUTLET WATERINLET I D H 25 J I 50 40 S G K L M R F C B A E P 40 93 40 15 N O 60 188 59 Q V T U 15 15 All dime...

Страница 7: ...atic part to melt or deform as a result of excessive heat or chemical reaction Whentheunitisusedinkitchen keepflourawayfromgoing into suction of the unit This unit is not suitable for factory used where cutting oil mist or iron powder exist or voltage fluctuates greatly Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively IMPORTANT DO NOT INS...

Страница 8: ...n in the diagram INSTALLATION DIAGRAM INSTALLATION OF THE INDOOR UNIT CAUTION Do not install the unit at altitude over 2000m for both indoor and outdoor CC FWPMM3A Z V1 FWPMM4A Z V1 FWPMM6A Z V1 FWPMM7A Z V1 FWPMM8A Z V1 A mm 741 881 1041 1176 959 L mm 225 225 225 225 339 CC FWPMM9A Z V1 FWPMM11A Z V1 FWPMM12A Z V1 FWPMM14A Z V1 FWPMM16A Z V1 A mm 956 1264 1076 1326 1526 L mm 266 401 266 266 266 3...

Страница 9: ...lve Gate Valve Gate Valve FCU Two Way Valve Good Controlling Bad Controlling Gate Valve Gate Valve FCU Worst Controlling WATER PIPING CONNECTION 100 100 The drain pipe must be installed as shown in the diagram see diagram above to avoid damage caused by leaks and condensation For the best result keep the piping as short as possible Slant the piping at an angle to improve the flow Ensure the drain ...

Страница 10: ...z or 208 230V 1ø 60Hz TH FSC FSC FL FM FH L N FL FM FH L N L N L N L N FL Fan Low FM Fan Medium FH Fan High L Live N Neutral FSC Fan Speed Controller X1 X2 X3 Relay 220 240V 10A TH Thermostat FCU 1 FCU 2 FCU 3 FSC X2 X1 Chiller SH H M L N TH 220 240V 1ø 50Hz or 208 230V 1ø 60Hz TH X3 220 240V 1ø 50Hz or 208 230V 1ø 60Hz 220 240V 1ø 50Hz or 208 230V 1ø 60Hz TH FSC FSC SH H M L N SH H M L N L N L N ...

Страница 11: ...Hz or 208 230V 1ø 60Hz L N 3WV 3 way valve Field supply X1 X2 X3 Relay 220 240V 10A FCU 1 FCU 2 FCU 3 Note This is a proposed wiring connection It may change subject to the chiller unit and must comply with the local and national code and regulations Model Indoor FWPMM3A Z V1 FWPMM4A Z V1 FWPMM6A Z V1 FWPMM7A Z V1 FWPMM8A Z V1 Voltage Range Indoor 220V 240V 1Ph 50Hz or 208V 230V 1Ph 60Hz Power Sup...

Страница 12: ... C F Minimum indoor temperature 19 0 66 2 14 0 57 2 Maximum indoor temperature 32 0 89 6 23 0 73 4 All wires must be firmly connected Make sure all the wire do not touch the refrigerant pipings compressor or any moving parts The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage The power supply cord must be equivalent to H07RN F which is ...

Страница 13: ... or chemicals to clean the indoor unit 1 2 At least once every 2 weeks More frequently if necessary Indoor Fan Check for any abnormal noise 1 When necessary For any enquiries on spare part please contact your authorized dealer When any malfunction of the air conditioner unit is noted immediately switch off the power supply to the unit Check the following fault conditions and causes for some simple...

Страница 14: ...MEMO IM CCCW 0308 5 DK asean EN indd12 12 IM CCCW 0308 5 DK asean EN indd12 12 11 29 13 8 37 32 AM 11 29 13 8 37 32 AM ...

Страница 15: ...CVR IM CCCW 0308 5 DK asean ind3 3 CVR IM CCCW 0308 5 DK asean ind3 3 11 29 13 8 34 19 AM 11 29 13 8 34 19 AM ...

Страница 16: ...0 B 8400 Oostende Belgium Importer for Turkey Hürriyet Mahallesi Yakacık D 100 Kuzey Yanyol Caddesi No 49 1 2 Kartal İstanbul Head office Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo office JR Shinagawa East Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com global CVR IM CCCW 0308 5 DK asean ind4 4 CVR IM CCCW 0308 5 DK asean ind4 4 11 29 13 8 34 19...

Отзывы: